Fire Notes Pre20160002.pdf'FUR DST CITY OF EDMONDS FIRE PREVENTION SERVICES 3/28/2016 DRC PRE20160002, Madrona K-8, Edmonds School District The following is a list of requirements for this project: 1. Need type of construction to determine fire flow requirements, IFC appendix B. 2. Fire access roads to be determined. IFC Section 503. 3. Type and size of private water mains, fire hydrants, including DCVA appliances and vault as required by Olympic View Water and Wastewater District. 4. Automatic sprinklers as required by Section 902.3. 5. Fire Alarm/Emergency voice communications system as required Section 907.2.3. 6. Hydrant located within 50' of FDC. PIV required. 7. Premise identification (address) Section 505. 8. Building access Section (key box) 506. 9. Emergency responder radio coverage Section 510. 10. Emergency and Standby Power Systems Section 604. 11. Fire lane markings Section 505.5 (Edmonds standard) 12. Commercial Cooking Type I or II hood system, if required Section 609. Please contact me if you have any questions: Kevin Zweber Acting Deputy Chief - Fire Marshal Fire Prevention Services Snohomish County Fire District 1 Proudly Serving the Cities of Brier, Edmonds, and Mountlake Terrace 425-771-0213 Office 12425 Meridian Avenue S / Everett WA 98208 / 425-551-1200 www. fire district 1.org