Jacobsen Marine Preapp.DOC MEMORANDUM Date:August 29, 2007 To:Development Services From:Mike Smith, Fire Inspector 425-775-7720 Subject:Preapp Jacobsen’s Marine 345 Admiral Way The Fire Department has reviewed the preapp under the 2006 IFC, the ECDC and NFPA 303. 1) Required permits/submittals include A. Fire Sprinkler System Permit/ proposed building requires an NFPA 13 fire sprinkler system B. Fire Connection Permit/ must be submitted at the same time as the civil plans. See handout. C. Fire Alarm Permit/ fire alarm system required for offsite sprinkler system monitoring to include local audible-visual and building exterior notification. D. Fire Protection Footprint/ required. See attached. 2) Building drawings appear to indicate a mixed use business (Business Office, Showroom, and Repair Area) Please indicate on plans the uses for the designated areas with building separations if applicable. Will flammable finishes, storage of hazardous materials, welding, exchange of fluids and storage of same, waste oil collection, etc. be conducted on site? If so reference 2006 IFC Chapters 15 (Flammable Finishes), 26 ( Welding), 34 (Flammable and Combustible Liquids), Section 105 Permits, NFPA 303 and the 2006 IBC. 3) Portable fire extinguishers are required in building. Protected area will dictate minimum spacing and size. 4) Fire Department Lock Box required. Please call 425-775-7720 for authorization to purchase and instructions for installation. 5) Fire Prevention Program Superintendent (IFC 1408) required on site during construction with authority to stop work and mitigate any environmental or hazardous materials concerns. City of Edmonds Fire Department