Fire Comments 2.docx
Eagle Eye Consulting Engineers, P.S.
PO Box 523
Olalla, WA 98359
hoytjeter@centurytel.net
360 874 0562
Fax 360 874 0591
To: Steve Adamson
Columbia Fire
st
1534 1 Ave S
Seattle, WA 98134
Re: Edmonds Yacht Club
326 Admiral Way
Edmonds, WA 98026
Plan Review # 2009-0579 EECE # EDM09-14 (2)
Second Comment Letter
The above referenced project is in the process of plan review for compliance with
Edmonds
ordinances and applicable codes. The following comments,
deficiencies/corrections must be addressed prior to completion of plans review and
subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items
listed below to facilitate a shorter back-check time.
SCOPE OF REVIEW
Automatic Fire Sprinkler System
The scope of this review is for therequirements of this
project.
All features were checked only to the extent allowed by the submittals provided. All
portions of this project are assumed to meet or will meet other departmental requirements,
conditions and concerns before permit approval.
Page 2 of 3
Plan Review Number 02
EECE#: EDM 09-14 (2)
Edmonds Yacht club
2009-0579
SPRINKLER COMMENTS
General
1.The hydraulic calculations for this project were not submitted. The plan has been
reviewed without the calculations but they must still be submitted for final approval.
IFC 105.4, IFC 901.2, NFPA 13, 22.3
Columbia fire attached hydraulic calculations to email and sent to City of Edmonds.
OK
Sheet 3
2.Riser detail: Provide a gauge below the backflow prevention valve. NFPA 13,
7.1.1.1
Columbia Fire added Gauge below backflow.
This appears not to be added to the drawings as noted in the response.
3.Main Floor: Provide a four-way brace at the change of direction on the main
located near grid D-6. This will serve as a longitudinal brace for the segment of the
main which runs parallel with gridline D and as a lateral brace for the section of
main which runs parallel with gridline 6. Additionally, provide a lateral brace at the
right end of the main which runs parallel with gridline 6. NFPA 13, 9.3.5.3 and
9.3.5.4
Columbia fire added all additional EQ as directed.
Additional details are not added to addresses the required bracing. Please revised
and resubmit.
4.Sprinkler Information Chart: Adjust the sprinkler head count for the dry sidewall
sprinklers to reflect the actual number of heads shown on the plans. (5) NFPA 13,
22.1.3
Columbia fire adjusted sprinkler head count to 5 dry sidewalls.
This information is not shown on the resubmitted drawings.
5.Upper Floor: Provide a longitudinal brace within 40 feet of the upper end of the
main located along gridline D. NFPA 13, 9.3.5.4
Columbia fire added additional EQ as directed.
This information is not shown on the resubmitted drawings.
Page 3 of 3
Plan Review Number 02
EECE#: EDM 09-14 (2)
Edmonds Yacht club
2009-0579
Additional corrections may be required following receipt of corrections and
additional information as requested.
Your plans are being reviewed concurrently with the Building Department, Fire
Department, Zoning Department and Public Works Engineering. Changes,
clarifications or additional corrections may be required subsequent to the Building
Department plan review when comments are received from the other concerned
departments.
Should you have any inquiries regarding this letter, please contact Hoyt Jeter at
(360) 874-0562 between 8:00 a.m. and 5:00 p.m.
By:
Hoyt Jeter, P.E.
President