Fire Stopping Assemblies for 2008-0463, 64 and 65.pdfRECEIVED
&NA&IJ JAN,� 9 201�i
PERMIT COUNTER
LANDSVERK QUALITY HOMES, INC.
21118 66" Ave. W. Lynnwood WA 98036
Offlce 425-742-2742
Fax 425-673-6373
1/27/10
To: Russ Steinike
C.O. Edmonds
From: Stan Little
Landsverk Quality Homes
RE: Sunset Condominiums 2oo80463, 64 and 65
Listed and Tested Fire Stopping Assemblies
Attached you will find the product data for the listed and tested fire stopping assemblies.
UL/cUL SYSTEM NO. l
METAL PIPE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL
TOP "VIEW
' d a
0.4
AA
d.
v
v a
d
.Q
dd
'a
4 d
a d
'a
o
L -RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT.
L -RATING AT 400° F = 4 CFM/SQ. FT.
SECTION A -A
1. CONCRETE FLOOR OR WALL ASSEMBLY (3 -HR. FIRE -RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-112'° THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. [OPTIONAL] ANY OF THE FOLLOWING STEEL SLEEVES MAY BE USED:
A. MAXIMUM 32" NOMINAL DIAMETER STEEL PIPE SLEEVE (SCHEDULE 40 OR HEAVIER) MAY EXTEND
MAXIMUM 3" ABOVE FLOOR OR BEYOND BOTH SURFACES OF WALL.
B. MAXIMUM 6" (MIN. 26 GA.) OR 12" (MIN. 24 GA.) DIAMETER GALVANIZED STEEL SLEEVE WITH
SQUARE FLANGE SPOT WELDED TO BOTTOM OF SLEEVE AND SIZED MINIMUM 2" LARGER THAN
SLEEVE DIAMETER. SLEEVE MAY EXTEND MAXIMUM 1" ABOVE TOP SURFACE OF FLOOR.
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING:
A. MAXIMUM 30" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 30" NOMINAL DIAMETER CAST IRON PIPE.
C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE.
D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT.
E. MAXIMUM 4" NOMINAL DIAMETER EMT.
4. MINIMUM 4" THICKNESS MINERAL WOOL (MINIMUM 4 PGF DENSITY) TIGHTLY PACKED AND RECESSED
TO ACCOMMODATE FIRESTOP SEALANT.
5. MINIMUM 114" DEPTH HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT FLUSH WITH TOP SURFACE OF
PIPE SLEEVE OR FLOOR ASSEMBLY.
6. MINIMUM 114" BEAD HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT.
NOTES:1 • OF OPENING
2. ANNULAR
• • ! MINIMUM 0", MAXIMUM
DEPTH3. MINIMUM 1/4" FS -ONE FIRESTOP
*• ! !
REQUIRED ON BOTH SIDES OF 1 1.. ASSEMBLY.
4. PIPE ! i. INSTALLED POINT CONTACT.
Sheet 1 of 1 Drawing No.
HILTI, Inc. Scale 5/64"=1" VMJ
Tulsa, Oklahoma USA (918) 252-6000
FIRESTOP SYSTEMS Date Sep.14, 2005 1226k
Saving Lives through Innovation and Education
UL SYSTEM NO. C -AJ -2109
PLASTIC PIPE THROUGH FLOORMALL OR BLOCK WALL ASSEMBLY
F -RATING = 2 -HR. OR
T -RATING = 0 -HR., OR
co
C�
W -RATING = CLASS I (SEE NOTES NO. 6 AND 7 BELOW)
BOTTOM VIEW
A
4
4
< �16 4
Tllc=� Sheet I of 2 Drawing No.
HILTI, Inc. Scale 3/16" =1" CAJ
Tulsa, Oklahoma USA (800) 879-8000
Hilti Firestop Systems 11 Date Aug. 01,2006 11 210p
Saving Lives through Innovation and Education
UL SYSTEM NO. C -AJ -2109
144
R-
., OR •
W -RATING = CLASS
NOTES! 6 AND 7 BELOW)
1. CONCRETE FLOOR OR WALL ASSEMBLY (2 -HR. OR 3 -HR. FIRE -RATING):
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-112" THICK).
B. ANY UL
CLASSIFIED CONCRETE BLOCKWALL.
2. [OPTIONAL] MAXIMUM 12" NOMINAL DIAMETER STEEL PIPE SLEEVE (SCHEDULE 40 OR HEAVIER).
3. PENETRATING ITEM TO BE ONE OF ! ! (ALSO SEE NOTER !
A. MAXIMUM
10" NOMINAL DIAMETER PVC PLASTIC (CELLULAR OR SOLID R•
B. MAXIMUM 10"• , +(CLOSED PIPING SYSTEM !
C. MAXIMUM 6" NOMINAL DIAMETER ABS PLASTIC PIPE (CELLULAR OR SOLID CORE).
D. MAXIMUM NOMINAL i, ... PLASTIC PIPE.
4. MINIMUM 1/2" DEPTH HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP 601S ELASTOMERIC
FIRESTOP SEALANT OR HILTI CP .04SELF LEVELING FIRESTOP SEALANT INSTALLED FLUSH WITH TOP
OR BOTTOM + OF FLOOR.
5. HILTI CP 643N OR CP 644 FIRESTOP COLLAR WITH FASTENING HOOKS (SEE TABLE BELOW).
BOLTS, MIN. 0.145" x 1-1/4" POWDER ACTUATED FASTENERS WITH 1-7116" DIAMETER STEEL WASHER,
!N 11+ CONCRETE SCREW ANCHOR, :R
EXPANSION ANCHOR,
R. R.P8 S1 5 POWDERACTUATED FWITHASTENER
INTEGRATED
NOMINAL PIPE
DIAMETER
PRODUCT
DESCRIPTION
NO. OF FASTENING
HOOKS
MAXIMUM HOLE
SIZE
F -RATING
1-1/2"
CP 643 50/1.5" N
2
2-1/8"
3
2"
CP 643 63/2" N
2
2-5/8"
3
3"
CP 643 90/3" N
3
4"
3
4"
CP 643110/4" N
3
5"
3
6"
CP 643 160/6" N
4
7"
3
8"
CP 644 20018"
10
10"
2
10"
CP 644 250/10"
12
12"
2
NOTES 1. HILTI FIRESTOP COLLARS AND FIRESTOP SEALANT ARE REQUIRED ON BOTH SIDES OF A
WALL ASSEMBLY.
2. ANNULAR SPACE ON PIPES NOMINAL 6" AND SMALLER = MINIMUM 0", MAXIMUM 1/2".
3. ANNULAR SPACE ON PIPES LARGER THAN NOMINAL 6" = MINIMUM 0", MAXIMUM 1-1/4".
4. CLOSED OR VENTED PIPING 1: : FRPP = SCHEDULE ,i CPVC = SDR
INSTALLED5. HILTI FIRESTOP SEALANT IS OPTIONAL ON PIPES HAVING A MAXIMUM DIAMETER OF
NOMINAL 6" 1 OPENINGS.
6. W -RATING DOES NOT APPLY IN SLEEVED OPENINGS.
7. W -RATING APPLIES ONLY WHEN THE PIPE DIAMETER IS 6" OR SMALLER, ANNULAR SPACE
IS MINIMUM 1 . ANDHILTI CP 60 . R• SEALANT OR
HILTI CP 604 SELF LEVELING FIRESTOP SEALANT IS USED.
co
0
0
00
0
rn
0
N
Q
U
Sheet 2 of 2 Drawing No.
HIL.TI, Inc. Scale _ AJ
Tulsa, Oklahoma USA (800) 879-8000
Hilti iFireStop Systems Date Aug.01,2006 2109p V9
Saving Lives through Innovation and Education