FirestoppiingDeferred2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: April 30, 2007 TO: Walt Joyce E-mail: FROM: Ann Bullis, Assistant Building Official RE: Deferred Submittal for Permit #2006-0563 Project: KUPC – Fire Stopping th Project Address: 8505 240 St. SW During review of the deferred submittal for the above noted project, it was found that the following information, clarifications or changes are needed. Please submit revised documents to Marie Harrison, Permit Coordinator. 1.We have received the product information submitted for 3M CP 25WB + Caulk, but still need the 1-hour listed and tested fire stopping assemblies for each type of penetration (such as for metal pipe, plastic pipe, cable, metal ducts, etc.) from the UL Fire Resistance Directory or 3M Fire Stop Manual. Please provide 2 copies for review. The Fire Barrier Moldable Putty product data submitted references UL System CAJ 3021 for cables through a concrete wall. A copy of this system has been made from the UL Fire Resistance Directory for use/reference in the field, and will be attached to the fire stopping documents when the additional information noted above is provided.