Lift Station 7and8.pdf Eagle Eye Consulting Engineers, P.S. PO Box 523 Olalla, WA 98359 hoytjeter@centurytel.net 360 874 0562 Fax 360 874 0591 To: Marie Harrison th 121 5 Ave N Edmonds, WA 98020 Re: Lift Station 7 & 8 209 West Dayton Edmonds, WA 98020 Plan Review # 2008-0545 EECE # EDM 08-64 Plan review number 01 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back-check time. SCOPE OF REVIEW Structural and Ordinance The scope of this review is for therequirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. STRUCTURAL COMMENTS General 1.The analysis submitted state there is a geotechnical report for this project. Please submit this upon response. 2.Please add to the drawing the required earthquake design data per IBC 1603.1.5 3.Please provide a key of the analysis to show which pile design is for which pile. It is not clear based off the information submitted at this time. 4.The shoring wall used a program prepared by civiltech. Please submit the portion of the manual specific for this project for review. With out this information there is Page 2 of 4 Plan Review Number 01 EECE#: EDM 08-64 Lift Station 7 & 8 2008-0545 no way tell if the program is design to the most current adopted code. The references specified are not in the IBC reference standards. 5.Please note continuous special inspections for the fillet welds exceeding 5/16” weld. The drawings note 3/8” weld will be used. IBC table 1704.3 item 5. 6.Please note on the drawings for the required periodical weld inspections per IBC table 1704.3 7.Please add to the drawing the required inspections for the pile foundations. IBC table 1704.8 Sheet G-5: 8.The adopted code for the State of Washington and the city of Edmonds is the 2006 edition of the code and not the 2003. Please modify the drawings accordingly. Sheet1 of 4 Sheet Pile Shoring 9.The drawings have three sections A-A noted. It is not clear which sections shall be used where since they have the same call out. Please modify in order to complete the review. 10.Please submit area and the moment of inertia structural information for the CZ114 or PZ323 sheet pile material and sections. This should be added to the drawings. This was not in the submitted information. Sheet2 of 4 Sheet Pile Shoring 11.Please submit area and the moment of inertia structural information for the LZ3 or SZ12 sheet pile material and sections. This should be added to the drawings. This was not in the submitted information 12.Please submit area and the moment of inertia structural information for the PZ7 or SZ375 sheet pile material and sections. This should be added to the drawings. This was not in the submitted information Sheet3 of 4 Sheet Pile Shoring 13.Please submit area and the moment of inertia structural information for the PZ22 or XZ85 sheet pile material and sections. This should be added to the drawings. This was not in the submitted information Sheet4 of 4 Sheet Pile Shoring Page 3 of 4 Plan Review Number 01 EECE#: EDM 08-64 Lift Station 7 & 8 2008-0545 No comment for this sheet at this time General LS7 14.Please add the seismic qualifications requirements for the mechanical and electrical per IBC 1708.5 to the drawings. 15.Please add to the drawing the required earthquake design data per IBC 1603.1.5 Sheet S7-1 LS7 Foundations / Lower Floor Plan No comment for this sheet at this time Sheet S7-2 LS7 Intermediate Floor Plan No comment for this sheet at this time Sheet S7-3 LS7 Grade Floor Plan No comment for this sheet at this time Sheet S7-4 LS7 Structural Sections 1 16.Engineer of Record (EOR), please specify the required placed location of the reinforcement steel. 17.EOR, please submit analysis for the elevated concrete stairs. Sheet S7-5 LS7 Structural Sections 2 18.EOR, please specify the required placed location of the reinforcement steel. Sheet S7-6 LS7 Structural Details 1 19.Detail 6: EOR, please specify the required adhesive anchor system to be used shown in this detail. This appears not to be specified on the drawings. Sheet S7-7 LS7 Structural Details 2 No comment for this sheet at this time General LS8 20.Please submit geotechnical report for this project. The design analysis states values from the geotechnical report but this was not submitted at this time. Page 4 of 4 Plan Review Number 01 EECE#: EDM 08-64 Lift Station 7 & 8 2008-0545 Sheet S8-1 LS8 Demolitions Plan and Details No comment for this sheet at this time Sheet S8-2 LS8 Structural Plan 21.EOR, please specify the required expansion bolt that is going to be used for the connections. Sheet S8-3 LS8 Access Structural Sections and Details No comment for this sheet at this time Sheet S8-4 LS8 Structural Sections and Details 22.Detail 1: EOR, please specify the required embedment for the ½ diameter expansion bolt in order to check the capacity. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874- 0562 between 8:00 a.m. and 5:00 p.m. By: Hoyt Jeter, P.E. President