Loading...
HERMANSON - Med Gas Certification Phase 3.pdf Hermanson Company LLP tel 206-575-9700 1221 2nd Avenue North fax 206-575-9800 Kent, WA 98032 SUBMITTAL DATA Swedish Edmonds - ACC 21601 76 Avenue West th Edmonds, WA 98026 Submittal 001-3 SPEC SECTION:- EQUIPMENT TAGS: None ITEM:Medical Gas Certification Reports * Emergency Oxygen Supply Connection * Imaging Dept. Rooms 021A, 022A & X-Ray 3 * Rooms 1 through 10 MANUFACTURER:MedGas Certified, LLC. SUPPLIER:MedGas Certified, LLC. Date Submitted:05/24/16 Comments: Mechanical Construction, Engineering and Service www.hermanson.com Emergency Oxygen Supply Connection (fax) Expansion Swedish Edmonds Medical Center Medical Gas Professionals Medical Gas Verification Report MedGas Certified, LLC 3573 Hermanson medgascertified@hotmail.com 2016 , 2016 MedGas Certified, LLC : La Center, WA 98629 May 24, Verification performed by Edmonds, WA 98026 - 456 May 25 Ambulatory Care Center 21601 76th Ave W - PO Box 83 888 Medical Gas Installer Date of this Report: erification: 2151 V Date of - 430 - 360 or agencies. The testing criteria were used as a base of 11 aterials; edGas Certified on nt, or health ith The tests cies and is thus many sponsibilities. Where public safety is primary, the authority having jurisdiction may be a federal, state, local, or erformed. he 2 erification Specialist Glenn Tsuda tested the Medical Pipeline System indicated by this report in accordance w Page y the ate testing laboratories. In determining the acceptability of installation, procedures, equipment, or materials the authority having jurisdiction may base acceptance on compliance with NFPA or other appropriate standards. In t performed on this system were found to be within test specifications unless otherwise noted on the Discrepancies or separate said authority may require evidence of proper installation, procedure or use. The authority having nce inspection department, rating bureau, or other insurance company representative may be the authority having jurisdiction. In The National Fire Protection Association does not approve, inspect, or certify any installations, procedures, equipment, or m The testing of this system may include all or part of the tests offered by MedGas Certified, LLC. Only the tests indicated bcircumstances, the property owner or his or her designated agent assumes the role of the authority having jurisdiction; at other regional department or individual such as a fire chief; fire marshal; chief of a fire prevention bureau, labor departme Level 1 medical gas verification. department; building official; electrical inspector; or others having statutory authority. For insurance purposes, an insura pipeline system component forms. The additional documentation contains the results, dates and locations of the tests p jurisdiction may also refer to the listing of labeling practices of an organization that is concerned with product evaluation government installations, the commanding officer or departmental official may be the authority having jurisdiction. report forms were performed on the dates indicated. The results of the tests reported represent the findings of M determine compliance with appropriate standards for the current production of listed items. Medical Gas Pipeline Verification line for determining the performance of the separate components that make up this and other applicable codes the dates and locations indicated by the report forms only. the Medical Gas and Vacuum Systems of NFPA99 MedGas Certified, LLC nor does it approve or evalu absence of such standard, Gas Professionals V vary, as do their re The Medical Gas in a position to :: Per NFPA99CPer NFPA99C Medical who has the nsibility of design requirements (bulk capacity, bulk levels of nitrogen or gas mixtures not The AHJ is normally the Fire Marshall in your area. In some instances the AHJ is the Department of Health or in the case of of 11 This report is reflective of the facilities condition and if necessary, contains recommendations to comply with the current upplying gas for patient treatment. This verification does and vel of inspection determined and contracted for by this collaboration. as e is the sole responsibility of the hospital, 3 or Page this is a testing of the installed medical gas systems from the source to the nsibility to approve equipment, materials, an installation or a procedure. The AHJ will make any and all decisions to requir The AHJ, in all matters, has the final ified, LLC has no power, nor does it undertake, to police or enforce compliance with the contents of this , inspected by the local building department, collaboration between the owner, engineers, local authority having jurisdiction and the medical gas equipment provider. MedG patient care. This ical gas and vacuum systems. Level of the facility is determined by , qualifications Determinations of all areas affected by shut downs, nitrogen purges and for final gas concentration testing is the sole respo inspection/verification. This document, in its entirety, must be presented to the local Authority Having Jurisdiction (AHJ), MedGas Certified, LLC has no knowledge or limited knowledge of the facilities existing medical gas systems. he General Contractor, the Plumbing Contractor or the Hospital address in ground/slab piping installation, materials used, installer installation for treatment and Facilities/Operations Department, are responsible for identifying and providing reports to your local AHJ. Errors in pipeline mapping can result in serious injury or death due to inhalation of high Bulk system design and bulk pad requirements are covered by NFPA50/55. These use corrections, modifications or repairs to the medical gas system recorded in this report. inspect the medical treatment equipment which is installed and connected tal, surgery center, facility. Notification of staff to prevent accidental patient pad design) are collaboration between the hospital and the bulk provider . installer testing compliance w/ ASSE 6010 & NFPA99 requirements, etc decision to approve the facility opening and starting patient services. plumber installed hard copper piping ending at connections for s determine Level and performs the Le are not the responsibility of the medical gas verifier. mortality in the event of an interruption of the piped med military facilities, the Commanding Officer. You, t - 5.1.12.3 System Verification suitable for human consumption. NOT NOT surgery center, facility. Certified, LLC does verification does IAW NFPA99 MedGas Cert document. the hospi NOTE:NOTE:NOTE:NOTE: respo NOT of 11 allowing enforcing authorities (governmental and nongovernmental) to grant exceptions to requirements. 1.4.1 Nothing in this code is intended to prevent the use of systems, methods, or devices of equivalent or uperior quality, strength, fire resistance, effectiveness, durability, and safety to those prescribed by this equivalency. The system, method, or device shall be approved for the intended purpose by the authority compliance with the provisions of this standard shall be permitted to be continued in use as long as the minder to authorities that they has determined that such use does not constitute a distinct hazard to life. 4 to demonstrate Page NFPA Committee Member comments: Although authorities having jurisdiction can adopt and enforce that they consider appropriate (e.g., adopt and enforce requirements as written; ; adopt a document but change mmittee Member comments: Paragraph 1.4.2 adds to the concept of equivalency in 1.4.1, The organization, office or individual responsible for dition of NFPA 101, with some 1.4.2 Alternative systems, methods, or devices approved as equivalent by the authority having An existing system that is not in strict submitted to the authority having jurisdiction certain requirements), 1.4.1 is intended to apply to the entire code as a re jurisdiction shall be recognized as being in compliance with this code. issue waivers to specific facilities not meeting certain requirements This wording on equivalency is similar to Section 1.4 of the 2012 e approving equipment, materials, an installation or a procedure. can grant exemptions NOTE: Per NFPA99 para 5.1.1.3 n (AHJ) code. Technical documentation shall be Authority Having Jurisdictio tion authority having jurisdic voluntary standards having jurisdiction. Equivalency NFPA Co 3.2.2 1.4 s of 11 construction and new equipment, except as modified in individual chapters. Only the altered, renovated, Construction and equipment requirements shall be applied only to new 5 Page individual component shall be required to meet the existing operational facility that might have or has medical gas piping modernization adversely impacts existing performance requirements of a system or component, installation and equipment requirements stated in this standard. If the alteration, renovation, or ode. 1.4.3 The authority having jurisdiction shall be permitted to grant exceptions to this c or modernized portion of an existing system or grading shall be required. NOTE: Per NFPA99 para 1.3.2 compliance inspection. - This is a pre additional up of 11 6 of NFPA99 Page of the hospitals ACC System has been verified and meets the requirements . This project: s inal phase Medical Gas Verification Report Summary expansion adding a new Emergency Oxygen Supply Connection (EOSC) f Medical Gas Verification Specialist II. Findings and Recommendations: This summary prepared by . MedGas Certified, LLC 1 piped systems erification: . Professionals Glenn Tsuda MedGas Certified, LLC Installed EOSC V Scope of Category Medical Gas 1. I. of 11 7 Page ng to cross connection testing but before the piping purge test. Can be performed with oil free dry Nitrogen NF, gas of rm condition if the pressure in the piping system increases or decreases 20% from the normal operating pressure for positive support and critical Valves installed in each medical gas and vacuum system shall be tested to verify proper operation and possible connection points for terminals, each possible position components function correctly care areas, such as post anesthesia recovery, ICU, CCU, emergency suites and operating rooms shall be tested to verify an Warning systems that are part of an addition to an existing piping system shall be tested prior to connection of the new pipi minute Connection Test. After closing of walls and completion of the Installers Initial Tests, it shall be Installation of any manufactured assemblies supplied through flexible hoses or tubing has been completed. - 5.1.12.3.2 Verifier Standing Pressure Test. Each positive pressure gas piping system shall be subjected to a ten - The warning signals for all medical gas piping systems supplying anesthetizing locations and other vital life each of the medical gas and vacuum piping systems. All warning systems for each medical gas and vacuum system shall be tested to ensure that all pressure gases, or when the vacuum system drops below a gauge pressure of 12 in. determined that no cross connections of the piping systems exist. 5.1.12.3.1.7 Where manufactured assemblies include multiple system designation or the operating vacuum source. Master alarm system tests shall be performed for operating line pressure. prior to placing system into service. shall be tested independently. rooms or areas of control. standing pressure test at - 5.1.12.3.3 Verifier Cross Test the existing system. 5.1.12.3.4 Valve Performed after 1.12.3.1.6 5.1.12.3.5.2 Master Alarms 5.1.12.3 System Verification 5.1.12.3.5.3 Area Alarms ala 5. Verification Alarm Tests N/AN/AN/AN/AN/AN/AN/A N/A Fail System 5.1.12.3.5 Pass 5/245/245/24 of 11 8 Page free, dry Nitrogen NF or the system gas. effective for use with oxygen. appropriate adapter, a high purge rate (8scfm) will be established. It shall be rapidly interrupted several times until the free, dry A test for dew point shall be conducted at the outlet most remote from the source and dew point shall not exceed 12 degrees C n no case tent n the immediate zone or area that is downstream form the point or area of intrusion shall be purged per Verifier tested with the gas of system system gas. The test shall be for total hydrocarbons (as methane) and halogenated hydrocarbons and tested, the specific altered zone and filter at a minimum flow rate of 100 Nl/minute (3.5 scfm). In order to remove any traces of particulate matter deposited in the pipelines as a result of construction, a heavy, intermit - For each positive pressure medical gas system, the purity of the piping system shall be verified. Test gas shall be oil This test shall be performed at the outlet most remote form the source. The difference between the two tests shall i designation or vacuum at the normal operating pressure by means of soapy water or other means purge produces no discoloration in a white cloth loosely held over the adapter during the purge. - Each joint in the final connection between the new work and the existing system shall be leak - The cleanliness of the piping in each medical gas shall be verified. Test gas shall be oil - pressure gases, immediately after the final connection is made and leak 2 ppm. . If not accessible a successful completion of standing pressure test is required 25% of the zones shall be tested at the outlet most remote form the source 1 ppm and Halogenated Hydrocarbons most remote outlet in every zone shall be tested Filter shall accrue no more than 1 mg of matter from any outlet tested 1000 L of gas shall be filtered through a clean, white 0.45 micron purging of each medical gas pipeline shall be done. compared with the source gas. exceed, Total Hydrocarbons (10 degrees F) @ 50 psig. If any outlet fails, the Nitrogen NF or the Piping Purge Test. iculate Test Verifier Piping Purge Test 5.1.12.3.8 Verifier Piping Purity Test components i - in Test For positive Using an 5.1.12.3.7 Verifier Piping Part - 5.1.12.3 System Verification Verifier Final Tie N/A N/AN/A N/A Fail 5.1.12.3.6 5.1.12.3.9 Pass 5/245/245/245/245/245/245/245/24 of 11 9 Page Operational pressure tests shall be performed at each station outlet in the medical gas piping systems where the user makes /min without reducing the vacuum pressure below 12 in. HgV at any adjacent be analyzed , All oxygen and medical air outlets serving critical care areas shall permit a transient flow rate of 170 The presence and correctness of labeling required by this standard for all components, station outlets/inlets, shutoff valves 55 psi. Medical air source shall be analyzed for concentration of contaminants by volume prior to the source vale being opened. Nitrogen outlets shall deliver 140 Nl/min with a pressure drop of no more than 5 psi and static pressure of 160 to 185 psi outlets shall deliver 100 NL/min with a pressure drop of no more than 5 psi and static pressure of 50 After purging each piping system with the gas of system designation, each pressure gas source and outlet shall free, dry Nitrogen NF or gas of system designation. Testing of source equipment performed and results are recorded on individual equipment sheets. - connections and disconnections. Performed with either oil at the system sample port. Medical surgical vacuum inlets shall draw 85 Nl for concentration of gas by volume. and alarm panels, shall be verified. /min (6 SCFM) for 3 seconds. 5.1.12.3.12 Medical Air Purity Test (Air Compressor) Sample shall be taken Critical care flow test 5.1.12.3.10 Verifier Operational Pressure Test 5.1.12.3.11 Medical Gas Concentration Test Verification Medical gas station inlet 5.1.12.3.14 Source Equipment Nl N/AN/AN/AN/AN/AN/AN/A N/A 5.1.12.3.13 Labeling Fail Pass 5/245/24 of 11 5.1.3.5.13* Emergency Oxygen Supply Connection (EOSC). Emergency oxygen supply connections (EOSCs) EOSC and one downstream of Where the bulk cryogenic liquid central supply system is outside of and remote from the 10 shall be installed to allow connection of a temporary auxiliary source of supply for emergency or maintenance Where there is not in the building a connected oxygen reserves sufficient for an average Where multiple freestanding buildings are served from a single oxygen source such that immediately downstream of the main shutoff valve. damage to the interconnecting oxygen line could result in one or more buildings losing oxygen supply. Page Has a female DN (NPS) inlet for connection of the emergency oxygen source that is Located on the exterior of the building being served in a location accessible by the main line shutoff valve, with both upstream from the tee connection for the two pipelines. Equipped with a manual shutoff valve to isolate the EOSC when not in use. 100 percent of the system demand at the emergency source gas pressure. Equipped with two check valves, one downstream of the Physically protected to prevent unauthorized tampering. eparate EOSC. emergency supply vehicles at all times in all weather conditions. In this situation, each building shall be provided with a s Connected to the main supply line s exist: building that the oxygen supply serves. situations where any of the following condition ------ (1) .1 (2) .2 (1) .2 (2) .2 (3) .2 (4) --- (1) (2) (3) 5.1.3.5.13.1 5.1.3.5.13 5.1.3.4.135.1.3.4.135.1.3.4.135.1.3.4.135.1.3.4.135.1.3.4.135.1.3.4.13 sized for N/A n/a No Yes 5/245/245/245/245/245/245/245/24 of 11 Equipped with a relief valve sized to protect the downstream piping system and related A.5.1.3.5.13 If 11 ion is moved downstream from the check valve Page Equipped with any valves necessary to allow connection of an emergency supply of Minimum of 1 m (3 ft) of clearance around the EOSC for connection of temporary Gauge in the emergency oxygen line, it should be connected to the system with a demand check fitting. P pressure. Leakage P equipment from exposure to pressures in excess of 50% higher than normal line Function P and isolation of the piping to the normal source of supply. Access P the relief valve on the emergency oxygen supply connect Label P Location South side of building ---e. .2 (5) .2 (6) (7) auxiliary sourc Pass/Fail 5.1.3.5.13.2 Pass 5.1.3.4.135.1.3.4.13 oxygen Oxygen Source Valve Valve Test n/a O2 No Service Yes 5/245/245/24 ray 3 - Imaging Department Rooms 021A, 022A & X (fax) Expansion Swedish Edmonds Medical Center Medical Gas Professionals Medical Gas Verification Report MedGas Certified, LLC 3573 Hermanson medgascertified@hotmail.com May 24, 2016 , 2016 MedGas Certified, LLC : La Center, WA 98629 Verification performed by Edmonds, WA 98026 - 456 May 25 Ambulatory Care Center 21601 76th Ave W - PO Box 83 888 Medical Gas Installer Date of this Report: erification: 2151 V Date of - 430 - 360 nt, or health ble codes or agencies. The testing criteria were used as a base of 10 aterials; fied on ith The tests cies and is thus many sdiction may be a federal, state, local, or ed. he 2 erification Specialist Glenn Tsuda tested the Medical Pipeline System indicated by this report in accordance w Page offered by MedGas Certified, LLC. Only the tests indicated by the n, procedures, equipment, or materials the authority having jurisdiction may base acceptance on compliance with NFPA or other appropriate standards. In t ations unless otherwise noted on the Discrepancies or separate use. The authority having pipeline system component forms. The additional documentation contains the results, dates and locations of the tests perform report forms were performed on the dates indicated. The results of the tests reported represent the findings of MedGas Certi tutory authority. For insurance purposes, an insurance inspection department, rating bureau, or other insurance company representative may be the authority having jurisdiction. In The National Fire Protection Association does not approve, inspect, or certify any installations, procedures, equipment, or m mes the role of the authority having jurisdiction; at other regional department or individual such as a fire chief; fire marshal; chief of a fire prevention bureau, labor departme Level 1 medical gas verification. jurisdiction may also refer to the listing of labeling practices of an organization that is concerned with product evaluation government installations, the commanding officer or departmental official may be the authority having jurisdiction. of listed items. absence of such standard, said authority may require evidence of proper installation, procedure or nor does it approve or evaluate testing laboratories. In determining the acceptability of installatio in a position to determine compliance with appropriate standards for the current production vary, as do their responsibilities. Where public safety is primary, the authority having juri Medical Gas Pipeline Verification line for determining the performance of the separate components that make up this circumstances, the property owner or his or her designated agent assu and other applica department; building official; electrical inspector; or others having sta performed on this system were found to be within test specific The testing of this system may include all or part of the tests nly. the dates and locations indicated by the report forms o the Medical Gas and Vacuum Systems of NFPA99 MedGas Certified, LLC Medical Gas Professionals V The Medical Gas :: Per NFPA99CPer NFPA99C who has the downs, nitrogen purges and for final gas concentration testing is the sole responsibility of ments are covered by NFPA50/55. These design requirements (bulk capacity, bulk not The AHJ is normally the Fire Marshall in your area. In some instances the AHJ is the Department of Health or in the case of of 10 This report is reflective of the facilities condition and if necessary, contains recommendations to comply with the current plumber installed hard copper piping ending at connections for supplying gas for patient treatment. This verification does and determine Level and performs the Level of inspection determined and contracted for by this collaboration. the medical gas equipment provider. MedGas The AHJ will make any and all decisions to require is the sole responsibility of the hospital, acilities location at the time of this 3 Errors in pipeline mapping can result in serious injury or death due to inhalation of high levels of nitrogen or gas mixtures or Page cal gas systems from the source to the The AHJ, in all matters, has the final iance with the contents of this , inspected by the local building department, patient care. This y , qualifications mortality in the event of an interruption of the piped medical gas and vacuum systems. Level of the facility is determined b inspection/verification. This document, in its entirety, must be presented to the local Authority Having Jurisdiction (AHJ), MedGas Certified, LLC has no knowledge or limited knowledge of the facilities existing medical gas systems. military facilities, the Commanding Officer. You, the General Contractor, the Plumbing Contractor or the Hospital address in ground/slab piping installation, materials used, installer installation d Operations Department, are responsible for identifying and providing reports to your local AHJ. for treatment an MedGas Certified, LLC has no power, nor does it undertake, to police or enforce compl use corrections, modifications or repairs to the medical gas system recorded in this report. inspect the medical treatment equipment which is installed and connected this is a testing of the installed medi the hospital, surgery center, facility. Notification of staff to prevent accidental patient collaboration between the owner, engineers, local authority having jurisdiction and Determination of the facilities medical gas Level (1, 2 or 3) is based on t pad design) are collaboration between the hospital and the bulk provider responsibility to approve equipment, materials, an installation or a procedure. . installer testing compliance w/ ASSE 6010 & NFPA99 requirements, etc decision to approve the facility opening and starting patient services. . are not the responsibility of the medical gas verifier - 5.1.12.3 System Verification Determinations of all areas affected by shutBulk system design and bulk pad require suitable for human consumption. NOT ity.NOT Certified, LLC does surgery center, facil verification does IAW NFPA99 document. Facilities/ TE:NOTE:NOTE:NOTE: NOT NO of 10 allowing enforcing authorities (governmental and nongovernmental) to grant exceptions to requirements. methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety to those prescribed by this lency. The system, method, or device shall be approved for the intended purpose by the authority compliance with the provisions of this standard shall be permitted to be continued in use as long as the that they at such use does not constitute a distinct hazard to life. 4 to demonstrate Page NFPA Committee Member comments: Although authorities having jurisdiction can adopt and enforce ropriate (e.g., adopt and enforce requirements as written; ; adopt a document but change s: Paragraph 1.4.2 adds to the concept of equivalency in 1.4.1, The organization, office or individual responsible for th some 1.4.2 Alternative systems, methods, or devices approved as equivalent by the authority having certain requirements), 1.4.1 is intended to apply to the entire code as a reminder to authorities An existing system that is not in strict This wording on equivalency is similar to Section 1.4 of the 2012 edition of NFPA 101, wi submitted to the authority having jurisdiction jurisdiction shall be recognized as being in compliance with this code. 1.4.1 Nothing in this code is intended to prevent the use of systems, issue waivers to specific facilities not meeting certain requirements approving equipment, materials, an installation or a procedure. can grant exemptions NOTE: Per NFPA99 para 5.1.1.3 has determined th Authority Having Jurisdiction (AHJ) voluntary standards that they consider app code. Technical documentation shall be NFPA Committee Member comment authority having jurisdiction having jurisdiction. Equivalency equiva 3.2.2 1.4 of 10 construction and new equipment, except as modified in individual chapters. Only the altered, renovated, Construction and equipment requirements shall be applied only to new 5 Page hall be required to meet the existing operational facility that might have or has medical gas piping modernization adversely impacts existing performance requirements of a system or component, installation and equipment requirements stated in this standard. If the alteration, renovation, or 1.4.3 The authority having jurisdiction shall be permitted to grant exceptions to this code. or modernized portion of an existing system or individual component s red. additional upgrading shall be requi para 1.3.2 compliance inspection. NOTE: Per NFPA99 - This is a pre of 10 medical gas system completing the final medical of NFPA99 medgas piping from the existing Imaging MedGas Zone piping (installed during 6 Page piping (installed during the initial construction project). This pipeline was extended down the corridor and is intended for been verified and meet the requirements is of the . This verification Extended the medair piping from the existing Imaging MedGas Zone Verification Report Summary existing future service valves. . the initial construction project) to feed 3 additional rooms ew Ambulatory Care Center (ACC) This project: ve ha Medical Gas s System 1 - . All new piping was tied in at pre this ACC expansion and Recommendations: is a This Medical Gas Verification Specialist . future expansion. piped systems erification: mv This summary prepared by Medical Gas Professionals for the n MedGas Certified, LLC Extended o2, MedGas Certified, LLC gas phase for expansion V Scope of II. Findings Glenn Tsuda 1 Level 1)2)3) I. of 10 alarm condition if free dry Nitrogen NF, gas of system o verify proper operation and rooms or or when After closing of walls and completion of the Installers Initial Tests, it shall be determined that e rior to 7 shall b support and critical care Page the minute standing the pressure in the piping system increases or decreases 20% from the normal operating pressure for positive pressure gases, ng systems that are part of an addition to an existing piping system shall be tested prior to connection of the new piping to All warning systems for each medical gas and vacuum system shall be tested to ensure that all components function correctly p 5.1.12.3.1.7 Where manufactured assemblies include multiple possible connection points for terminals, each possible position Installation of any manufactured assemblies supplied through flexible hoses or tubing has been completed. areas, such as post anesthesia recovery, ICU, CCU, emergency suites and operating rooms shall be tested to verify an - 5.1.12.3.2 Verifier Standing Pressure Test. Each positive pressure gas piping system shall be subjected to a ten - The warning signals for all medical gas piping systems supplying anesthetizing locations and other vital life Master alarm system tests shall be performed for each of the medical gas and vacuum piping systems. Performed after cross connection testing but before the piping purge test. Can be performed with oil Valves installed in each medical gas and vacuum system shall be tested t the vacuum system drops below a gauge pressure of 12 in. no cross connections of the piping systems exist. designation or the operating vacuum source. Connection Test. pressure test at operating line pressure. placing system into service. - 5.1.12.3.3 Verifier Cross 5.1.12.3.4 Valve Test tested independently. areas of control. existing system. .12.3.1.6 5.1.12.3.5.2 Master Alarms 5.1.12.3 System Verification 5.1.12.3.5.3 Area Alarms Warni Alarm Tests 1 5. System Verification N/A N/A N/A N/A N/A N/A N/A N/A Fail 5.1.12.3.5 Pass 5/245/245/24 of 10 8 Page free, dry Nitrogen NF or the system gas. designation or vacuum at the normal operating pressure by means of soapy water or other means effective for use with oxygen. propriate adapter, a high purge rate (8scfm) will be established. It shall be rapidly interrupted several times until the free, dry e A test for dew point shall be conducted at the outlet most remote from the source and dew point shall not exceed 12 degrees C tent eam form the point or area of intrusion shall be purged per Verifier tested with the gas of system This test shall be performed at the outlet most remote form the source. The difference between the two tests shall in no cas ydrocarbons (as methane) and halogenated hydrocarbons and tested, the specific altered zone and Nl/minute (3.5 scfm). In order to remove any traces of particulate matter deposited in the pipelines as a result of construction, a heavy, intermit - For each positive pressure medical gas system, the purity of the piping system shall be verified. Test gas shall be oil 1000 L of gas shall be filtered through a clean, white 0.45 micron filter at a minimum flow rate of 100 purge produces no discoloration in a white cloth loosely held over the adapter during the purge. - oint in the final connection between the new work and the existing system shall be leak - The cleanliness of the piping in each medical gas shall be verified. Test gas shall be oil - pressure gases, immediately after the final connection is made and leak 2 ppm. sible a successful completion of standing pressure test is required. 25% of the zones shall be tested at the outlet most remote form the source pm and Halogenated Hydrocarbons ll be tested Filter shall accrue no more than 1 mg of matter from any outlet tested Nitrogen NF or the system gas. The test shall be for total h components in the immediate zone or area that is downstr If any outlet fails, the most remote outlet in every zone sha purging of each medical gas pipeline shall be done. 1 p compared with the source gas. exceed, Total Hydrocarbons (10 degrees F) @ 50 psig. Piping Purge Test. ulate Test Verifier Piping Purge Test 5.1.12.3.8 Verifier Piping Purity Test - in Test Using an ap If not accesFor positive 5.1.12.3.7 Verifier Piping Partic Each j - 5.1.12.3 System Verification 5.1.12.3.9 Verifier Final Tie N/A N/A N/A N/A Fail 5.1.12.3.6 Pass 5/245/245/245/245/245/245/245/24 of 10 9 Page ch station outlet in the medical gas piping systems where the user makes Medical surgical vacuum inlets shall draw 85 Nl/min without reducing the vacuum pressure below 12 in. HgV at any adjacent After purging each piping system with the gas of system designation, each pressure gas source and outlet shall be analyzed ling required by this standard for all components, station outlets/inlets, shutoff valves, All oxygen and medical air outlets serving critical care areas shall permit a transient flow rate of 170 55 psi. Medical air source shall be analyzed for concentration of contaminants by volume prior to the source vale being opened. shall deliver 140 Nl/min with a pressure drop of no more than 5 psi and static pressure of 160 to 185 psi op of no more than 5 psi and static pressure of 50 free, dry Nitrogen NF or gas of system designation. equipment sheets. Testing of source equipment performed and results are recorded on individual Medical gas outlets shall deliver 100 NL/min with a pressure dr - connections and disconnections. Performed with either oil Operational pressure tests shall be performed at ea Sample shall be taken at the system sample port. The presence and correctness of labe for concentration of gas by volume. and alarm panels, shall be verified. Nl/min (6 SCFM) for 3 seconds. ompressor) Critical care flow test 5.1.12.3.10 Verifier Operational Pressure Test 1.12.3.11 Medical Gas Concentration Test 5.1.12.3.14 Source Equipment Verification Nitrogen outlets 5.1.12.3.12 Medical Air Purity Test (Air C station inlet N/AN/AN/A N/A 5.1.12.3.13 Labeling Fail Pass 5/245/245/245/245/24 5/24 5. of 10 10 Page 41°F @ 50 psig 5°C @ 50 psig Dew Point Pass Labeling Outlet PPPPPP Gauge Function P Lock PPPPPP Hydrocarbons Halogenated Pass < 2ppm Leakage Leakage Outlet Inlet P PPPPPP Function Total Hydrocarbons as P O2 161/MA 170 Critical Care Methane Pass < 1ppm Flow n/an/an/a PPP Access P Label Vacuum ty Data Max Flow 0150150 n/an/an/a 1 mg @ 35 cuft 15 P Particulates Pass Piping Puri Operational Pressure Test 2 Above ceiling tiles in Xray Particulates LocationPPPPPP Visual Medical Gas Pipeline Purge & Purity Test Pass ray 3 Pass Oil (slpm) Test Flow 100100100 - 858585 ACC Imaging Rooms 021A, 022, X Pass/Fail Pass Odor PASS PassPassPassPassPassPass PassFail or Visible Moisture PASS Pass outlet/inlet Room info location MA, Vac Valve Test - Oxygen Pipeline O2, Gas Type Service ray 3 Gas or Service N2 Vac VacVac c O2O2O2 A Va 21022 - 0X (fax) Expansion Swedish Edmonds Medical Center Medical Gas Professionals Medical Gas Verification Report MedGas Certified, LLC 3573 Hermanson medgascertified@hotmail.com y 24, 2016 May 24, 2016 MedGas Certified, LLC : La Center, WA 98629 Verification performed by Edmonds, WA 98026 - 456 Rooms 1 thru 10 Ambulatory Care Center 21601 76th Ave W Ma - PO Box 83 888 Medical Gas Installer Date of this Report: erification: 2151 V Date of - 430 - 360 sting criteria were used as a base nt, or health of 12 fied on l Fire Protection Association does not approve, inspect, or certify any installations, procedures, equipment, or materials; ith The tests cies d is thus many te, local, or ed. e 2 erification Specialist Glenn Tsuda tested the Medical Pipeline System indicated by this report in accordance w Page LLC. Only the tests indicated by the aterials the authority having jurisdiction may base acceptance on compliance with NFPA or other appropriate standards. In th t, or on the Discrepancies or separate pipeline system component forms. The additional documentation contains the results, dates and locations of the tests perform report forms were performed on the dates indicated. The results of the tests reported represent the findings of MedGas Certi ce purposes, an insurance inspection department, rating bureau, or other insurance company representative may be the authority having jurisdiction. In absence of such standard, said authority may require evidence of proper installation, procedure or use. The authority having isdiction may also refer to the listing of labeling practices of an organization that is concerned with product evaluation an having jurisdiction; at nor does it approve or evaluate testing laboratories. In determining the acceptability of installation, procedures, equipmen other regional department or individual such as a fire chief; fire marshal; chief of a fire prevention bureau, labor departme Level 1 medical gas verification. vary, as do their responsibilities. Where public safety is primary, the authority having jurisdiction may be a federal, sta government installations, the commanding officer or departmental official may be the authority having jurisdiction. in a position to determine compliance with appropriate standards for the current production of listed items. circumstances, the property owner or his or her designated agent assumes the role of the authority and other applicable codes or agencies. The te department; building official; electrical inspector; or others having statutory authority. For insuran performed on this system were found to be within test specifications unless otherwise noted The testing of this system may include all or part of the tests offered by MedGas Certified, dical Gas Pipeline Verification line for determining the performance of the separate components that make up this the dates and locations indicated by the report forms only. Me the Medical Gas and Vacuum Systems of NFPA99 MedGas Certified, LLC Medical Gas Professionals V The Medical Gas :: Per NFPA99CPer NFPA99C The Nationa jur m who has the r final gas concentration testing is the sole responsibility of . These design requirements (bulk capacity, bulk mapping can result in serious injury or death due to inhalation of high levels of nitrogen or gas mixtures not ire Marshall in your area. In some instances the AHJ is the Department of Health or in the case of of 12 This report is reflective of the facilities condition and if necessary, contains recommendations to comply with the current plumber installed hard copper piping ending at connections for supplying gas for patient treatment. This verification does and determine Level and performs the Level of inspection determined and contracted for by this collaboration. ider. MedGas l decisions to require is the sole responsibility of the hospital, of this 3 or Page e to the The AHJ, in all matters, has the final s , inspected by the local building department, patient care. This f morbidity or MedGas Certified, LLC has no power, nor does it undertake, to police or enforce compliance with the contents of thi y , qualifications mortality in the event of an interruption of the piped medical gas and vacuum systems. Level of the facility is determined b inspection/verification. This document, in its entirety, must be presented to the local Authority Having Jurisdiction (AHJ), this is a testing of the installed medical gas systems from the sourc MedGas Certified, LLC has no knowledge or limited knowledge of the facilities existing medical gas systems. collaboration between the owner, engineers, local authority having jurisdiction and the medical gas equipment prov military facilities, the Commanding Officer. You, the General Contractor, the Plumbing Contractor or the Hospital responsibility to approve equipment, materials, an installation or a procedure. The AHJ will make any and al address in ground/slab piping installation, materials used, installer installation for treatment and ponsible for identifying and providing reports to your local AHJ. use corrections, modifications or repairs to the medical gas system recorded in this report. inspect the medical treatment equipment which is installed and connected the hospital, surgery center, facility. Notification of staff to prevent accidental patient Bulk system design and bulk pad requirements are covered by NFPA50/55 pad design) are collaboration between the hospital and the bulk provider . installer testing compliance w/ ASSE 6010 & NFPA99 requirements, etc decision to approve the facility opening and starting patient services. Determinations of all areas affected by shut downs, nitrogen purges and fo are not the responsibility of the medical gas verifier. - 5.1.12.3 System Verification Facilities/Operations Department, are res The AHJ is normally the F suitable for human consumption. Errors in pipeline NOT NOT surgery center, facility. Certified, LLC does tion does IAW NFPA99 document. verifica NOTE:NOTE:NOTE:NOTE: NOT of 12 allowing enforcing authorities (governmental and nongovernmental) to grant exceptions to requirements. lent or superior quality, strength, fire resistance, effectiveness, durability, and safety to those prescribed by this device shall be approved for the intended purpose by the authority compliance with the provisions of this standard shall be permitted to be continued in use as long as the certain requirements), 1.4.1 is intended to apply to the entire code as a reminder to authorities that they e a distinct hazard to life. 4 to demonstrate Page NFPA Committee Member comments: Although authorities having jurisdiction can adopt and enforce rce requirements as written; ; adopt a document but change concept of equivalency in 1.4.1, 1.4.1 Nothing in this code is intended to prevent the use of systems, methods, or devices of equiva The organization, office or individual responsible for This wording on equivalency is similar to Section 1.4 of the 2012 edition of NFPA 101, with some 1.4.2 Alternative systems, methods, or devices approved as equivalent by the authority having An existing system that is not in strict submitted to the authority having jurisdiction has determined that such use does not constitut voluntary standards that they consider appropriate (e.g., adopt and enfo jurisdiction shall be recognized as being in compliance with this code. issue waivers to specific facilities not meeting certain requirements NFPA Committee Member comments: Paragraph 1.4.2 adds to the approving equipment, materials, an installation or a procedure. NOTE: Per NFPA99 para 5.1.1.3 risdiction (AHJ) code. Technical documentation shall be equivalency. The system, method, or authority having jurisdiction Authority Having Ju additional information can grant exemptions having jurisdiction. Equivalency 3.2.2 1.4 of 12 construction and new equipment, except as modified in individual chapters. Only the altered, renovated, equipment requirements shall be applied only to new 5 Page or modernized portion of an existing system or individual component shall be required to meet the perational facility that might have or has medical gas piping modernization adversely impacts existing performance requirements of a system or component, nstallation and equipment requirements stated in this standard. If the alteration, renovation, or 1.4.3 The authority having jurisdiction shall be permitted to grant exceptions to this code. Construction and additional upgrading shall be required. NOTE: Per NFPA99 para 1.3.2 compliance inspection. existing o - This is a pre i of 12 medical gas system medical of NFPA99 6 Page ompleting the final been verified and meet the requirements . ms r a new zone valve, area alarm panel and 10 patient roo c is of the . This verification Medical Gas Verification Report Summary ew Ambulatory Care Center (ACC) This project: ve ha s System 1 . gas phase for this ACC expansion and Recommendations: is a fo piping This Medical Gas Verification Specialist . piped systems erification: Added o2, ma, mv This summary prepared by Medical Gas Professionals for the n MedGas Certified, LLC MedGas Certified, LLC expansion V Scope of II. Findings Glenn Tsuda 1 Level 1) I. of 12 ndition if as of system Valves installed in each medical gas and vacuum system shall be tested to verify proper operation and rooms or , it shall be determined that ses or decreases 20% from the normal operating pressure for positive pressure gases, or when shall be rior to 7 support and critical care Page em shall be tested prior to connection of the new piping to the minute standing areas, such as post anesthesia recovery, ICU, CCU, emergency suites and operating rooms shall be tested to verify an alarm co All warning systems for each medical gas and vacuum system shall be tested to ensure that all components function correctly p 5.1.12.3.1.7 Where manufactured assemblies include multiple possible connection points for terminals, each possible position Performed after cross connection testing but before the piping purge test. Can be performed with oil free dry Nitrogen NF, g ible hoses or tubing has been completed. - est. Each positive pressure gas piping system shall be subjected to a ten Connection Test. After closing of walls and completion of the Installers Initial Tests - upplying anesthetizing locations and other vital life Master alarm system tests shall be performed for each of the medical gas and vacuum piping systems. Installation of any manufactured assemblies supplied through flex Warning systems that are part of an addition to an existing piping syst the vacuum system drops below a gauge pressure of 12 in. The warning signals for all medical gas piping systems s no cross connections of the piping systems exist. g vacuum source. pressure test at operating line pressure. the pressure in the piping system increa 5.1.12.3.2 Verifier Standing Pressure T placing system into service. designation or the operatin - 5.1.12.3.3 Verifier Cross 5.1.12.3.4 Valve Test tested independently. areas of control. existing system. 1.12.3.1.6 5.1.12.3.5.2 Master Alarms 5.1.12.3 System Verification 5.1.12.3.5.3 Area Alarms sts 5. Alarm Te System Verification N/A N/A N/A N/A Fail 5.1.12.3.5 Pass 5/245/245/245/245/245/245/24 of 12 8 Page free, dry Nitrogen NF or the system gas. lished. It shall be rapidly interrupted several times until the designation or vacuum at the normal operating pressure by means of soapy water or other means effective for use with oxygen. test for dew point shall be conducted at the outlet most remote from the source and dew point shall not exceed 12 degrees C free, dry e r area of intrusion shall be purged per Verifier der to remove any traces of particulate matter deposited in the pipelines as a result of construction, a heavy, intermittent tested with the gas of system This test shall be performed at the outlet most remote form the source. The difference between the two tests shall in no cas and tested, the specific altered zone and 1000 L of gas shall be filtered through a clean, white 0.45 micron filter at a minimum flow rate of 100 Nl/minute (3.5 scfm). Nitrogen NF or the system gas. The test shall be for total hydrocarbons (as methane) and halogenated hydrocarbons - For each positive pressure medical gas system, the purity of the piping system shall be verified. Test gas shall be oil purge produces no discoloration in a white cloth loosely held over the adapter during the purge. - ection between the new work and the existing system shall be leak - medical gas shall be verified. Test gas shall be oil - pressure gases, immediately after the final connection is made and leak 2 ppm. components in the immediate zone or area that is downstream form the point o pletion of standing pressure test is required. e tested at the outlet most remote form the source 1 ppm and Halogenated Hydrocarbons If any outlet fails, the most remote outlet in every zone shall be tested Filter shall accrue no more than 1 mg of matter from any outlet tested Using an appropriate adapter, a high purge rate (8scfm) will be estab purging of each medical gas pipeline shall be done. The cleanliness of the piping in each If not accessible a successful com compared with the source gas. exceed, Total Hydrocarbons (10 degrees F) @ 50 psig. Each joint in the final conn 25% of the zones shall b Piping Purge Test. 5.1.12.3.7 Verifier Piping Particulate Test 5.1.12.3.6 Verifier Piping Purge Test 5.1.12.3.8 Verifier Piping Purity Test - in Test For positive - 5.1.12.3 System Verification In or 5.1.12.3.9 Verifier Final Tie A N/A N/A N/A N/A Fail Pass 5/245/245/245/245/245/245/245/24 of 12 9 Page n the medical gas piping systems where the user makes Medical surgical vacuum inlets shall draw 85 Nl/min without reducing the vacuum pressure below 12 in. HgV at any adjacent After purging each piping system with the gas of system designation, each pressure gas source and outlet shall be analyzed d by this standard for all components, station outlets/inlets, shutoff valves, All oxygen and medical air outlets serving critical care areas shall permit a transient flow rate of 170 55 psi. Medical air source shall be analyzed for concentration of contaminants by volume prior to the source vale being opened. 0 Nl/min with a pressure drop of no more than 5 psi and static pressure of 160 to 185 psi 5 psi and static pressure of 50 free, dry Nitrogen NF or gas of system designation. sheets. Testing of source equipment performed and results are recorded on individual equipment Medical gas outlets shall deliver 100 NL/min with a pressure drop of no more than Operational pressure tests shall be performed at each station outlet i - connections and disconnections. Performed with either oil Sample shall be taken at the system sample port. The presence and correctness of labeling require for concentration of gas by volume. and alarm panels, shall be verified. Nl/min (6 SCFM) for 3 seconds. Nitrogen outlets shall deliver 14 5.1.12.3.12 Medical Air Purity Test (Air Compressor) Critical care flow test 5.1.12.3.10 Verifier Operational Pressure Test cal Gas Concentration Test 5.1.12.3.14 Source Equipment Verification station inlet N/AN/AN/A N/A 5.1.12.3.13 Labeling 5.1.12.3.11 Medi Fail Pass 5/245/245/245/245/24 5/24 of 12 10 Page Labeling Outlet PPPPPPPPPPPPPPPPPPPP Gauge Function P Lock PPPPPPPPPPPPPPPPPPPP Leakage Leakage Outlet Inlet P PPPPPPPPPPPPPPPPPPPP Function P O2 161/MA 170 Critical Care Flow n/an/an/an/an/an/an/an/a PPPPPPPPPPPP Access P Label Vacuum Max Flow 00000000 n/an/an/an/an/an/an/an/an/an/an/an/a 1515151515151515 P Operational Pressure Test PASS CC Nurses Station Vac n/a CC Nurses Station LocationPPPPPPPPPPPPPPPPPPPP PASSPASS MA A A Location: (slpm) Test Flow 100100100100100100100100100100100100 8585858585858585 PASSPASS O2 Pass/Fail PASS PassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPass PassFail or CC Rooms 1 thru 10 Medical Gas Monitored outlet/inlet oom info location WallWallWallWallWallWallWallWall Line Pressure High MA, Vac Line Pressure Low Area Alarm Test Valve Test R O2, oom 1234 oom oom oom Gas or Service Vac VacVacVacVacVacVacVacVac O2O2O2O2O2O2O2O2 Zone MAMAMAMA RRRR A of 12 11 Page Labeling Outlet PPPPPPPPPPPPPPPPPPPPPPPPP Function Lock PPPPPPPPPPPPPPPPPPPPPPPPP Leakage Outlet Inlet PPPPPPPPPPPPPPPPPPPPPPPPP O2 161/MA 170 Critical Care Flow n/an/an/an/an/an/an/an/an/an/a PPPPPPPPPPPPPPP Vacuum Max Flow 0000000000 n/an/an/an/an/an/an/an/an/an/an/an/an/an/an/a 15151515151515151515 Operational Pressure Test PPPPPPPPPPPPPPPPPPPPPPPPP (slpm) Test Flow 100100100100100100100100100100100100100100100 85858585858585858585 t) PassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPassPass PassFail or (con CC Rooms 1 thru 10 outlet/inlet oom info location WallWallWallWallWallWallWallWallWallWall R 56789 oom oom oom oom oom Gas or Service Vac VacVacVacVacVacVacVacVacVacVac O2O2O2O2O2O2O2O2O2O2 MAMAMAMAMA RRRRR A of 12 12 Page 41°F @ 50 psig41°F @ 50 psig 5°C @ 50 psig5°C @ 50 psig Dew PointDew Point PassPass Labeling Outlet PPPPP Function Lock PPPPP Hydrocarbons < Hydrocarbons Halogenated Halogenated PassPass < 2ppm 2ppm Leakage Outlet Inlet PPPPP Total Hydrocarbons as Total Hydrocarbons as O2 161/MA 170 Critical Care Methane Methane PassPass < 1ppm< 1ppm Flow n/an/a PPP Vacuum Piping Purity DataPiping Purity Data Max Flow 00 n/an/an/a 1 mg @ 35 cuft1 mg @ 35 cuft 1515 ParticulatesParticulates PassPass Operational Pressure Test ParticulatesParticulates PPPPP sual Visual Medical Gas Pipeline Purge & Purity Test PassPass Vi PassPass OilOil (slpm) Test Flow 100100100 8585 t) PassPass OdorOdor PassPassPassPassPass PassFail or (con PASS CC Rooms 1 thru 10 Visible Visible MoistureMoisture PASS PassPass outlet/inlet oom info - Medical Air Pipeline location WallWall - Oxygen Pipeline R Gas TypeGas Type 10 oom Gas or Service N2N2 Vac VacVac O2O2 MA R A