PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: April 30, 2007
TO: Walt Joyce
E-mail:
FROM: Ann Bullis, Assistant Building Official
RE: Deferred Submittal for Permit #2006-0563
Project: KUPC Fire Stopping
th
Project Address: 8505 240 St. SW
During review of the deferred submittal for the above noted project, it was found that the following
information, clarifications or changes are needed. Please submit revised documents to Marie Harrison,
Permit Coordinator.
1.We have received the product information submitted for 3M CP 25WB + Caulk, but still need the 1-hour
listed and tested fire stopping assemblies for each type of penetration (such as for metal pipe, plastic
pipe, cable, metal ducts, etc.) from the UL Fire Resistance Directory or 3M Fire Stop Manual. Please
provide 2 copies for review.
The Fire Barrier Moldable Putty product data submitted references UL System CAJ 3021 for cables
through a concrete wall. A copy of this system has been made from the UL Fire Resistance Directory
for use/reference in the field, and will be attached to the fire stopping documents when the additional
information noted above is provided.