Field inspection report.pdfO tOA 3/15/19 UPSTATE 1engineering PO BOX 952 LYNNWOOD, WA 98046 T. (206) 280-4715 F. (206) 834-6261 SERVICES@UPST8.COM March 14, 2019 John Murphy Murphy Building Co. 6203 202"d Street SW Lynnwood, WA 98036 Re: Upstate Job#0719 O'Neal Residence Foundation Wall Revision To Whom It May Concern: The following issues were brought to our attention subsequent to a recent inspection by the Building Department: 1. The beam along the north side of the rear patio roof was hung from its post rather than bearing on top of the post. The hanger used, HUCQ5.25/12, is structurally adequate to carry the required loads. No retrofitting should be required. 2. The shear wall between the den and the powder room has perforations along the top plate to allow for HVAC. This wall is responsible for resisting 150 PLF lateral load (p. 5.1 house lateral calcs) or 10'x150 PLF = 1500 lbs. The perforations in the shear wall leave us with approximately 4'- 6" of shear transfer length. 15001bs/ 5351bs/A35 = 2.8. Install a minimum of (3) A35 clips from floor framing to double top plate within the 4'-6" of undisturbed shear wall. No further retrofitting should be required. Should there be any questions or comments please contact our office. Sincerely, rA2 Andrew Gahan, PE 15/7 019