hadfieldgeotech.pdfMarch 10, 2006 File No. 05-155 Mr. Carter Woollen, AIA Woollen Studio He 5339 Ballard Avenue NW Seattle, WA 98107 ED F 2 2446 EECE _. DOI EDM 06-18 F�inGE@ C O R P O R A?■ O Geotechnical a Earthquake Engineering Consultants Subject: Geotechnical Engineering Report 506 -- 6t" Avenue South, Edmonds, Washington 98020 Dear Mr. Woollen, RECEIVED APR I 1 £ 006 PERMIT COUNTER As requested, PanGEO Inc. completed a geotechnical engineering study to assist you and your designers with the design of the two new single family residences to be constructed at 506 6th Avenue South. This study was performed in accordance with our mutually agreed upon scope of work as outlined in our proposal dated September 6, 2005. Our service scope included reviewing readily available geologic data, drilling three test borings, and developing the conclusions and recommendations presented in this report. PROJECT AND SITE DESCRIPTION The site is located just southeast of downtown Edmonds, at the approximate location shown in Figure 1. The site is currently vacant, although we understand that a single family residence with a basement (finish floor elevation 131.5 feet) was removed from the eastern portion of the site prior to our involvement. The property is bordered on the south by Holly Drive, on the east and west by sinve-family residences, and on the north by an apartment building and the cul-de-sac for 6 Avenue South. The site measures approximately 100 feet in the north -south direction and approximately 120 feet in the east -west direction. Plate 1. Looking northeast from southwest corner of site The majority of the site slopes down to the west at grades of about 10%, as shown on Figure 2. There is an existing rockery along the west end of the property with a maximum height on the order of 3 feet. We understand that you plan to subdivide the lot and build two single-family residences. Both houses will have three floors, including a basement, and anticipated to be conventional wood -frame structures. 3414 N.E. 55u' Street Seattle, WA 98105 (206)262-0370 FAX (206) 262-0374 Mr. Carter Woollen Hadfield Residence March 10, 2006 The eastern (upslope) house will have a finish floor elevation of about 125.5 feet. With the existing ground surface at about Elev. 138 feet, up to about 14 feet of excavation will be needed along the east building line to facilitate the footing construction. Because the new house will be setback about 12 feet from the east property line, limited space is available for an open excavation. The western house will have its lowest floor at Elevation 123 feet, approximately snatching the existing grade along the west property line. Therefore, the amount of excavation for the west house is considered relatively minor. SUBSURFACE EXPLORATIONS Three borings H-1 through BH -3 were drilled at the site on October 1 2 g CB g ) 0, 005 to explore the subsurface conditions. The approximate boring locations are indicated on Figure 2. The borings were drilled to depths of approximately 161/2 to 24 feet below the existing ground surface, using a portable drill rig owned and operated by CN Drilling of Seattle, WA. The drill rig was equipped with 4 -inch outside diameter hollow stem augers. Soil samples were obtained from the borings at 2%2 -foot intervals using Standard Penetration Test (SPT) sampling methods. SPT samples are obtained using a 2 -inch outside diameter split -spoon sampler, driven into the soil a distance of 18 inches using a 140 -pound weight failing a distance of 30 inches. The number of blows required for each 6 -inch increment of sampler penetration was recorded. The number of blows required to achieve the last 12 inches of sample penetration is defined as the SPT N -value. The N - value provides an empirical measure of the relative density of cohesionless soil, or the relative consistency of fine-grained soils. An engineer from PanGEO was present during the field exploration to observe the drilling, assist in sampling, and to describe and document the soil samples obtained from the borings. The soil samples were described using the system outlined on Figure 3, and summary logs are included as Figures 4 through 6. SUBSURFACE CONDITIONS According to mapping by Booth, Cox, Troost, and Shimel (Draft Geologic Map of Sno- King Area, 2004), the site is underlain by Pre -Fraser Deposits. Our exploratory borings advanced at the site appear to have encountered a different geologic sequence. The soil conditions encountered in our explorations generally consisted of up to 12 feet loose to medium dense sand fill overlying glacially medium dense to dense native outwash and glacial till deposits. Descriptions of these soil units are discussed below and a generalized subsurface profile is shown in Figure 7. Unit I Fill — Fill was encountered in borings BH -1 and BH -2. The fill ranged from about 9 foot thick in BH -1 to about 12 feet in BH -2. This unit consisted of loose to medium dense sand with occasional roots. The composition and quality of fill may vary significantly across the site. 05-155 Report.aoe Page 2 of 11 PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 Unit 2 Outwash Sand — Medium dense to dense sand was encountered beneath the fill in borings BH -1 and BH -2 and directly below the topsoil at a depth of 18 inches in boring BH -3. This unit extended to a depth of 21 feet below the existing grade in borings BH -1 and BH -3, and to the bottom of the boring in BH -2. Unit 3 Glacial Till --- Very dense sandy silt was encountered below unit 2 in borings BH -1 and BH -3. The top of Unit 3 was approximately 21 feet below existing grade. Groundwater seepage was not encountered in any of the borings. It should be noted that groundwater elevations may vary depending on the season, local subsurface conditions, and other factors. Groundwater levels are normally highest during the winter and early spring. Based on the subsurface stratigraphy, a seasonal perched groundwater table could be present on top of the glacial till during the wet winter months. CONCLUSIONS AND RECOWYTENDATIONS GROUND MOTION FOR SEISMIC DESIGN We understand that the 2003 IBC will be used for the project. Ground motion parameters consistent with the IBC are provided below. Recurrence Interval 25475 year Site Class D SS 1.22 S1 0.43 FA 1.01 Fv 1.57 SDs 0.82 SDI 0.45 Design PGA 0.33 (SDs/2.5) The spectral response accelerations were obtained from the USGS Earthquake Hazards Program website using the Interactive Deaggregation (2002) for the project latitude and longitude. - FOOTING FOUNDATION It is our opinion that conventional spread footings are appropriate for the proposed addition project. The footing subgrade conditions are anticipated to vary across the site, and may,consist of loose sandy fill and medium dense, native outwash sand. Where loose fill is encountered, we recommend a one -foot overexcavation below the bottom of the footing. The exposed subgrade should then be compacted to a dense and unyielding condition. On site soil may then be placed on the compacted surface in two equal lifts 05-155 ReporLdoc Page 3 of 11 PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 and compacted to a dense condition. Overexcavation is not needed when native outwash sand is present at the footing subgrade. Footings constructed as described above may be sized using an allowable bearing pressure of 2,000 psf. For allowable stress design, the recommended allowable bearing pressure may be increased by 1/3 for transient conditions such as wind and seismic loadings. All footings should be founded a minimum depth of 18 inches below the adjacent finish grade, or for interior footings, 12 inches below the floor slab. For this project, we recommend that all footings should have minimum width of 24 inches. Total and differential settlements are anticipated to be within tolerable limits for footings designed and constructed as discussed above. Footing settlement under static loading conditions are estimated to be less than about 1 -inch and differential settlement between adjacent columns should be less than about !/z -inch. Most settlement will occur during construction as loads are applied. Lateral forces from wind or seismic loading may be resisted by the combination of passive earth pressures acting against the embedded portions of the foundations and by friction acting on the base of the foundations. Passive resistance values may be determined using an equivalent fluid weight of 300 pounds per cubic foot (pcf). This value includes a factor safety of at least 1.5 assuming that a properly compacted structural fill will be placed adjacent to the sides of the footings. A coefficient friction of 0.4 may be used to determine the frictional resistance at the base of the footings. This coefficient includes a factor safety of approximate 1.5. All footing excavations should be trimmed neat and footing subgrades should be carefully prepared. Any loose or softened soil should be removed from the footing excavations. Footing excavations should be observed by PanGEO to confirm that the exposed footing subgrade is consistent with the expected conditions and adequate to support the design bearing pressure. BASEMENT WALLS Basement walls should be properly designed to resists the pressure exerted by the soils behind the walls. Proper drainage provisions should also be provided behind the walls such that groundwater will not accumulate behind the wails. Presented below are our geotechnical recommendations for the design and construction of the basement walls. Lateral Eartk Pressures — Basement walls may be designed for an equivalent fluid pressure of 45 pcf We also recommend that a uniform lateral pressure of 7H psf be used to account to seismic loading conditions, where "H" is the exposed wall height in feet. The recommended lateral pressures assume that the backfill behind the wail 05-155 ReporLdoa Page 4 of 11 PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 will consist of properly compacted structural fill, and adequate wall drainage provisions are incorporated into the design and construction of the walls. Surcharge — Surcharge loads, where present, should also be included in the design of retaining walls. We recommend that a lateral load coefficient of 0.3 be used to compute the lateral pressure on the wall face resulting from surcharge loads located within a horizontal distance of one-half wall height. Wall Footing — See the Footing Foundation section above Lateral Resistance — See the Footing Foundation section above Wall Drainage — As a minimum, for conventional walls that require backfill, provision for permanent control of subsurface water should consist of a perforated drainpipe behind and at the base of the wall footings, embedded in clean washed drain rock or pea gravel. The drain rock should be wrapped in geotextile filter fabric to limit the migration of fines from the native soils into the drain system. The drainpipe should be graded to direct water away from the backfill and subgrade soils and to a suitable outlet. Wall Backfill — Wall backfill should consist of free draining granular soils. The existing on-site soils may be used as wall backfill, provided that the on-site soils can be properly moisture conditioned and compacted. All wall backfill should be placed in loose, horizontal lifts less than 8 inches in thickness, and systematically compacted to a dense and relatively unyielding condition. Within 5 feet of the walls, we recommend using small equipment such as plate wackers for fill compaction, to prevent damage to the concrete wall. In the area where the space is limited between the wall and the face of excavation, pea gravel may be used without compaction. Damp Proofing — All basement walls should be protected with a damp proofing compound. FLOOR SLABS Conventional slab on grade construction may be used for the floor slabs. Prior to the slab construction, we recommend that the exposed subgrade be compacted to a dense and unyielding condition. We also recommend that interior slabs be constructed on a minimum 4 -inch thick capillary break placed on the compacted subgrade. The capillary break should consist of free -draining, crushed rock or well -graded gravel compacted to a firm and unyielding condition. The capillary break material should have no more than 10 percent passing the No. 4 sieve and less than 5 percent by weight of the 05-155 Report.aoo Page 5 of l 1 PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 material passing the U.S. Standard No_ 100 sieve. We also recommend that a 10 -mil polyethylene vapor barrier be placed below the slab. Prior to placement of the capillary break, the adequacy of the exposed subgrade should be verified by PanGEO. We also recommend that construction joints be incorporated into the floor slab to control cracking. ROCKERY We understand that a series of short rockeries may be constructed for grade separation. Although rockeries are typically used to retain cuts, it is our opinion that rockeries may also be used to retain fill provided that the retained fill height is less than 5 feet, and the backslope above the rockeries is no steeper than 411:1 V. In addition, any foundation elements behind the rockeries should be placed sufficiently deep that the foundation elements will be located beyond a IY2H:1V projection from the heel of the rockeries. Construction of rockeries should be performed in accordance with Section 8-24 of the 2004 WSDOT Standard Specifications. For design purposes, the base rock should have a minimum width equivalent to at least one-third the wall height, and gradually taper to a minimum top width of 1 %z foot (i.e., two-man rock). Rocks smaller than 1'/2 -foot in width should not be used for this project. The width is designated as the width of a single rock as measured perpendicular to the face of the slope. The wall face should be inclined no steeper than 6V:1 H, and the base rocks should be keyed in at least 1 foot below the lowest adjacent grade. All rockeries should be founded on relatively undisturbed native soils or properly compacted structural fill. if soft compressible soils are encountered in the rockery foundation soils, it may be necessary to remove and replace the soft soils to the depth determined by the field engineer. Rocks should be placed so that the contact seam between two adjacent rocks is not above or below the vertical contact seam for the upper and lower courses (i.e. each rock should overlap at least two different rocks in the course below). The long axis of each rock should be placed perpendicular to the slope. The rock surfaces between individual courses should be relatively flat, and should in no case slope downward away from the wall face. Rock quality is critical to rockery wall performance. Many rockery failures occur because of degradation of poor -grade rocks under freeze -thaw and weathering conditions. As a minimum, the rock used should meet the requirements outlined in Section 9.13.7(1) of the 2004 edition of WSDOT/APWA Standard Specifications. The chinking material for backfill should meet the requirements outlined in Section 9.13.7(2). 05-155 Repomdoc Page 6 of 11 PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 TEmpoRARY ExcAVAnoN We anticipate the excavation to encounter mostly loose to medium dense sand. For p y planning purposes, where space is available, we recommend that temporary excavations over 4 feet deep be graded no steeper than IH:IV. We also recommend that heavy construction equipment, building materials, excavated soil, and vehicular traffic should not be allowed within a distance equal to 1/3 the slope height from the top of any excavation. From the design information provided for our review, it appears that sufficient space is available for a 1 H:1 V except a portion of east property line. We understand that the eastern (upslope) residence will be located about 12 feet from the east property line, and will have a finish floor elevation of 125.5 feet in the basement, and the excavation is anticipated to extend to about Elevation 124 feet for the footings. The maximum depth of excavation is anticipated to be about 14 feet to facilitate the footing construction. Asa result, a 1 H:1 V excavation will encroach into the neighboring property to the east. Therefore, it may be necessary to obtain an easement from the neighboring property owner or excavation shoring will be required. If shoring will be required, PanGEO will be available to provide additional input regarding appropriate shoring types and design parameters. Note that the neighboring house to the east is located about 17 feet away from the new house. The excavating contractor should limit the amount of the excavation beyond the edge of the new footing such that the neighboring footings will be located beyond a 1 HAV projection from the toe of the excavation. Some groundwater seepage may be encountered during excavation. The amount of groundwater may vary seasonally. If groundwater seepage is encountered, .we anticipate that the use of drainage ditches and sump pumps will provide adequate construction dewatering. During wet weather, runoff water should be prevented from entering excavations. We also recommend that all cut slopes be completely covered with plastic sheets to prevent surficial erosion. BASELINE SURVEY AND MON roRmG Ground movements will occur as a result of excavation activities. As a result, conditions of the adjacent structures and the ground surface elevation should be documented prior to commencing earthwork to provide baseline data. As a minimum, we recommend that existing adjacent residence be monitored during construction. This may include existing crack surveys and photo -documentations. Optical survey points should be established on existing building corners, and around the perimeter along the excavation as the excavation proceeds. Both vertical and horizontal deformations should be measured 05-I55 Reportdoe Page 7 of 11 PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 periodically during the construction process. We recommend that the monitoring be performed by the contractor, and the results submitted to PanGEO for review. The results of the monitoring will allow the design team to confirm design parameters, and for the contractor to make adjustments if necessary. WET EARTHWORK RECOMMENDATIONS Given that the site soils can be moisture sensitive, it may be more economical to perform the earthwork in the drier summer months. However, if earthwork will be conducted in wet weather conditions, certain steps should be taken to mitigate the impacts of the weather on the site conditions. General recommendations relative to earthwork performed in wet weather or in wet conditions are presented below: • Earthwork should be performed in small areas to minimize subgrade exposure to wet weather. Excavation or the removal of unsuitable soil should be followed promptly by the placement and compaction of clean structural fill. The size and type of construction equipment used may have to be limited to prevent soil disturbance. • During wet weather, the allowable fines content of the structural fill should be reduced to no more than 5 percent by weight based on the portion passing 3/4 - inch sieve. The fines should be non -plastic. • The ground surface within the construction area should be graded to promote run-off of surface water and to prevent the ponding of water. • Bales of straw and/or geotextile silt fences should be strategically located to control erosion and the movement of soil. As a minimum, erosion control measures should be installed along the east property boundaries. • Excavation slopes and soils stockpiled on site should also be covered with plastic sheets. SURFACE DRAINAGE AND EROSxON CONTROL Surface runoff can be controlled during construction by careful grading practices. Typically, this includes the construction of shallow, upgrade perimeter ditches or low earthen berms to collect runoff and prevent water from entering the excavation. All collected water should be directed under control to a positive and permanent discharge system such as a storm sewer. os-lss Report.doc Page 8 of 11 PanGEO, hie. Mr. Carter Woollen Hadfield Residence March 10, 2006 Temporary erosion control measures should be provided and maintained during construction. Erosion control should consist of bales of straw and/or geotextile silt fences strategically located to control erosion and the movement of soil. As a minimum, erosion control measures should be installed along the south and west property boundaries. In addition, filter "socks" should be installed in nearby catch basins and cleaned or replaced periodically. The socks should be inspected after heavy rains. Efforts should be made to prevent or at least limit the amount of soil material that is tracked off site on construction vehicles. Temporary erosion control is especially critical when site grading activities occur during wet weather periods. Permanent control of surface water should be incorporated in the final grading design. Adequate surface gradients and drainage systems should be incorporated into the design such that surface runoff is directed away from structures. ADDITIONAL SERVICES To confirm that our recommendations are properly incorporated into the design and construction of the proposed construction, PanGEO should be retained to conduct a review of the final project plans and specifications, and to monitor the construction of geotechnical elements. PanGEO can provide you a cost estimate for construction monitoring services on a later date. We anticipate that the following additional services may be required: • Review final project plans and specifications • Verify implementation of erosion control measures • Evaluate and confirm the stability of temporary excavation slopes • Verify adequacy of footing subgrade • Verify the adequacy of subsurface drainage installation • Confirm the adequacy of the compaction of structural backfill • Other consultation as may be required during construction Modifications to our recommendations presented in this report may be necessary, based on the actual conditions encountered during construction. LEVIITATIONS We have prepared this report for use by Joel and Dana Hadfield and their project team. Recommendations contained in this report are based on a site reconnaissance, a subsurface exploration program, review of pertinent subsurface information, and our 05-155 Report.aoc Page 9 of 11 PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 understanding of the project. The study was performed using a mutually agreed-upon scope of work. Variations in soil conditions may exist at locations away from the explorations and the actual conditions underlying the site. The nature and extent of soil variations may not be evident until construction occurs. If any soil conditions are encountered at the site that are different from those described in this report, we should be notified immediately to review the applicability of our recommendations. Additionally, we should also be notified to review the applicability of our recommendations if there are any changes in the project scope. The scope of our work does not include services related to construction safety precautions. Our recommendations are not intended to direct the contractors' methods, techniques, sequences or procedures, except as specifically described in our report for consideration in design. Additionally, the scope of our work specifically excludes the assessment of environmental characteristics, particularly those involving hazardous substances. We are not mold consultants nor are our recommendations to be interpreted as being preventative of mold development. A mold specialist should be consulted for all mold -related issues. This report may be used only by the client and for the purposes stated, within a reasonable time from its issuance. Land use, site conditions (both off and on-site), or other factors including advances in our understanding of applied science, may change over time and could materially affect our findings. Therefore, this report should not be relied upon after 24 months from its issuance. PanGEO should be notified if the project is delayed by more than 24 months from the date of this report so that we may review the applicability of our conclusions considering the time lapse. It is the client's responsibility to see that all parties to this project, including the designer, contractor, subcontractors, etc., are made aware of this report in its entirety. The use of information contained in this report for bidding purposes should be done at the contractor's option and risk. Any party other than the client who wishes to use this report shall notify PanGEO of such intended use and for permission to copy this report. Based on the intended use of the report, PanGEO may require that additional work be performed and that an updated report be reissued. Noncompliance with any of these requirements will release PanGEO from any liability resulting from the use this report. Within the limitation of scope, schedule and budget, PanGEO engages in the practice of geotechnical engineering and endeavors to perform its services in accordance with generally accepted professional principles and practices at the time the Report or its contents were prepared. No warranty, express or implied, is made. os-iss Report.aoc Page 10 of 1 I PanGEO, Inc. Mr. Carter Woollen Hadfield Residence March 10, 2006 We trust that the information presented herein meets your need at this time. If you have any questions, please do not hesitate to contact our office. Sincerely, ►cls In, 7OD b EXPIRES 10111 Z/ZDV Siew L. Tan, P.E. Principal Geotechnical Engineer Attachments: Figure I Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 05-155 Repomdoc Vicinity Map Site and Exploration Plan Terms and Symbols for Boring and Test Pit Logs Log of Test Boring BH -I Log of Test Boring BH -2 Log of Test Boring BH -3 Generalized Profile, Section A .Page 11 of 11 PanGEO, Inc. Approx. Scale: 1" =112 mile RanI Hadfield Residence GE&I506 P Avenue S I C a R P 0 x A T E O Edmonds, Washington 05-155 VICINITY MAP I Z O > 39V aVJLl u -� U ,4 > 00 3 a MIS 3 Z F] )n M13 NO g11 30N33 DOOM IT 7T 0.6 00`6 o0N Z CV Z � max 1 O I J �I LO I 0 Z tl 30i5 313aONOa J 0- x W 1 I �3 I HON to w m Lh o N d Z 4� U Z O U� 2 C� to -- Wim-- --- w �a� Mw �i �CE a. W O 0 r s 0F'� 0I 0 Li a z 0 Z£4 0 ' w z v� = - p� / c N ZZ or 7 I i� m A �!) n n � � Q 9zr a O )_ QD 126 ON33 3aVA 5 ? �--tia► x�vm N�Iaa � 3aaN � w � C n n U A 3AIa0 N C C _O t A N d N co m [tl O - o V m X C U O J u o p CLto a C Q o fly E rte) Ih C 4 r D N O _ O jD O m0 (D U Z.0 a Z CV Z O 0 Z Z6 J 0- x W Z to w Lh o N d Z 4� U Z O U� 2 C� to � Q �CE =�*3 W O W r s a 0 a z 0 0 u w z v� = - p� g ZZ or 7 I i� RELATIVE DENSITY / CONSISTENCY SAND / GRAVEL Fissured: Breaks along defined planes SILT / CLAY Density SPT Approx. Relative Consistency SPT Approx, Undrained Shear GP c Poorly�raded GRAVEL N -values Density (%) .....;...................................................... GM t SiltyGRAVEL N•values Strength (psf) Very Loose <4 <15 : Very Soft <2 <250 Loose = 4 to 10 15-35 Soft 2 to 4 250-500 Med. Dense 10 to 30 35-65 Med, Stiff 4 to 8 500.1004 Dense 30 to 50 65-85 Stiff 8 to 15 1040.2000 Very Dense >50 85.100 Very Stiff 15 to 30 2040.4000 OH: Organic SILT or CLAY ............................................................. Highly Organic Soils Hard >30 >4000 UNIFIED SOIL CLASSIFICATION SYSTEM MAJOR DIVISIONS GROUP DESCRIPTIONS Fissured: Breaks along defined planes •� GW: Well -graded GRAVEL Gravel GRAVEL {<5% foes} Blocky: Angular soil lumps that resist breakdown .....:...................................................... 50% or more of the coarse :.................I................ •� GP c Poorly�raded GRAVEL fraction retained on the #4 ; sieve. Use dual symbols (eg. Numerous: More than one per foot .....;...................................................... GM t SiltyGRAVEL GRAVEL (>12% fines) GP-GM)for 5%to 12% fines. j ...................................................................... Fine Sand: 440 to #200 sieve (0.42 to 0.074 mm) GC : Clayey GRAVEL 314 inches to #4 sieve ... ..... _................................. 6................... SW: Well -graded SAND Sand SAND (<5% ) 5/°fines 50% or moreotthecoarse:...................................�.,:... ;:: .......,�- .. SP Poorl raded SAND :. fraction passing the #4 sieve. Use dualsymbols a SP-SN) N i • ��.:. ' r s ...................................................... SM Silty SAND. for 5%to19 fines.SAND (>12%fifines) ...................................................................... :.::......,..•.......• ........................................... SC ` Clayey SAND TXC Triaxial Compression ML c SILT Liquid Limit < 50 CL : Lean SILT Silt and Clay - _ ............................................................ OL c Organic SILT or CLAY .... 50%or more passing #200 sieve -inch OD Split Spoon, SPT ._...:...................................................... MH :........................... Elastic SILT Liquid Limit> 50 (140-1b. hammer, 30" drop) CH : Fat CLAY ...................................................................... OH: Organic SILT or CLAY ............................................................. Highly Organic Soils PT i PEAT Notes: 1. Soil exploration lo ggs contain material descriptions based on visual observation and field tests us'ng a system modified from the Uniform Soil Classification System (USCS). Where necessary laboratory.tests have been conducted (as noted in the "Other Tests" column), unit descriptions may include a classification. Please refer to the discussions in the report text for a more complete description of the subsurface conditions. 2. The graphic symbols given above are not inclusive of all symbols that may appear on the borehole logs. Other symbols may be used where field observations indicated mixed soil constituents or dual constiluent materials. DESCRIPTIONS OF SOIL STRUCTURES Layered: Units ofrpaterial distinguished by color and/or Fissured: Breaks along defined planes composition from material units above and below Slickensided: Fracture planes that are polished or glossy Laminated: Layers of soil typically 0.05 to imm thick, max,1 cm Blocky: Angular soil lumps that resist breakdown Lens: Layer of soil that pinches out laterally Disrupted: Soil that is broken and mixed Interlayered: Alternating layers of differing soil material Scattered: Less than one per foot Pocket: Erratic, discontinuous deposit of limited extent Numerous: More than one per foot Homogeneous: Soil with uniform color and composition throughout BCN: Angle between bedding plane and a plane Fine Sand: 440 to #200 sieve (0.42 to 0.074 mm) normal to core axis COMPONENT DEFINITIONS COMPONENT SIZE / SIEVE RANGE COMPONENT SIZE I SIEVE RANGE Boulder: = > 12 inches Sand Cobbles: 3 to 12 inches Coarse Sand: #4 to #10 sieve (4.5 to 2.0 mm) Gravel DD Medium Sand: #10 to #40 sieve (2.0 to 0.42 mm) Coarse Gravel: i 3 to 3/4 inches Fine Sand: 440 to #200 sieve (0.42 to 0.074 mm) Fine Gravel: 314 inches to #4 sieve Silt 0.074 to 0.002 mm Penn Permeability Clay <0.002 mm J PmGE@Terms and Symbols for a r N c o a r a re a T E n Boring and Test Pit Logs Phone: 206.262.0370 TEST SYMBOLS for In Situ and Laboratory Tests listed in "Other Tests" column. CBR California Bearing Ratio Comp Compaction Tests Con Consolidation DD Dry Density DS Direct Shear %F Fines Content GS Grain Size Penn Permeability PP Pocket Penetrometer R R -value SG Specific Gravity TV Torvane TXC Triaxial Compression UCC Unconfined Compression SYMBOLS Samplefin Situ test types and intervals ®2 -inch OD Split Spoon, SPT (140-1b. hammer, 30" drop) e3.25 -inch OD Spilt Spoon (3004b hammer, 30" drop) Non-standard penetration test (see boring log for details) Thin wall (Shelby) tube Grab Rock core ® Vane Shear MONITORING WELL 5Z Groundwater Level at time of drilling (ATL)) 1 Static Groundwater Level Cement! Concrete Seal Bentonite grout I seal Silica sand backfill Slotted fip Slough Bottom of Boring MOISTURE CONTENT Dry Dusty, dry to the touch Moist Damp but no visible water Wet Visible free water Figure 3 0 x m m 0 0 J Project: Hadfield Residence Surface Elevation: -138 Job Number: 05-155 Top of Casing Elev.: Location: Seattle, Washington Drilling Method: Hollow Stem Auger Coordinates: Northing:, Easting Sampling Method: SPT N -Value A o CL t- >` co ai a PL Moisture LL n a y � E MATERIAL DESCRIPTION (D n E M E 3 m >, ® RQD Recovery c4 O M. 0 0 50 S-1 1 2 Medum dense, reddish brown, silty SAND with gravel, dry to moist, 9 occasional roots (TOPSOILIFILL). Loose to medium dense, brown, SAND, dry to moist, with occasional 2 roots. (PILL). S-2 2 3 5 3 S-3 3 5 5 S-4 B - numerous roots noted in sampler tip. 10 Medium dense to dense, grayish brown SAND with occasional gravel, FEA S-5 6 s moist to very moist. (OUfWASH). 10 6 S-6 10 12 15 8 S-7 14 18 20 8 S-8 15 25 Verydense, grayish brown sandy SILT with gravel, moist, heterogenous texture. (GLACIAL TILL). S-9 21 5015 > Bottom of boring at 23.5 ft. No groundwater encountered during drilling. 25 30 Completion Depth: 23.4ft Remarks: Standard Penetration Test (SPT) sampler driven with a 140 Ib. safety hammer. Date Borehole Started: 10/10/05 Hammer operated with an rope and cathead mechanism. No groundwater encountered Date Borehole Completed: 10/10/05 during drilling. Logged By: TEA Drilling Company: CN Drilling PcmGE1@ LOG OF TEST BORING 131-1-1 INcaaP0RATE.O Figure Phone. 206.262.0370 The stratification lines represent approximate boundaries. The transition may be gradual. Sheet 1 of 1 cc C C C: C C Z 4 Project: Hadfield Residence Surface Elevation: -128 Job Number: 05-155 Top of Casing Elev.: Location: Seattle, Washington Drilling Method: Hollow Stem Auger Coordinates: Northing: , Easting: Sampling Method: SPT N N -Value A $ Z CL CD a) p PL Moisture LL C Q a n MATERIAL DESCRIPTION m � ® RQD Recovery CD � 0 0 50 100 S-1 Loose, brown, silty SAND with gravel, dry to moist, numerous roots 2 2 ,(TOPSOIL). Medium dense, brown, SAND, dry to moist. (FILL). 3 S-2 6 7 5 6 S-3 8 10 5 S-4 7 5law 10 3 S-5 6 5 - numerous roots noted in sampler tip. Medium dense, grayish brown SAND, moist to very moist. S-6 7 7 :. (OUTWASH). 12 15 6 S-7 10 15 Bottom of boring at 16.5 ft. No groundwater encountered during drilling- rilling_20253 20- 25- 3 Completion Depth: 16.5ft Remarks: Standard Penetration Test (SPT) sampler driven with a 940 Ib. safety hammer. Date Borehole Started: 10/10/05 Hammer operated with an rope and cathead mechanism. No groundwater encountered Date Borehole Completed: 10/10/05 during drilling. Logged By: TEA Drilling Company: CN Ddlling LOG OF TEST BORING 131-1-2 F�LnGE@ ' N C 0 R° Q N A T E° Figure 5 Phone: 206.262.0370 The stratification lines represent approximate boundaries. The transition may be gradual. Sheet 1 of 1 u c x LL a LLC Project: Hadfield Residence Surface Elevation: —137 Job Number: 05-155 Top of Casing Elev.: Location: Seattle, Washington Drilling Method: Hollow Stem Auger Coordinates: Northing: , Easting: Sampling Method: SPT c N -Value A p Z a� a (Q a) o PL Moisture LL o CL n ~ E MATERIAL DESCRIPTION o E M rn E CU W 3 m p >' ® RQD Recovery 0 0 50 100 5-1 1 Loose, reddish brown, silty SAND with gravel, dry to moist, numerous 2 2 roots (TOPSOIUFILL). Medium dense to dense, grayish brown SAND with occasional gravel, 3 moist to very moist. (OUTWASH). S-2 7 9 5 7 S-3 17 24 6 S-4 X 10 19 10 7 S-5 10 13 7 S-' 6 X .11 16 15 7 S-7 18 19 20- 17 5016 :» Very dense, grayish brown sandy SILT with gravel, moist, heterogenous texture. (GLACIAL TILL). 27 S-8 33 50 Bottom of boring at 24 ft. No groundwater encountered during drilling. 25- -30 Completion Depth: 24.Oft Remarks: Standard Penetration Test (SPT) sampler driven with a 140 Ib. safety hammer. Date Borehole Started: 10110/05 Hammer operated with an rope and cathead mechanism. No groundwater encountered Date Borehole Completed: 10/10/05 during drilling. Logged By: TEA Drilling Company: CN Drilling PanGE@ LOG OF TEST BORING 131-1-3 1 N L 0 6 P O N A T E D Figure r F Phone: 2D6.262.0370r g V i ne sirauricavon ones represent approximate boundaries. The transition may be gradual. Sheet 1 of 1 (D. � e-- : § §| � C) 2 2$?%% g q LO CD 1�1 f Fr k k k k k// V- 2 V -V- (1901) (1em)U04BA913 kk o k.9k LU ate— k\ O & §0$ I «cc \ \82 pZ LL �/ \ - / �2■ &LU ® a -£ LU kk§ w co Aka�7 C;) 2 (D @*o - $t222 r to =1 2ko=� $m.8 �0�JB ■ § -0$0" em2cL fnr �%72? ■®I §§2 coEZ5 q 2&72�$gf $ 2&) � mk OU)@m kwww¥ %2§ . 2� � � & Le w 1�1 f Fr k k k k k// V- 2 V -V- (1901) (1em)U04BA913 kk