HSAC 160 W Dayton Addition.DOC
EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: March 4, 2009
To: File
From: Mike Smith, Fire Marshal 425-775-7720
Subject: 160 W Dayton HSAC Addition BLD20090063
The Fire Department has the following comments:
1) Apply for a Fire Connection Permit. This permit must be issued along with the
building permit.
2) On the plans you show an area where fire sprinklers are to be installed. Please
show a 3 hour separation which may allow you to avoid sprinklering the whole
building since you have an S-2 under the old and new addition.
3) Correct size of portable fire extinguishers to read 2A10:B:C
4) Show specs, ratings and cut sheets on the roll down fire doors. On a side note
the doors operate from the Fire Alarm panel and are closed when a sprinkler
water flow alarm is received or with spot smoke detectors on each side of the
openings.
This information should be included on these plans.
5) Deferred submittals include Fire Sprinkler and Fire Alarm permits.
6) Upgrade the three closest fire hydrants to the project with Stortz Fittings, 4 inch
in size.