Loading...
FIRE REVIEW NUMBER TWO.docxReviewed X2: Approved. A residential fire sprinkler system is required. A recommended flow-through design will meet specifications and reduce equipment and continuing maintenance requirements. ECDC19.05.020B2. Provide a minimum combination water service of one inch (1”) meter and one and one half (11/2”) service line, or show that domestic and fire protection needs can be met with a smaller service. The covered porch and covered stairs are included which puts this project over the 3000 square foot threshold. Also the upper floor calculates out to 920 instead of the 785 when we include "Fire Area". Approved: DFM17