Loading...
Holy Rosary Parish BLD20100013.DOC EDMONDS FIRE DEPARTMENT MEMORANDUM Date: February 25, 2010 To: File From: Mike Smith, Fire Marshal 425-775-7720 Subject: Holy Rosary Parish The project was reviewed under the 2006 IFC with Washington State Amendments and the ECDC. 1) Fire Connection Permit is required and must be issued with the main building permit (this is not a deferred submittal). 2) Portable Fire Extinguishers are required/minimum size 2A10:B:C and spaced so maximum travel distance is no more than 75 feet from any building location. (I did not see them marked on the plans) 3) Deferred submittals are Fire Sprinkler, Fire Alarm, Fire Protection Foot Print, Life Safety Plan, and Fire Lane Stripping requirements. 4) At the start of construction the building owner shall designate a Fire Prevention Program Superintendent. Contact my office for more details and responsibilities. 5) Varify lighting (Exit and Emergency) on your Exiting Plan match your Electrical Reflected Ceiling Plans. 6) Please locate the Fire Alarm Panel in the Sprinkler Riser Room. Please Resubmit plans with these additions.