PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: January 10, 2008
TO: Chris Amonson
TGB Architects
e-mail: camonson@TGBarchitects.com
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check # 2007-1214
Project: Edmonds Eye Surgery
th
Project Address: 21911 76 Ave W, #210
During re-review of the plans for the above noted project, it was found that the following
information, clarifications or changes are needed. Provide written responses to each comment and
where changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator.
1.Per our phone conversation and voice mail messages, medical gas will not be piped within the
suite, but portable canisters will be used. Revise plans and notes to reflect this change. Show
where the portable canisters will be stored (see enclosed copies from IFC) and note the types and
quantities of gases to be stored, including size and number of canisters for each gas. Please
contact John Westfall, Fire Marshal, at 425-771-0125 if you have any questions.