Edmonds - 650 Bell ST.docxComments
To:
VONS BELL ST - CHARLES VON GOEDERT
From:
Assistant Fire Marshal Karl Fitterer
Date:
Re:
BLD20181634 - 650 Bell St - 4 TOWNHOMES
Deferred Submittal Fire Sprinklers. Townhomes are considered R2 occupancies and are required a Fire Sprinkler System. A 13D flow through type is allowed and recommended.
Need to provide access to two sides of building. Alley will need to be signed and stripped to Fire Department Fire Lane Standards (attached) for compliance
Hydrant spacing is sufficient,but 4” Storz type fittings will be required to be installed on the hydrant in front of 632 Bell and the hydrant on the corner of 7th and Bell St. These
are the two hydrants required for fire flow for the construction of these townhomes.
Building addressing to be determined by the City of Edmonds. Individual unit designation to be determined by the owner.
Karl Fitterer CFI
Assistant Fire Marshal
City of Edmonds
Department of
Fire Prevention