EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: February 25, 2010
To: File
From: Mike Smith Fire Inspector
th
Subject: Pre App Pre School 18530 76 Ave W
I spoke with Kathleen Graham (applicant) on the phone requesting more information.
The pre school will be licensed for 20 children ages 3 to 6. At present the school will
share the building with the current tenant.
The FD has the following comments:
1) Since the building will be shared with a “B” and an “E” occupancy the IBC Table
508.3.3 calls for a two hour separation that may be required between the occupancies.
2) Portable fire extinguishers will be required, minimum size 2A10:B:C. Total number
will be called out when the T/I permit is reviewed.
3) Post Exit Signs and Emergency Lighting at all exits.
th
4) Address must be posted on building and be clearly visible from 76 Ave W.
5) Floor Plan showing emergency exit routs must be posted in the main entrance and
else where if needed.
The FD may have additional comments as the project progresses.