HEATCAB Cabinet Heaters.pdf
Submittal Approval Page
214
Swedish Edmonds - Ambulatory Care CenterSubmittal #:
Submittal Spec #:230548.012-0
Preparer ApprovalSellen Approval
Spec SectionSub SectionRevision A. Approved as noted for A/E Review
2305480B. Revise & Resubmit
C. Rejected
Mechanical Seismic Restraint
Ceiling Mounted Cabinet Unit Heaters
This review is for general conformance with the plans and specifications only.
Any deviations from same not clearly noted by the subcontractor have not been
tĻƩ wCL ЊВЉ
reviewed. Review shall not constitute a complete check or detailed dimensions
or count or serve to relieve the subcontractor of contractual responsibility for
any error or deviation from contract requirements.
Prepared By:
Sellen Construction
Jenni Gregg
HermansonBy: Scott SolbergDate: 05/14/15
Architect ApprovalEngineer / Consultant Approval
Swedish Edmonds ACC - 214-230548-012.0
SUBMITTAL #
Mazzetti - SUBMITTAL REVIEW
THIS SUBMITTAL HAS BEEN REVIEWED BY THE
UNDERSIGNED
NO EXCEPTIONS TAKEN
MAKE CORRECTIONS NOTED
NOT APPROVED
REVISE AND RESUBMIT
REVIEWED AS NOTED ON CDi SUBMITTAL LOG
REVIEWED FOR MECHANICAL INFORMATION ONLY
Checking of submittals is only for general conformance with the design
concept of the project and general compliance with the information
given in the contract documents. Any action shown is subject to the
requirements of the plans and specifications. The contractor is
responsible for dimensions which shall be confirmed and correlated at
the job site's fabrication processes and techniques of construction;
coordination of his work with that of all other trades; and the
satisfactory performance of his work.
Rick Grove May 26, 2015
BY:DATE:
nformation given in the contract documents. Any action shown is subject to the
ated at the job site's fabrication processes and techniques of construction;
REVIEW COMMENTS Swedish Edmonds ED Expansion - Mechanical Submittal Review Comments -Page 1 of 15/26/2015
MECHANICAL SUBMITTA
L
Remarks
Reviewed For Info Only
Not Reviewed
Not Approved
Revise and Resubmit
Submittal Status
Make Corrections Noted
XPetra5/14/155/26/15X
No Exceptions Taken
Reviewed
Date
Green highlight indicates "No Exceptions Taken" or "Make Corrections Noted"; status of current submittal
Checking of submittals is only for general conformance with the design concept of the project and general compliance with the i
requirements of the plans and specifications. The contractor is responsible for dimensions which shall be confirmed and correl
Swedish/Edmonds ED Expansion
Received
Date
Yellow highlight indicates "Revise and Resubmit" or "Not Approved"; status of current submittal
CDi PN 2013-024.00
Manufacturer
coordination of his work with that of all other trades; and the satisfactory performance of his work.
O&M Manual
A/E Review
Seismic Anchorage for Ceiling CAB
23 05 48 Mechanical Vibration Controls and Seismic Restraints
Description
Heaters
230548-
Number
23 05 482.4214-012.0
Sub
Number
Para
Number
Spec
230548-012 Ceiling-mounted Cabinet Unit Heater Seismic Calcs
5/14/15
9
57-A
CABLE RESTRAINT DETAILS FOR
HEATCAB002 & HEATCAB003
REV.DESCRIPTION:DATE:BY:
PETRASEISMIC DESIGN, LLC
SEISMIC CONSULTING ENGINEERS
JOB:
Swedish Edmonds
HOUSTON, TX 281-656-1439
n
LOCATION:Edmonds, WA
WWW.PETRASEISMICDESIGN.COM
CUSTOMER:Hermanson
CUSTOMERNO.:
-REPORT NO.REV.
BY:
DATE:
PI5/5/15
-D12.0
P21588
CHK:
DATE:
KAH5/5/15
ANCHOR DETAILS FOR HEATCAB001
REV.DESCRIPTION:DATE:BY:
PETRASEISMIC DESIGN, LLC
SEISMIC CONSULTING ENGINEERS
JOB:
Swedish Edmonds
HOUSTON, TX 281-656-1439
n
LOCATION:Edmonds, WA
WWW.PETRASEISMICDESIGN.COM
CUSTOMER:Hermanson
CUSTOMERNO.:
-REPORT NO.REV.
BY:
DATE:
PI5/5/15
-D13.0
P21588
CHK:
DATE:
KAH5/5/15
REV.DESCRIPTION:DATE:BY:
PETRASEISMIC DESIGN, LLC
SEISMIC CONSULTING ENGINEERS
JOB:
Swedish Edmonds
HOUSTON, TX 281-656-1439
n
LOCATION:Edmonds, WA
WWW.PETRASEISMICDESIGN.COM
CUSTOMER:Hermanson
CUSTOMERNO.:
-REPORT NO.REV.
BY:
DATE:
PI5/5/15
-D15.0
P21588
CHK:
DATE:
KAH5/5/15
REV.
-SCH-A
P21588-14, D12, D15P21588-15, D13, D19
P21588-10-13, D11, D16 P21588
P21588-16, D14
REFERENCE
DWG
(2) FHS-2-185,(2) FHS-2-135
MODEL
--------
DRAWING NO.
ISOLATOR
5/5/2015
5/5/2015
QTY
--------
4
DATEDATE
PETRA SEISMIC DESIGN, LLC
SEISMIC CONSULTING ENGINEERS
KWIK HUS-EZ
W/SB-125 BKT.W/SB-125 BKT.
1439
SEISMIC RESTRAINT
LRC-18-B58LRC-12-B58
HKB TZHKB TZ
MODEL
-
WWW.PETRASEISMICDESIGN.COM
656
KAH
PI
-
281
n
HOUSTON, TX
CHECKED
DRAWN
QTY
84444
3-1/2"2-1/2"3-1/2"
EDGEDIST ATTACHMENT LEVEL E & P21588-MH4.03 FOR LAYOUT
SEE P21588-SR-D4.1 SFOR STRUCTURAL SEE P21588-SR-D4.1 SFOR STRUCTURAL
2-3/8"1-5/8"2-3/8"
EMBED
ATTACHMENT LEVEL E
Swedish Edmonds
ANCHOR QTY
(2) PER ISOLATOR
44
8
Edmonds, WA
Hermanson
1/4"3/8"
1/2"
ANCHOR DIA.
JOB:LOC:CONTR:
KWIK HUS-EZ
ANCHOR MODEL
HKB TZHKB TZ
1
z 1111
1.51.51.51.51.5
P
I
VARIES
QTY
1212
550 Lbs150 Lbs150 Lbs750 Lbs
WEIGHT
24" DIA.
DUCT
VEKTOR-CD-15-1-II-HVCW 00450ADDL130H00CW 00406ADDL110H00
GREENHECK
ARMSTRONG
DF535DW40
MODINEMODINE
MODEL
--
EXHAUST STACK
HEATCAB002,
HEATCAB003HEATSDW1,
HEATCAB001
FANISO-001
HEATSDW2
EQUIPMENT
TAG
45°
IBC Seismic LoadAnchor Loads
F=(0.4aSI/R)(1+2(z/h))W
phpDSppp
where, 0.3SIW < Fp < 1.6SIW
DSppDSpp
Lcg
F= (1 + 0.2*S)W
pvDSp
L
S=
0.8421.5
I=
DS
p
a=
2.56
R=
p
p
F
ph
Z/h= Equipment height above grade
Wcg
PLAN VIEW
NOTE 1)Contractor to mount cablerestraintsthrough equipment
T
RR
12
mounting holes, field holes drilled through equipment support, or
W
install supplementary supportsteelwelded or bolted to equipment.
55°
MAX
Any supplemental drilling, welding, or screw added to equipment
must be approved by equipment manufacturer. Calculation is for
R
r
minimum cable requirements. If equipment has additional hanger
h
cg
mounting holes, hangers must be installed in the extra holes with
appropriate size hangerrod to fit hole diameter. Equipment design
F
ph
not included in this review. Equipment manufacturer must
determine if equipment can adequately transfer seismic loads to
F
pv
restraints and resist loads shown.
ELEVATION VIEW
NOTE 2) See listed reference drawing forinstallation details.
INPUT
WLWh
RefAttach LW
Anchor
pcgcgcg
DwgLevelRod SizeZ/h(lbs)(in.)(in.)(in.)(in.)(in.)
Size
Equip. Tag Cable Model/Size
HEATCAB002, LRC-12-B57
P21588-D1257-A1/2"115040.0020.001.000.5012.501/2
HEATCAB003W/SB-125
RESULTS
RR
12
T
FFFT/F < 1.0rRRR < 1.0
Equip. Tag
(-is comp)(-is comp)
phpvttvtvr
HEATCAB002,
63.4175.322.43000.07349.3-352.287.6220011000.24
HEATCAB003
*NOTE: CABINET UNIT HEATER WITH TAG CUH-B5, USED AS WORST CASE FOR SEISMIC CALCULATION
REV.DESCRIPTION:DATE:BY:
PETRA SEISMIC DESIGN, LLC
SEISMIC CONSULTING ENGINEERS
JOB:
HOUSTON, TX 281-656-1439
Swedish Edmonds
n
WWW.PETRASEISMICDESIGN.COM
LOCATION:
Edmonds, WA
CUSTOMER NO.:
CUSTOMER:
REV.
HermansonDRAWING NO.
BY:
DATE:
PI05/05/15
P21588-14
CHK:DATE:
RES5/5/2015