Utility Engineer Comments:
9/3/19 Comments Addressed.
9/20/19 Comments on revised plan:
1. Plans are not stamped and signed by an engineer.
2. All pipe needs to be CL 52. Called out as CL 50.
Need callouts for required vertical bends (degree of bend, vertical blocking needed, etc) that are
required for the fittings under the RPBA pad.
4. Add note to plans: "PreConstruction meeting between City's Utility Engineer, Contractor and
their consultant to determine coordination of RPBA pad in relation to City's Meter Vault is
required."