FW Salish Crossing Comments.htm
From: John J. Westfall
Sent: Monday, February 25, 2013 5:27 PM
To: 'Alexander Thomson'
Cc: Michael J. Smith; 'Bjorback, Leif'
Subject: FW: Salish Crossing Comments
Attachments: 2013_2_22_SALISH_CENTER_FIRE_MARSHALL_REVISIONS.pdf
Alexander:
Looks great. Fire has approved with corrections.
Will you resubmit new sheet with other departmental corrections made to rest of set?
Thank you,
John J. Westfall
Fire Marshal
Fire Prevention Services
425-771-0213 Desk
425-775-7721 Fax
425-231-3644 Mobile
This image cannot currently be displayed.
From: Alexander Thomson \[mailto:athomson@j-arch.com\]
Sent: Friday, February 22, 2013 4:56 PM
To: John J. Westfall
Subject: Re: Salish Crossing Comments
Hi John,
Please disregard the last Fire Access Plan SHEET A1.4 I sent you at 3PM Friday 2/22/13. Please
find the new revised Fire Access Plan Sheet A1.4 attached. The fire lane has been moved to be
closer to the building to be located in the 24' wide drive lane. At the Northwest terminus of the
fire lane, the turning radius from the 19' wide drive asile is equal to the turning radius of the 24'
asile. Also the move closer to the building would allow us more flexibility in the Northeast
corner of the site for future development. This adjustment from the plan we discussed earlier this
week should be fine because it 1. Moves the Fire Access Lane closer to the building and 2.
provides a wider drive asile. Please let us know if this will work.
Thank You
--
Alexander Thomson
J O H N S O N
A R C H I T E C T U R E
& P L A N N I N G L L C
2124 Third Avenue, Suite 200
Seattle, WA 98121
(206) 448.7580 x18
T:
(206) 448.8977
F:
On Thu, Feb 21, 2013 at 12:20 PM, John J. Westfall <jwestfall@firedistrict1.org> wrote:
Hi Alexander:
Your email was already in my system here.
Per our discussion and FD requirements, please make following changes to Sheet A1.4
1)Call out two PIVs on exterior of building(s). For A: It is approx. 30’ from SW corner of
building behind gated fence. We will be deconflicting and landscaping in the gray box for access
purposes. For B: It is approx spaces 8-9 (at Laundromat) on sidewalk.
2)Delete two FDCs called out to the north on Sunset. Only one FDC feeds both sprinklers, that
is at the intersection of Sunset and Dayton.
3)Revise note “150’ “ instead of “ 300’ “.
4)Extend Fire Lane striping along outer parking area around corner to James St entry.
5)FIRE LANE-NO PARKING words to be painted on the pavement inside the lane. Letters to
be a minimum of 12” high, 2” stroke, yellow in color and alternatively spaced every 50 feet.
Perimeter of fire lane striped to 4” yellow.
Let me know if questions.
John J. Westfall
Fire Marshal
Fire Prevention Services
425-771-0213 Desk
425-775-7721 Fax
425-231-3644 Mobile
This image cannot currently be displayed.