Fire Comments McDonald's 10124 Edmonds Way.doc
Serving the cities of Brier, Edmonds, Mountlake Terrace,
and the Town of Woodway
MEMORANDUM
:
DATE May 21, 2013
:
TO File
:
FROM Mike Smith, Edmonds Fire Inspector
:
SUBJ Plan Check/McDonald’s 10124 Edmonds Way
Your plans have been reviewed under the 2009 IFC and the ECDC with the following comments:
1) Check with Olympic View Water for approval on the fire line, tap, vault and DCDA.
They are the water purveyor and have authority over the installation. I have no issues with the
submittal.
2) Fire Sprinkler, Life Safety Plan and Fire Alarm permits are deferred.
A fire alarm is required for fire sprinkler monitoring, type 1 hood suppression monitoring, off site
monitoring and audible/visual alarms in the building.
3) Portable Fire Extinguishers for the building and kitchen are required and can be included in the
Life Safety Plan.
4) It appears the Sprinkler Riser room is in the janitor’s closet next to the entry/exit on the East side
of the building. Please label as such.