Loading...
INSPECTION AND TESTING FORM FIRE ALARM.pdfBRED HAWK Fire & Security INSPECTION AND TESTING FORM DATE: 3/29/19 TIME: TESTING ORGANIZATION PROPERTY NAME (USER) Name: Red Hawk Fire & Security Name: 85c Bakery Cafe Address: 21312 30t" Drive SE Address: 22611 76th Avenue W, Space 100 Bothell, WA 98021 Edmonds, WA 98026 Representative: Red Hawk Fire & Security Owner Contact: License No.: REDHAHF882NH Telephone: Telephone: (425) 486-2600 MONITORING ENTITY APPROVING AGENCY Contact: Alarm Center Contact: Telephone: 1-866-402-3673 Telephone: Monitoring Account AES-6009 Ref No.: TYPE TRANSMISSION SERVICE • McCulloh 0 Weekly • Multiplex 0 Monthly • Digital 0 Quarterly • Reverse Priority 0 Semiannually x RF (Radio) 0 Annually 0 Other (Specify): 0 N/A Control Unit: Notifier Model No.: NFW-10OX Circuit Styles: 4, Class B No. of Circuits: 1 Software Rev.: 9. Last Date System Had Any Service Performed: 3/29/19 Last Date That Any Software or Configuration Was Revised: 3/29/19 ALARM INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Devices Installed Circuit Style Quantity of Devices Tested 7 Style 4 7 Manual Fire Alarm Boxes N/A N/A N/A Ion Detectors 1 Style 4 1 Photo Detectors N/A N/A N/A Duct Detectors 28 Style 4 28 Heat Detectors N/A N/A N/A Waterflow Switches N/A N/A N/A Supervisory 2 Style 4 2 Monitor Only Kitchen Hood Alarm verification feature is X enabled 0 disabled. Revised 06/20/2007 by JML. I ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION Quantity of Appliances Installed Circuit Style Quantity of Appliances Tested N/A N/A N/A Bells N/A N/A N/A Horns 10 Style 4 10 Visuals 12 Style 4 12 Horns W/ Visuals N/A N/A N/A Speakers N/A N/A N/A Speaker W/ Strobes No. of alarm notification appliance circuits: Are circuits monitored for integrity? f) Yes 0 No SUPERVISORY SIGNAL -INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Devices Installed Circuit Style Quantity of Devices Tested N/A N/A N/A Building Temp. N/A N/A N/A Site Water Temp. N/A N/A N/A Site Water Level N/A N/A N/A Fire Pump Power N/A N/A N/A Fire Pump Running N/A N/A N/A Fire Pump Auto Position N/A N/A N/A Fire Pump or Pump Controller Trouble N/A N/A N/A Fire Pump Running N/A N/A N/A Generator in Auto Position N/A N/A N/A Switch Transfer N/A N/A N/A Generator Engine Running Other: SIGNALING LINE CIRCUITS Quantity and style of signaling line circuits connected to system. Quantity: 2 Style(s): Style 4 SYSTEM POWER SUPPLIES (a) Primary (Main): Nominal Voltage 120V Amps Overcurrent Protection: Type Breaker Amps 20 Location (of Primary Supply Panelboard): By back door in kitchen Disconnecting Means Location: By back door in kitchen (b) Secondary (Standby): Storage Battery: Amp-Hr Rating 12AMP-hr Calculated capacity in 24 AMP-Hrs to operate system for 4 Hours. Engine -driven generator dedicated to fire alarm system: N/A Location of fuel storage: N/A TYPE BATTERY • Dry Cell (c) Emergency or standby system used as a backup to primary power • Nickel -Cadmium supply, instead of using a secondary power supply: x Sealed Lead -Acid x Emergency system described in NFPA 70, Article 700 0 Lead -Acid x Legally required standby described in NFPA 70, Article 701 0 Other (Specify): x Optional standby system described in NFPA 70 Article NOTIFICATIONS ARE MADE Monitoring Entity Building Occupants Building Management Other (Specify) AHJ Notified of Any Impairments 702, which also meets the performance requirements of Article 700 or 701 PRIOR TO ANY TESTING YES NO x i) x i) x f) x i) Revised 06/20/2007 by JML. PRE -TEST SYSTEM TESTS TYPE Visual Functional Comments Control Unit x x Interface Equipment x x Lamps/LEDs x x Fuses x x Primary Power Supply x x Trouble Signals x x Disconnect Switches x x Ground -Fault Monitoring x x SECONDARY POWER TYPE Visual Functional Comments Battery Condition x x Load Voltage x x Discharge Test x x Charger Test x x Specific Gravity x x TRANSIENT SUPPRESSORS x x REMOTE ANNUNCIATORS x x Located in Bakery by back door NOTIFICATION APPLIAMCES x x EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Comments Phone Set N/A Phone Jacks N/A Off -Hooks Indicator N/A Amplifier(s) N/A Tone Generator(s) N/A System Performance N/A Device Simulated COMBINATION SYSTEMS Visual Operation Operation Fire Extinguisher Monitoring Device/System Carbon Monoxide Device/System t> () t> (Specify): N/A 0 (? 0 INTERFACE EQUIPMENT (Specify): N/A (? (? f? (Specify): N/A 0 0 0 (Specify): N/A 0 0 0 System restored to normal operation: Date: 3/29/19 Time: AM THIS TESTING PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS. Name of Inspector: Dave Rasmussen Date: 3/29/19 Time: AM Signature: Name of Owner or Representative: Date: Time: Signature: Revised 06/20/2007 by JML. 3