Field report.pdfSSSSOUND STRUCTURAL SOLUTIONS E N G I N E E R 5 OLD 1,0 Ld o(oeq 8/10/2018 To: Todd Cliggott Westerly LLC From: Easton Wright, EIT Re: Brackett's Corner Lots 9 & 13 8000, 8010 212st — Edmonds, WA SSS# s1512023 During plumbing installation, 4" diameter holes were drilled in floor joists (1-0) over the garage. These holes were drilled less than the minimum edge distance allowed. Two LVL members and a strap shall be installed at the hole to resist the bending and shear forces due to the reduced section caused by the hole. See the attached partial plans, hand calculations, and detail. If you have any questions or require additional information, please call. Attached: Partial Plans (2) Calculations (3) Detail (1) 24113 Wh Ave W - Mountlake Terrace, WA 98043 - Ph: 425-778-1023 - www.ssseng.com 1%x5yLVL B-B TY4).j2x12 JOIST SECTION A -A N.T.S. T-2" MIN 2" STAGGER OPPOSING SIDES SECTION B-B - TOP VIEW ELEVATION .... I „ 11 ..1 (13) -10d FASTENERS EA SIDE OF HOLE 1%x5yLVL EA SIDE (2) #SDSY4" x 4Y2" @ 4" oc E.S. STAGGER OPPOSING SCREWS 3�M 6X6 w/ #PCZ @TOP FIRST FLOOR SHEARWALLS & FRAMING ABOVE BUILDINGS 5, 9 1/4" = P-O" DO NOT SCALE - REFER TO ARCHIPECTURAL SHEETS FOR DIMENSIONS �- 02.5 @ EACH RAFTER BEARING *HW J I t- 4X4 IGNGPOSI wl *PC2 @ TOP #PU INVERTED @ Bi I - #HUC 1 , #HUC 2-TRIMMERS C BE uAE RCS MAX HEIGHT OF RaFRAMED MSHALLBET-6" WALL*HUC #HUC #HUCQ SHALL BE 5' 6" *HUCQ #PCZ@TOP 4X12(1.3) 5/xllyPSL(1-1) 3� *ABU@ BASE I *HU #HU 4x12 L2)- I Kf t I I tHT - SW tHfT SW I �w 4X6 w/ sPCZ@TOP r 1 E33 4X12 COLLECTOR E33 *ABU@ BASE *H * SW 3 *HTT E33 M 5v IX12COLLECTOR LANDING: 08 DROPPED 2Xl�la 16' a b / 1 (1-8) P HANGER I I ?� $1I I TO POST �ia *STHD14 3�M Q �itq I 2.2X12 (I.9) 04 w/ roP GARAGE BASE 2X12 @ 16" oc TYP U.N.O. 2X12 @ 12" a (1-0) �a III T-pn p �a Hole Location 2.2X12(1. 1 Sw 4X12COLLECMI.12) A6 GREAT ROOM P ALLTR Y �Q KITCHEN X �c------------------- ________ D2 xSTHD19 *ST6224 3X X 11y LSL (1-13) HEADER TO *STHD14 *ST6224 tSTH014 STUDS HEADER TO STUDS 2-TRIMMERS D2 FIRST FLOOR SHEARWALLS & FRAMING ABOVE 1/4" = 1'-0" BUILDINGS 11,13 DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS SOUND STRUCTURAL SOLUTIONS sss L� E N G I N E E R 5 5v A.l 2,36 q"��*12" V V v Ph:425-778-1023 - www.ssseng.com t r SOUND STRUCTURAL SOLUTIONS E N G I N E E R 5 2.5 Ph:425-778-1023 - www.ssseng.com SOUND STRUCTURAL SOLUTIONS 4; SSS] E N G I N E E R S sl�f2�Ia3 L! Aii& pk 1-2 Ph: 425-778-1023 - www.ssseng.com