Jacobsen Marine Preapp.DOC
MEMORANDUM
Date:August 29, 2007
To:Development Services
From:Mike Smith, Fire Inspector 425-775-7720
Subject:Preapp Jacobsen’s Marine 345 Admiral Way
The Fire Department has reviewed the preapp under the 2006 IFC, the ECDC and
NFPA 303.
1) Required permits/submittals include
A. Fire Sprinkler System Permit/ proposed building requires an NFPA 13
fire sprinkler system
B. Fire Connection Permit/ must be submitted at the same time as the civil
plans. See handout.
C. Fire Alarm Permit/ fire alarm system required for offsite sprinkler system
monitoring to include local audible-visual and building exterior
notification.
D. Fire Protection Footprint/ required. See attached.
2) Building drawings appear to indicate a mixed use business (Business Office,
Showroom, and Repair Area) Please indicate on plans the uses for the
designated areas with building separations if applicable.
Will flammable finishes, storage of hazardous materials, welding, exchange of
fluids and storage of same, waste oil collection, etc. be conducted on site? If so
reference 2006 IFC Chapters 15 (Flammable Finishes), 26 ( Welding),
34 (Flammable and Combustible Liquids), Section 105 Permits, NFPA 303 and
the 2006 IBC.
3) Portable fire extinguishers are required in building. Protected area will dictate
minimum spacing and size.
4) Fire Department Lock Box required. Please call 425-775-7720 for authorization
to purchase and instructions for installation.
5) Fire Prevention Program Superintendent (IFC 1408) required on site during
construction with authority to stop work and mitigate any environmental or
hazardous materials concerns.
City of Edmonds Fire Department