ENG20150490-Revision.pdf
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
10/26/1510/27/1510/27/1512/08/15
DATE
1
N/A
1/4
PAGE
SAP Sup Order Nbr
Drawing Number
CALL 811 AT LEAST 2 BUSINESS DAYS BEFORE YOU DIG
109092829 EDMONDS
109092829
N
office
425-505-3768425-424-6413425-424-6414253-405-2703425-766-1307N/AN/AN/A
N/A
PHONE NO
PURGE POINTS AND PRESSURE TAPS TO BE INSTALLED PER PSE GAS OPERATING STANDARDS 2525.3300, AND 2525.1200.
1"=20'
MAINS AND SERVICES SHALL BE TESTED AND PURGED PER PSE GAS OPERATING STANDARDS 2525.3300 AND 2525.3400.
NOTIFY PROPERTY OWNERS ADJACENT TO PROPOSED CONSTRUCTION ACTIVITIES A MINIMUM OF TWO WORKING DAYSTO PREVENT ACCIDENTAL OVERPRESSURE OF ADJOINING SYSTEMS, NO TWO MAINS SHALL BE CONNECTED
EXCEPT AS
EROSION AND SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE 0150.3200 TECHNIQUES FOR TEMPORARY
N/A
N/A
INSTALL MAIN VALVES OUT OF TRAFFIC WHERE POSSIBLE. VALVE MARKERS SHALL BE INSTALLED AND RECORDED BY Owner / Developer Contact Info
For contacts below dial 1-888-CALL PSE (225-5773)
PIPELINE MARKERS AND WARNING SIGNS SHALL BE INSTALLED AND RECORDED BY THE CONTRACTOR PER PSE GAS
PERMIT
NOT READILY ACCESSIBLE, AND FOR ALL VALVES WHERE PERSISTENT SNOWFALL MAY OBSCURE THE VALVE BOX.
SCALE
DELIVER FLYERS BE SURE TO INCLUDE THE LIST OF FREQUENTLY ASKED QUESTIONS AND INFORMATION ABOUT
PER GAS OPERATING STANDARD 2550.1600. ALLOW ADEQUATE TIME FOR CUSTOMER DECISION AND RESPONSE.
ANY CHANGE IN ROUTE, PIPE SIZE/TYPE, TIE-IN METHOD OR ADDITIONAL MAIN FOOTAGE MUST BE APPROVED BY
EXCESS FLOW VALVE TO BE INSTALLED ON ALL NEW RESIDENTIAL SERVICES PER GOS 2500.2200. (RECORD ALL
FIELD LOCATE ALL UNDERGROUND UTILITIES. EXCAVATOR TO CALL "ONE-CALL" TWO WORKING DAYS PRIOR TOTHE OPPORTUNITY TO PURCHASE AN EXCESS FLOW VALVE WHEN THEIR SERVICE IS INSTALLED OR REPLACED
COMPLETE "PIPE CONDITION REPORT" ON ALL METALLIC PSE FACILITIES. CHECK BOX ON REPORT FOR WIRE
THE CONTRACTOR PER PSE GAS OPERATING STANDARD 2525.2600 FOR ALL HP VALVES IF THE LOCATION IS
ALL CONSTRUCTION IS TO CONFORM TO PSE GAS OPERATING STANDARDS AND GAS FIELD PROCEDURES.
SHOWN ON THIS DESIGN UNLESS APPROVED BY APPROPRIATE PSE ENGINEER OR PSE REPRESENTATIVE.NOTE ALL ACTUAL FOOTAGE, LOCATION AND MATERIAL CHANGES ON THE AS-BUILT IN RED. ( ') DENOTES
PRIOR TO BEGINNING CONSTRUCTION. USE iSi TO DISTRIBUTE FLYERS IF JOB IS LARGE, OTHERWISE HAND
M. JANSSON
SITE
KEVIN ANSON
STANDARD GAS CONSTRUCTION NOTES:CONTACT
J. GUAY
MLOCK
T. LY
N/A
NOTIFY APPROPRIATE PERMITTING AGENCY PRIOR TO JOB START (SEE PERMIT REQUIREMENTS).
TO CONSTRUCTION, IN WESTERN WASHINGTON CALL: 1-800-424-5555. OR CALL NATIONWIDE: 811
EROSION AND SEDIMENT CONTROL AND ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
REAL ESTATE/EASEMENT
N/AN/AN/A
RESTORE ALL DRIVEWAYS SUBJECT TO OPEN CUT TO ORIGINAL OR BETTER CONDITION.
N/A
RETIREMENT
LENGTH OF
Vicinity Map
ACTUAL
PROJECT MGRAPPROVED BY
CP APPROVAL
JOINT FACILITIES ARRANGEMENTS
CHECKED BY
N/A
ENGR - GAS
2" STW IP MAIN REPLACEMENT
GAUGE AND MONITOR USE OF ALL STOPPERS TO ENSURE ADEQUATE FEED.
DRAWN BY
FUNCTION
16. IF METALLIC PIPE IS INVOLVED, COORDINATE INSTALLATION WITH CP TECH.MAPPING
ATTN:7529 BRAEMAR DR
N/A
N/AN/AN/A
EDMONDS, WA 98026
___________________________, PHONE______________.
RETIREMENT
LENGTH OF
SAP BATCH YEAR & FOOTAGE PROPOSED
Manufacturer
THE APPROPRIATE PSE ENGINEER OR PSE REPRESENTATIVE.
TESTED BYTESTED BY
WATERWATER
REVISE LINE OF MAIN ON BRAEMAR DR
159.070 & 159.069
N/AN/AN/A
109092829109092830108587104108587105
SYSTEM MAOP DENOTED BY: SYSTEM MAOP = ___ PSIG
SYSGGPM
Order #
GAS WK CTR
TESTED BY PSE PRESSURE CONTROL, SEE FORM 1928
60
425-766-1307
NITROGENNITROGEN
PLAT MAP
Act Lgth
ORIGINAL
GAS MAIN INSTALLATION/RETIREMENT
FF
YEAR
60 PSIG
GAS MAIN PRESSURE & TESTING
PP
DESCRIPTION
OPERATING STANDARD 2525.2500.
Est Length
BOX (TEST LEAD) INSTALLATION.
1100'1066'
FOOTAGE BETWEEN FITTINGS.
TEST RESULTSTEST RESULTS
ORIGINAL
INFORMATION ON D-4 CARD)
START TIMESTART TIME
JOB
AIRSTOP TIMEAIRSTOP TIMESYS MAOP
N/AN/AN/A
156.068
Notification #
Yes NoYes No
Project Manager Contact Information:
4
11153693Emer Sect
Type
MPE
KEVIN ANSON STW
OP MAP
BY ML
john.guay@pse.com
MATERIAL
RETIRED
SOAPSOAP
/ / / / / / / /
425-505-3768
Pipe Size
JOHN GUAY
60CONTACTPHONE#
UTILITIES
Service/MeterService/MeterService/MeterService/Meter10/28/16SW 8-27-4 & SE 7-27-4
SAP Superior
Dis. Reg. / FTSVC Retirement
Main Retirement
2"
DATE
2"HP Svc/MSA
Ind. ServicePSE
"Flagging Required"
"Locates Required"
PROJECT PHASE
SNOHOMISH
Ind. MSA
10.11.12.13.14.15.17.DESIGN PRESS
18.DESIGNED BY
1.2.3.4.5.6.7.8.9.
RETIRED
SIZE OF Type/Work
TYPE TESTTYPE TESTPRESSURE
PRESSURE
INSTALL
2023 03/10
MAIN DATE OFFDATE OFF
RETIRE Cell Phone:
DATE ONDATE ON
REV#
Manager:COUNTY
1/4 SEC
1
32
E-Mail:
GAS
MAINTAIN CATHODIC PROTECTION FOR STEEL MAINS BY THE USE OF CONTINUITY BONDS OR OTHER MEANS DETERMINED
INSIDE METER SETS SHALL BE MOVED OUTSIDE WHENEVER POSSIBLE OR SET REGULATORS AND VENTS OUTSIDE PER
INSTALL ANODES AND TEST LEAD WIRES AS REQUIRED PER PSE GAS FIELD PROCEDURES 4515.1000 AND 4515.1020 AND
INSTALL REPLACEMENT MAINS PER PSE GAS OPERATING STANDARDS 2525.2100 FOR INSERTIONS AND 2525.3600 FOR
INSTALL CURB VALVE AT PROPERTY LINE OR 5/8" PE WHIP AT MAIN (AS REQUIRED) ON NEW AND EXISTING SERVICES
MAINS AND SERVICES SHALL BE TESTED AND PURGED PER PSE GAS OPERATING STANDARDS 2525.3300, 2525.3400
INSTALL ONE POUND ANODE FOR EVERY 1000' OF LOCATING WIRE. INSTALL ANODE AND TEST LEAD WIRES PER PSENOTIFY PROJECT MANAGER IF ADDITIONAL DUPONT AND/OR STW MATERIALS ARE FOUND DURING CONSTRUCTION,
NOTIFY GAS CUSTOMERS, OR DISTRIBUTE FLYER #1443 A MINIMUM OF TWO WORKING DAYS PRIOR TO A PLANNED
PLUG ENDS OF DEACTIVATED OR INSERTED MAINS AND SERVICES IN ACCORDANCE WITH PSE GAS OPERATING
PSE GAS OPERATING STANDARD 2600.1200. TEST LEAD WIRES ARE REQUIRED ON ALL TRANSITION FITTINGS.
Completed post installation inspection per GOS 2525.1200 and 2525.2700.
REFER TO PSE GAS OPERATING STANDARD 2525.1700 FOR MAIN AND SERVICE COVER REQUIREMENTS.
(CHECK BOX TO CONFIRM COMPLETION)
REPLACE EXISTING ACTIVE SERVICES PER PSE GAS OPERATING STANDARDS 2525.2100 AND 2575.2300.
REMOVE OR RENDER INOPERABLE DEACTIVATED VALVES ON CASING WHERE MPE PIPE IS INSERTED.
Recorded all required information on the as-built per GOS 2500.1700.
REPLACEMENT CONSTRUCTION NOTES
Foreman's Name (printed) ___________________________________
Foreman's Signature________________________________________
Company: InfraSource Construction Date ______________
Inspected Steel and PE pipe per GOS 2450.1400 and 2450.1500
PROJECT MANAGER TO MAKE EGOR RUN IMMEDIATELY PRIOR TO STARTING CONSTRUCTION.
REPLACE ALL "NO RECORD" SERVICES AND 1-1/8" PE SERVICES INSTALLED PRIOR TO 1985.
KEY TO SERVICE ACTION
LEGEND
BY THE PSE CORROSION ENGINEER PER PSE GAS OPERATING STANDARD 2600.1300.
Reviewed and complied with all construction notes.
Left the work area in a clean and safe condition.
STANDARD IP & LP GAS
FOR MAIN DESIGNS REALIGNMENTS - FIELD DESIGNER
PROJECT CONTACT INFORMATION:
ALL DUPONT AND STW PIPES SHALL BE RETIRED PER SCOPE OF WORK.
FITTER'S CHECKLIST
PSE GAS OPERATING STANDARDS 2575.2300 AND 2550.1700.
AND 2525.1200, AND PSE GAS FIELD PROCEDURE 4700.1500.
#####
mark.jansson@pse.com
INCLUDING AT OR BEYOND THE CONNECTION POINTS.
david.lima@pse.com
john.guay@pse.com
ACTIVE SERVICES TO BE REPLACED DENOTED BY:T&TT&T###
MARK JANSSON
PER PSE GAS OPERATING STANDARD 2550.1600.
206-396-0691425-466-9047425-505-3768
JOHN GUAY
DAVID LIMA
4680 06/11
#
CONSTRUCTION QUESTIONS:#
GAS OPERATING STANDARD 2525.2300.
#
STANDARDS 2525.2100 AND 2525.3600.
ABANDONMENT OR DEACTIVATION.
SHALL BE CONTACTED:
FIELD NOTES:
BILLING QUESTIONS:
CONST MANAGER: CELL: EMAIL: FIELD DESIGNER: CELL: EMAIL: PROJ MANAGER: CELL: EMAIL:
OUTAGE.
10.11.12.13.
14.15.
1.2.
1.2.3.4.5.6.7.8.9.
SHEET 3
R
D
R
A
M
E
A
R
B
SCALE: NOT TO SCALE
AREA PLAN
RD
RA
MEA
RB
SHEET 2
R
D
R
A
M
LENGTH
E
A
R
B
DEPTH
173RD ST
HOLE HOG TABLE
LOCATION
76TH AVE W
STARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTARTSTART
ENDENDENDENDENDENDENDENDENDENDENDENDENDENDENDENDENDEND
CALLOUT
BP10BP11BP12BP13BP14BP15BP16BP17BP18BP19BP20BP21BP22BP23BP24BP25BP26BP27BP28BP29BP30BP31BP32BP33BP34BP35BP36
BP1BP2BP3BP4BP5BP6BP7BP8BP9
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES 12/01/1510/26/1510/27/1510/27/1512/08/15
DATE
1
N/A
2/4
PAGE
SAP Sup Order Nbr
Drawing Number
CALL 811 AT LEAST 2 BUSINESS DAYS BEFORE YOU DIG
EDMONDS
109092829
425-505-3768425-424-6413425-424-6414253-405-2703425-766-1307N/AN/AN/A
N/A
PHONE NO
1"=20'
N/A
For contacts below dial 1-888-CALL PSE (225-5773)
PERMIT
SCALE
M. JANSSON
KEVIN ANSON
CONTACT
J. GUAY
MLOCK
T. LY
N/A
REAL ESTATE/EASEMENT
N/AN/AN/A
N/A
PROJECT MGRAPPROVED BY
CP APPROVAL
Scale: N.T.S JOINT FACILITIES ARRANGEMENTS
CHECKED BY
BRAEMAR DR (STATION POINT 11+55)
ENGR - GAS
2" STW IP MAIN REPLACEMENT
DRAWN BY
FUNCTION
SECTION A-A MAPPING
7529 BRAEMAR DR
EDMONDS, WA 98026
REVISE LINE OF MAIN ON BRAEMAR DR
159.070 & 159.069
N/AN/AN/A
Scale: N.T.S.
SYSGGPM
DETAIL TIE-IN
GAS WK CTR
PLAT MAP
DESCRIPTION
A
1
N/AN/AN/A
156.068
Yes NoYes No
Project Manager Contact Information:
4
Emer Sect
OP MAP
ML
BY
john.guay@pse.com
1
425-505-3768
JOHN GUAY
CONTACTPHONE#
UTILITIES
10/28/16
SW 8-27-4 & SE 7-27-4
1
DATE
PSE
"Flagging Required"
"Locates Required"
SNOHOMISH
DESIGNED BY
Cell Phone:
REV#
Manager:COUNTY
1/4 SEC
1
32
E-Mail:
7510
7508
MATCHLINE A-A(SEE SHEET 3)
7
5
1
2
7515
7
5
1
4
7520SCALE: 1" = 20'-0"
PLOT PLAN
AA
1
9
2
5
7
7530
1
17400
IP GAS FLOW
29'
16'
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES 12/01/1510/26/1510/27/1510/27/1512/08/15
DATE
1
N/A
3/4
PAGE
SAP Sup Order Nbr
Drawing Number
CALL 811 AT LEAST 2 BUSINESS DAYS BEFORE YOU DIG
EDMONDS
109092829
425-505-3768425-424-6413425-424-6414253-405-2703425-766-1307N/AN/AN/A
N/A
PHONE NO
1"=20'
N/A
For contacts below dial 1-888-CALL PSE (225-5773)
PERMIT
SCALE
M. JANSSON
KEVIN ANSON
CONTACT
J. GUAY
MLOCK
T. LY
N/A
REAL ESTATE/EASEMENT
N/AN/AN/A
N/A
PROJECT MGRAPPROVED BY
CP APPROVAL
JOINT FACILITIES ARRANGEMENTS
CHECKED BY
ENGR - GAS
2" STW IP MAIN REPLACEMENT
DRAWN BY
FUNCTION
MAPPING
7529 BRAEMAR DR
EDMONDS, WA 98026
Scale: N.T.S
BRAEMAR DR (STATION POINT 17+60)
SECTION B-B
REVISE LINE OF MAIN ON BRAEMAR DR
159.070 & 159.069
N/AN/AN/A
MATCHLINE B-B
(THIS SHEET)
SYSGGPM
GAS WK CTR
PLAT MAP
DESCRIPTION
N/AN/AN/A
156.068
B
Yes NoYes No
Project Manager Contact Information:
4
Emer Sect
OP MAP
1
ML
BY
john.guay@pse.com
425-505-3768
JOHN GUAY
CONTACTPHONE#
UTILITIES
10/28/16SW 8-27-4 & SE 7-27-4
7
DATE
3
PSE
"Flagging Required"
9
"Locates Required"
3
SNOHOMISH
DESIGNED BY
Cell Phone:
REV#
Manager:COUNTY
1/4 SEC
1
32
E-Mail:
7
4
0
0
2047
7401
03
74
MATCHLINE B-B
B
(THIS SHEET)
5
1
4
7
B
5
2
4
7
SCALE: 1" = 20'-0"
PLOT PLAN
7
4
0
4
1
1
0
5
7
(SEE SHEET 2)
MATCHLINE A-A
3
0
5
7
7
0
5
7
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES 12/01/1510/26/1510/27/1510/27/1512/05/15
DATE
1
N/A
4/4
PAGE
SAP Sup Order Nbr
Drawing Number
CALL 811 AT LEAST 2 BUSINESS DAYS BEFORE YOU DIG
EDMONDS
109092829
425-505-3768425-424-6413425-424-6414253-405-2703425-766-1307N/AN/AN/A
N/A
PHONE NO
N.T.S.
N/A
For contacts below dial 1-888-CALL PSE (225-5773)
PERMIT
SCALE
M. JANSSON
KEVIN ANSON
CONTACT
J. GUAY
MLOCK
T. LY
N/A
REAL ESTATE/EASEMENT
N/AN/AN/A
N/A
PROJECT MGRAPPROVED BY
CP APPROVAL
JOINT FACILITIES ARRANGEMENTS
CHECKED BY
ENGR - GAS
2" STW IP MAIN REPLACEMENT
DRAWN BY
FUNCTION
MAPPING
7529 BRAEMAR DR
EDMONDS, WA 98026
REVISE LINE OF MAIN ON BRAEMAR DR
159.070 & 159.069
N/AN/AN/A
SYSGGPM
GAS WK CTR
PLAT MAP
DESCRIPTION
N/AN/AN/A
156.068
Yes NoYes No
Project Manager Contact Information:
4
Emer Sect
OP MAP
ML
BY
john.guay@pse.com
425-505-3768
JOHN GUAY
CONTACTPHONE#
UTILITIES
10/28/16
SW 8-27-4 & SE 7-27-4
DATE
PSE
"Flagging Required"
"Locates Required"
SNOHOMISH
DESIGNED BY
Cell Phone:
REV#
Manager:COUNTY
1/4 SEC
1
32
E-Mail:
SAP# 109092829
1
BYPASS MATERIALS
45
44
43
42
41
40
23
22
21
20
19
18
17
16
15
14
BOX COMPLETE 1" THRU 4" POLYVALVES9996260
1
13
BOX SUPPORT 2" POLYVALVE9996257
1
12
VALVE 2" MPE5600259
1
11
CAP 2" MPE5200649
1
10
8500930
CP WIRE #10 TEST LEAD
10'
9
3
6000484
8
CP TEST LEAD BOX COMPLETE5000307
2
7
TRANSITION FITTING 2"7800809
1
6
CAP 2" WELD5200675
1
5
6000500
1
4
STOPPER 2" X 150 STD H-17160 B/O7600741
1
3
PIPE 2" MPE STRAIGHT7000263
20'
2
WIRE #14 TRACING8500940
1100'
1
1100'
PIPE 2" MPE COIL7000261
QTY
ITEMDESCRIPTIONPART NO.
BILL OF MATERIAL