Fire Notes Pre20160002.pdf'FUR
DST
CITY OF EDMONDS
FIRE PREVENTION SERVICES
3/28/2016
DRC PRE20160002, Madrona K-8, Edmonds School District
The following is a list of requirements for this project:
1. Need type of construction to determine fire flow requirements, IFC appendix B.
2. Fire access roads to be determined. IFC Section 503.
3. Type and size of private water mains, fire hydrants, including DCVA appliances
and vault as required by Olympic View Water and Wastewater District.
4. Automatic sprinklers as required by Section 902.3.
5. Fire Alarm/Emergency voice communications system as required Section
907.2.3.
6. Hydrant located within 50' of FDC. PIV required.
7. Premise identification (address) Section 505.
8. Building access Section (key box) 506.
9. Emergency responder radio coverage Section 510.
10. Emergency and Standby Power Systems Section 604.
11. Fire lane markings Section 505.5 (Edmonds standard)
12. Commercial Cooking Type I or II hood system, if required Section 609.