Holy Rosary Parish BLD20100013.DOC
EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: February 25, 2010
To: File
From: Mike Smith, Fire Marshal 425-775-7720
Subject: Holy Rosary Parish
The project was reviewed under the 2006 IFC with Washington State Amendments
and the ECDC.
1) Fire Connection Permit is required and must be issued with the main building
permit (this is not a deferred submittal).
2) Portable Fire Extinguishers are required/minimum size 2A10:B:C and spaced so
maximum travel distance is no more than 75 feet from any building location. (I
did not see them marked on the plans)
3) Deferred submittals are Fire Sprinkler, Fire Alarm, Fire Protection Foot Print, Life
Safety Plan, and Fire Lane Stripping requirements.
4) At the start of construction the building owner shall designate a Fire Prevention
Program Superintendent. Contact my office for more details and
responsibilities.
5) Varify lighting (Exit and Emergency) on your Exiting Plan match your Electrical
Reflected Ceiling Plans.
6) Please locate the Fire Alarm Panel in the Sprinkler Riser Room.
Please Resubmit plans with these additions.