EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: August 29, 2008
To: File
From: Mike Smith, Acting Fire Marshal
Subject: Jantz Addition 547 Dayton BLD20080287
The Fire Department has the following comments:
1) It appears there may still be an exiting issue(s). Please reference Ann Bullis’s
comments on her review.
2) Apply for a Fire Connection Permit. I will send you the City’s handout which
also includes requirements for the Fire Alarm and the Fire Sprinkler submittals.
3) You have located the sprinkler riser room towards the rear of the building. A
better location may be on the street side of the building closest to the water
main on Dayton Street. Requirements included in the Fire Connection Handout
will clarify this.
4) Maximum travel distance to portable fire extinguishers is 75 feet. Verify the
distances on the new and existing construction.
5) Deferred submittals will include Fire Sprinkler, Fire Alarm and Fire Protection
Footprint.