REQUEST FOR ADDITIONAL INFORMATION
Date: September 6, 2019
To: Amber Groll, Planning Division
From: JoAnne Zulauf, Engineering Division
Subject: PLN20190036, Sundstone 2 lot short plat
1414 9t' Ave N
The comments provided below are based upon review of the preliminary civil plans &
documents for the subject short plat. Additional information is requested from the applicant
at this time in order to continue review of the application and provide preliminary approval of
the short plat. Please ask the applicant to provide a written response to each of the comments
below and revise and resubmit plans accordingly.
GENERAL
1. There is an existing access easement provided for this property. Please provide the
reasoning for preferring to access Lot 2 from 91h Ave. Are there challenges with the
access?
2. In accordance with Edmonds Community Development Code (ECDC) Chapter 18.90,
sidewalks are required as a condition of short plat approval.
a. Sidewalks are required on 9th Ave but only on one side of the road. Since the
existing sidewalks are on the west side of 9th Ave at this location, no additional
sidewalk is required.
b. Puget Drive is an arterial and per the Comprehensive plan Street Tree Plan shall
have street trees. The Puget Dr frontage shall have 4 ft wide landscape strip with
street trees and a 5 ft sidewalk. The street trees shall be installed at 40 ft on center.
Please resubmit plans showing the proposed sidewalk and landscape strip with
dimensions. Indicate the location of the street trees.
c. The curb ramp will not need to be replaced unless it is damaged. If it is damaged,
it will need to be replaced to today's WSDOT standards.
3. Driveway area in the right of way shall be positioned perpendicularly to the property line,
shifting or widening can be done once on private property.
City of Edmonds
UTILITIES
1. Provide approximate invert elevations for side sewer at house, property line and new
connection to main to show feasibility. Call out length and size of all pipe to verify slopes.
2. Show location of existing utility connections to existing condo building.
3. If a fire sprinkler system is required for the proposed single-family residence, the water
service to the property will need to be larger than what's proposed. Typically a 1" meter
and 1 1/2" water service line provides sufficient flow. While the water meter will not be
issued with the subdivision, the water tap will be installed by City crew. A note
indicating a 1" meter will be sufficient to notify the water division of the size of tap
needed. Revise plans accordingly.
STORMWATER ENGINEER REVIEW
Refer to attached plan review comments by City Stormwater Engineer, Zachary Richardson.
Please contact Zack directly at 425-771-0220 or by email at
zachary.richardson(&edmondswa.2ov with any specific questions you may have regarding his
comments.
Thank you.