HSAC 160 W Dayton Addition.DOC EDMONDS FIRE DEPARTMENT MEMORANDUM Date: March 4, 2009 To: File From: Mike Smith, Fire Marshal 425-775-7720 Subject: 160 W Dayton HSAC Addition BLD20090063 The Fire Department has the following comments: 1) Apply for a Fire Connection Permit. This permit must be issued along with the building permit. 2) On the plans you show an area where fire sprinklers are to be installed. Please show a 3 hour separation which may allow you to avoid sprinklering the whole building since you have an S-2 under the old and new addition. 3) Correct size of portable fire extinguishers to read 2A10:B:C 4) Show specs, ratings and cut sheets on the roll down fire doors. On a side note the doors operate from the Fire Alarm panel and are closed when a sprinkler water flow alarm is received or with spot smoke detectors on each side of the openings. This information should be included on these plans. 5) Deferred submittals include Fire Sprinkler and Fire Alarm permits. 6) Upgrade the three closest fire hydrants to the project with Stortz Fittings, 4 inch in size.