Loading...
EngineeringMemo_06-04-08.pdfDate: To: From: Subject: MEMORANDUM June 4, 2008 Gina Coccia, Planner Ed Sibrel, Engineering Technician PLN20080037, Reimer, 3 -Lot Short Plat 8805 — 220 St SW The comments provided below are based upon review of the Preliminary Plans for the subject short plat. Additional information is requested from the applicant at this time in order to continue review of the application and provide preliminary approval of the short plat. The applicant will be required to submit civil engineering plans to the City for review and approval after receiving preliminary short plat approval from the Planning Division. Please ask the applicant to revise and resubmit a Preliminary Short Plat Plan addressing each of the comments below: 1. The overhead utilities for Lot 2 that cross over Lot 1 must be underground. 2. The proposed storm drainage system shows a force main within the City right-of-way. Please terminate force main on private property, and convey the water to the City storm system via gravity, or show cause how this cannot be accomplished. 3. The sanitary sewer system is owned by the Olympic View Water and Sewer District. The District must approve the plans prior to City approval. 4. Please provide distance (ground, not straight-line) from SW corner of Lot 3 to nearest fire Hydrant. Thank you. City of Edmonds