October 18, 2010
Mr. Jeremy Carter
Progressive Air Systems
17711 Interurban blvd.
Snohomish, WA 98296
SUBJECT: Plan Review – Jantz building mechanical – 547 Dayton St. Edmonds
Dear Mr. Carter:
I reviewed the permit application submitted for the mechanical work associated with the Jantz building
addition. There is a problem with the proposed location of the garage exhaust fan and ductwork. This
exterior wall is located two feet from the adjoining property line. At this location openings in the exterior
wall are prohibited by IBC section 705.8, which prohibits all openings less than three feet from the
property line. Additionally section 501.2.1 of the IMC prohibits exhaust terminations less than three feet
from the property line. The exhaust system for the garage will need to be redesigned to comply with the
required minimum location from the property boundary.
I have approved the permit for issuance of the other HVAC work including the new roof top heat pump
and associated ductwork.
If you have any questions, you may contact me at (425) 771-0220.
Sincerely,
Leonard Yarberry
Building Official