MacGregor Pl Test Certifications.pdf�ET�g
DRY SYSTEM
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
SMITH FIRE SYSTEMS, INC.
3813 - 168th Street NE • Suite 1
Arlington, WA 98223
BUS (360) 651-7701
k� FAX (360) 651-2419
Contr. Reg. No. SMITHFS1360T
PROJECT NAME
PROJECT ADDRESS
5TH & WALNUT MIXED USE
437 5TH AVENUE SOUTH
EDMONDS. WASHINGTON 98020
SYSTEM NO. 1 1
PROCEDURE
AUTHORITY HAVING
JURISDICTION
SERVES PARKING LEVEL
JOB NO. N1 k - 159
Upon completion of work, inspection and tests shall be made by the contractors representatives and witnessed by an AHJ and/or owner's
representative. All defects shall be corrected and systems left in service before contractor's personnel finally leaves the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor„ It is
understood that owner's representative's signature in no way prejudices any claim, against contractor for faulty material, poor workmanship, or failure
to m N with a rovi�n authont "s� requirements or local ordinances.
CITY OF EDMONDS
121 5TH AVE. NO., EDMONDS, WA. 98020
PIPE AND
...
PIPE CONFORMS TO NFPA 13 - 1996 STANDARD
®YES ❑ NO
FITTINGS
FITTINGS CONFORM TO NFPA 13 - 1996 STANDARD
YES ❑I NO
WELDED
Do you certify as the sprinkler contractor that welding procedures comply with the requirements of at least
Q YES ❑ NO
AWS D10,9, level AR -3?
PIPING
Cf) Do you certify that the welding was performed by welders qualified in compliance with the requirements of at
®YES ❑ NO
>_ least AWS D10 9, level AR -3?
YES ❑ NO
Do you certify that welding was carried out in compliance with a documented quality control procedure to
YES ❑ NO
ensure that all discs are retrieved, that openings in piping are smooth, that slag and other welding residue are
removed, and that the internal diameters of piping are not penetrated?
HYDROSTATIC TEST
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi for two hours or 50 psi above static pressure in excess of 150psi for two
hours. Differential dry -pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be stopped.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS?
0 YES ❑ NO
IF NO, STATE REASON
TEST WITNESSED BY
r
FOR O D
SIGNATURE � ® TITLE 'F-'Vr„ M f '.�i 1
DATE 1 l U 7
PNEUMATIC TEST
PNEUMATIC: Establis40 psi air pr „sure and easure drop which shall not exceed 1 '/ psi in 24 hours. Test pressure tanks at normal water level
and air pressure and m1air pressure drop w ich shall not exceed 1 'Y2 psi in 24 hours,
DRY PIPING PNEUMATICALLY TESTED?
M YES ❑ NO
IF NO, STATE REASON
FOR (WW ER
SIGNATURE
C a
S /d
TEST WITNESSED BY
TITLE I °✓
DATE /
FLUSHING
Underground mains and lead-in connections to system risers flushed before connection made to sprinkler piping.
VERIFICATION
VERIFIED BY COPY OF UNDERGROUND PIPING TEST CERTIFICATE?
N YES ❑ NO
FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING?
® YES ❑ NO
❑ OTHER -EXPLAIN
ADDITIVE AND
DO YOU CERTIFYAS THE SPRINKLER CONTRACTOR THATADDITIVES AND CORROSIVE CHEMICALS,
CORROSIVE CHEM-
SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS
®YES [I NO
ICAL VERIFICATION
WERE NOT USED FOR TESTING SYSTEM OR STOPPING LEAKS?
BLANK TEST GASKETS
Number Used: 0 Locations
Number Rernoved: 0
YROf`
TEMP.
MANUFACTURER TYPE MODEL MFG. K -FACTOR
RATING°Fi QUANTITY
RELIABLE SSU G 2002 5.6
165° 125
RELIABLE HSW G 2002 1 5.6
165° 1
..... - .M
RELIABLE DRY SSP G3-2002 5.6
165° 12
SPRINKLERS
TOTAL 1 138
ALARM DEVICE
ALARM DEVICE
MAX. TO OPERATE THRU TEST PIPE
TYPE MAKE
MODEL
MIN,
SEC.
PRESSURE SWITCH POTTER ELECTRIC
PS10-2
1�
DRY VALVE
O.O.D.
DRY PIPE
OPERATING
MAKE MODEL SERIAL NO.
MAKE MODEL
SERIAL NO,
TEST
VICTAULIC [7:5:6 NIA7AIRPRESSURE
NIA
N/A
NIA
TIME WATER
ALARM
TIME TO TRIP' WATER
TRIP POINT
REACHED
OPERATED
PRESSURE
AIR
TEST OUTLET,
PROPERLY
PRESSUREMIN.SEC.
PSI SI PSI MIN. SEC.
YES NO
Without Q.O.D.
With Q.O.D.
IF NO, EXPLAIN
`MEASURED FROM THE TIME THE INSPECTOR'S TEST CONNECTION VALVE IS OPENED.
EQUIPMENT
EQUIPMENT OPERATES PROPERLY
EM YES ❑ NO
OPERATION
IF NO, EXPLAIN
INSTRUCTIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES
JJYES ❑ NO
AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES?
1. SYSTEM COMPONENTS INSTRUCTIONS
® YES []NO
2. CARE AND MAINTENANCE INSTRUCTIONS
DYES ❑ NO
3. NFPA 25
❑ YES 0 NO
HYDRAULIC DATA
NAME PLATE PROVIDED
YES ❑ NO
NAMEPLATE
IF NO, EXPLAIN
CUT OUT (DISC)
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUT OUTS (DISCS) ARE
0 YES ❑ NO
RETRIEVED?
CERTIFICATION
IF NO, EXPLAIN
LOCATION MAKE &
PRESSURE
MODEL SETTING STATIC PRESSURE RESIDUAL PRESSURE
FLOW RA'T'E
REDUCING
INLET (PSI)
OUTLET (PSI)
INLET (PSI)
OUTLET (PSI)
FLOW (GPM)
VALVEINSTALLED
❑ YES NO
EN STUDS ARE USED IN CONCRETE, HAS REPRESENTATIVE SAMPLE TESTING BEEN
❑ YES ❑ NO
POWDER DRIVEN
SATISFACTORILY COMPLETED?
STUD INSTALLED
IF NO, EXPLAIN
❑ YES EM NO
IN-SERVICE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN
57-1—A
DATE
—/_
MAIN DRAIN
READING GAUGE LOCATED NEAR WATER SUPPLY TEST PIPE
RESIDUAL PRESSURE WITH VA4VES IN TEST
PIPE
TEST
STATIC PRES RE ; Q [ Sl
OPEN WIDE: �/T (�L) PSI
FINAL ACCEPTANCE
FOR l , F
SIGNATURE ? "` J"
TITLE- DATE S /7-41
TEST WITNESSED BY
H FIR6
FOR VMS
DAATITLE
1n,
�AjDATE
SIGNATURE
CERTIFICATION
I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT
THIS SPRINKLER SYSTEM WAS INSTALLED IN ACCORDANCE
WITH RCE 16-160 AND THE RULES ADOPTED BY THE
mow. Inc.
WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY
ct"Ille r r
THE STATE FIRE MARSHALL.
or
TOM HINTON
A `" 3
1-11<
NAME OF CERTIFICATE OF COMPETENCY HOLDER
If PRINT OR YPE;)
.�d�•
Am'- J-jo �__
--- _tEC:V HOLDFR
CIf_NATI IRF (1F f �
IA,� "e^�j";'•.
olig'lNi MCI"
CERTIFICATE REGISTRATION # 391-11-2369
PERMIT# 2002-0235 DATE 3
�9TH
WET SYSTEM
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
SMITH FIRE SYSTEMS, INC.
3813 - 168th Street NE • Suite 1
Arlington, WA 98223
uuIlopy
BUS (360) 651-7701
FAX (360) 651-2419
Contr. Reg. No. SMITHFS1360T
PROJECT" NAME
5TH & WALNUT MIXED USE JOB NO, N1
t 159
PROJECT ADDRESS
437 5TH AVENUE SOUTH
EDMONDS, WASHINGTON 98020
SYSTEM NO.
2 SERVES FIRST FLOOR
PROCEDURE
Upon completion of work„ Inspection and tests shall be made by the contractor's representatives and witnessed by an AhIJ and/or owner's representative
Ali defectis shall be corrected and systems left in service before contractor's personnel finally leaves the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is
understood that owners representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to
I
com pivwith approving authority's requirements or local ordinances.
AUTHORITY" HAVING
CITY OF EDMONDS
JURISDICTION
121 5TH AVE. NO, EDMONDS, WA. 98020
PIPE AND
PIPE CONFORMS TO NFPA 13 - 1996 STANDARD
YES ❑ NO
FITTINGS
Fii1iNGS CONFORM TO IN FPA 13 -1996 STANDARD
® YES ❑ NO
WELDED PIPING
Do you certify as the sprinkler contractor that welding procedures comply with the requirements of at
® YES ❑ NO
least AWS D10.9, level AR -3?
91 YES ❑ NOW
Do you certify that the welding was performed by welders qualified in compliance with the requirements
fR YES ❑ NO
of at least AWS D10.9, level AR -3?
Do you certify that welding was carried out in compliance with a documented quality control procedure
IH YES ❑ NO
to ensure that all discs are retrieved, that openings in piping are smooth, that slag and other welding
residue are removed, and that the internal diameters of piping are not penetrated?
HYDROSTATIC TEST
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi for two hours or 50 psi above static pressure in excess of 150psi for two hours.
Differential dry -pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be
stopped.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS?
® YES ❑ NO
IF NO, STATE
REASON r' ,
TEST WITNESSED BY
FOR F'
SIGNATURE TITLE
DATE _51 7
FLUSHING
rg nd ma s and lea -in connections to system risers flushed before connection made to sprinkler piping.
9
VERIFIED BY COnd
UNDER ROUND P ING TEST CERTIFICATE?
U
® YES ❑ NO
FLUSHED BY INS LLER OF UNDEI 'ND SPRINKLER PIPING?
® YES ❑ NO
OTHER — EXPLAIN
ADDITIVE ,AND
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
CORROSIVE CHEM-
SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT
® YES ❑ NO
ICAL VERIFICATION
USED FOR TESTING SYSTEM OR STOPPING LEAKS?
BLANK TEST GASKETS
Number Used 0 Locations
Number Removed 0
YR. OF
TEMP.
MANUFACTURER TYPE MODEL MFG, K - FACTOR
RATING °F OUANTIT
RELIABLE
SSU
G
2002 5.6
165°
4
RELIABLE
SSP
F1FR
2002 5.6
155°
95
RELIABLE
HSW
F1 FR
2002 5.6
155°
11
RELIABLE
I DRY HSW
G3A
2002 5.6
165°
4
SPRINKLERS
TOTAL 1 114
ALARM DEVICE
. TO OPERATE THRU TEST' PIPE
ALARM DEVICE
TYPE
MAKE MODEL
MIN.
SEC.
WATERFLOW SWITCH
POTTER ELECTRIC VSR-F
m
g
YES NO
EQUIPMENT
EQUIPMENT OPERATES PROPERLY
OPERATION
IF NO, EXPLAIN
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES
YES ❑ NO
AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO, EXPLAIN
INSTRUCTIONS
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES?
YES ❑ NO
1. SYSTEM COMPONENTS INSTRUCTIONS
2. CARE AND MAINTENANCE INSTRUCTIONS
YES ❑ NO
3. NFPA 25
[ YES NO
YES ❑ NO
HYDRAULIC DATA
NAME PLATE PROVIDED
NAMEPLATE
IF NO, EXPLAIN
DO YOU CERTlrY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THATALL CUT OUTS (C1SCS) ARE
® YES ❑ NO
CUT OUT (DISC)
RETRIEVED?
CERTIFICATION
IF NO, EXPLAIN
PRESSURE
LOCATION &
FLOOR
MAKE &
MODEL
SETTING
STATIC PRESSURE
RESIDUAL PRESSURE
FLOW RATE
REDUCING
_
INLET (PSI)
OUTLET (PSI)
INLET (PSI)
OUTLET (PSI)
FLOW (GPM
VALVEINSTALLED
❑ YES ® NO
IF POWDER DRIVEN STUDS ARE
USED IN CONCRETE, HAS REPRESENTATIVE SAMPLE TESTING BEEN
❑ YES ❑ NO
POWDER DRIVEN
SATISFACTORILY COMPLETED?
STUD INSTALLED
IF NO, EXPLAIN
❑ YES NO
®
IN-SERVICE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN
DATE
MAIN DRAIN
READING GAUGE LOCATED NEAR WATER SUPPLY TEST PIPE RESIDUAL PRESSURE WITH VALVES IN TEST PIPE
TEST
STATIC PRESSURE: r� , v n PSI OPEN WIDE
PSI o
FINAL ACCEPTANCE
FOR
O Eft
SIGNATURE
r
TITLE
DATE QiJ
TEST WITNESSED BY
FOR S I H Fl E Y TEMS
SIGNATURE TITLE
r
DATE
CERTIFICATION
I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT
THIS SPRINKLER SYSTEM WAS INSTALLED IN ACCORDANCE
WITH RCE 18-160 AND THE RULES ADOPTED BY THE
WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY
THE STATE FIRE MARSHALL. a lac S
CVc
TONT HINTON °�6
NAME OF CERTIFICATE OF COMPETENCY HOLDER T+ulmy IEl tan
39I•tk,21
(PRINT OR TYPE)
,
SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER 0418 ccc rug
CERTIFICATE REGISTRATION# 391-11-2369
/
PERMIT# 2002-0235 DATE +/++ 3
mow
WET SYSTEM
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
SMITH FIRE SYSTEMS, INC.
3813 - 168th Street NE • Suite 1
Arlington, WA 98223
("N '11) 11)
BUS (360) 651-7701
FAX (360) 651-2419
Contr. Reg. No. SMITHFS1360T
SYSTEM NO.
JURISDICTION
FITTINGS
WELDED PIPING
® YES ❑ NO
H'YDROST'ATIC TEST
TEST WITNESSED BY
FLUSHING
VERIFICATION
ADDITIVE AND
CORROSIVE CHEM-
ICAL VERIFICATION
BLAND TEST GASKETS
SPRINKLERS
5` & WALNUT MIXED USE
------------ — _...
4
---
437 5THAVENUE SOUTH
EDMONDS, WA. 98020
3 SERVES SECOND FLOOR
N1 - 159
Upon completion of work, lnspection and tests shall be made by the contractor's representatives and witnessed by an AHJ and/or owners representative
All defects shall be corrected and systems left in service before contractors personnel finally leaves the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is
understood that owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to
CITY OF EDMONDS
121 5T" AVE. NO., EDMONDS, WA. 98020
PIPE CONFORMS TO NFPA 13 - 1996
nrTTINMA r:nnrr=raRM TO NFPA 13 - 1996
STANDARD WYES u NO
STANDARD ® YES ❑ NO
----
Do you certify as the sprinkler contractor that welding procedures comply with the requirements of at
least AWS D10.9, level AR -3?
® YES ❑ NO
WDo you certify that the welding was performed by welders qualified in compliance with the requirements
} of at least AWS D10.9, level AR -3?
Do you certify that welding was carted out in compliance with a documented quality control procedure
YES ❑ NO
EYES ❑ NO
to ensure that all discs are retrieved, that openings in piping are smooth, that slag and other welding
residue are removed, and that the internal diameters of piping are not penetrated?
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi for two hours or 50 psi above static pressure in excess of 150psi for two hours.
Differential dry -pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be stopped.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS? ® YES ❑ NO
IF NO, STATE
REASON 41
FOR F D a O S
T ' f
SIGNA URE TITLE �i(�MHI%L.
DATE 9rQ
UndoGROUND ound! mai and loadIn connections to system risers flushed before connection made to sprinkler piping.
VERIFIED BY COPY C UNDERPIP G TEST CERTIFICATE?
FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING?
® YES ❑ NO
® YES '❑ NO
OTHER — EXPLAIN
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT
USED FOR TESTING SYSTEM OR STOPPING LEAKS?-
+
YES ❑ NO,,
Number Used 0 Locations
Number Removed 0
YR. OF
TEMP.
MANUFACTURER TYPE MODEL MFG. K -FACTOR
RATING °F QUANTIT
RELIABLE RECESSED SSP F1/RES 18 2002 3.9
155° 142
RELIABLE DRY HSW G3A 2002 5.6
165° 9
TOTAL
151
ALARM DEVICE
ALARM DEVICE
MAX. TO OPERATE THRU TEST PIPE
TYPE
MAKE
MODEL MIN.
SEC.
WATERFLOW SWITCH
POTTER ELECTRIC
VSR-F
A il
EQUIPMENT
EQUIPMENT OPERATES PROPERLY
® YES ❑ NO
OPERATION
IF NO, EXPLAIN
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES ® YES ❑ NO
AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO, EXPLAIN
INSTRUCTIONS
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES?
1. SYSTEM COMPONENTS INSTRUCTIONS
® YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS
® YES ❑ NO
3. NFPA 25
❑ YES NO
HYDRAULIC DATA
NAME PLATE PROVIDED
0 YES ❑ NO
NAMEPLATE
IF NO, EXPLAIN
CUT OUT (DISC)
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUT OUTS (DISCS) ARE YES ❑ NO
RETRIEVED?
CERTIFICATION
IF NO, EXPLAIN
LOCATION &
MAKE &
PRESSURE
FLOOR
MODEL
SETTING
STATIC PRESSURE
RESIDUAL PRESSURE
FLOW RATE
REDUCING
INLET (PSI)
OUTLET (PSI)
INLET (PSI) OUTLET (PSI)
FLOW (GPM)
VALVEINSTALLED�
❑ YES NO
IF POWDER DRIVEN STUDS ARE USED IN CONCRETE, HAS REPRESENTATIVE SAMPLE TESTING BEEN [I YES El NO
POWDER DRIVEN
SATISFACTORILY COMPLETED?
STUD INSTALLED
IF NO, EXPLAIN
❑ YES ® NO
IN-SERVICE
DATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN
,5 / -9 l o3
MAIN DRAIN
READING GAUGE LOCATED NEAR WATER SUPPLY TEST PIPE
RESIDUAL PRESSURE WITH VALVES IN TEST PIPE
TEST
STATIC PRESSURE: 11 Q PSI
OPEN WIDE 0 PSI
FINAL ACCEPTANCE
FOR OI"
SIGNATURE /
,
TITLE S4-tL DATE
TEST WITNESSED BY
I FOR ITH
ESfSTEMS
SIGNATURE
TITLE DATE
CERTIFICATION
I CERTIFY THAT THE INFORMATION HEREIN IS TRUE.AND THAT
THIS SPRINKLER SYSTEM WAS INSTALLED IN ACCORDANCE
WITH RCE 18-160 AND THE RULES ADOPTED BY THE
WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY
'A6016 lot.
THE STATE FIRE MARSHALL.
t Cm
TOM HINTON
-'
� T4MW1G.l9Y) Illrproar
NAME OF CERTIFICATE OF COMPETENCY HOLDER
391-11-?,469
(PRINT OR TYPE)
q.
4N Slkp-w—
sp
SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER
CERTIFICATE REGISTRATION # 391-11-2369
k%I// l/�
PERMIT# 2002-0235
J2Q
DATE u/!5/1✓
�9TH
WET SYSTEM
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
SMITH FIRE SYSTEMS, INC.
3813 - 168th Street NE - Suite 1
Arlington, WA 98223
("Opy
BUS (360) 651-7701
d FAX (360) 651-2419
Contr. Reg. No. SMITHFS1360T
SYSTEM NO.
FITTINGS
WELDED PIPING
IM YES ❑ NO
5TH & WALNUT MIXED USE
437 5TH AVENUE SOUTH
EDMONDS, WA. 98020
JOB NO. N1 — 159
4 SERVES THIRD FLOOR
Upon completion of work, Inspection and tests shall be made by the contractor's representatives and witnessed by an AHJ and/or owner's representative
All defects shall be corrected and systems left in service before contractor's personnel finally leaves the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is
understood that owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to
compli with a2proving author s re ultements or local ordinances.
CITY OF EDMONDS
121 STH AVE. NO., EDMONDS, WA. 98020
PIPE CONFORMS TO NFPA 13 - 1996 STANDARD
YES ❑ NO
® YES ❑ NO
FITTINGS CONFORM TO NFPA 13 -1996 STANDARD
Do you certify as the sprinkler contractor that welding procedures comply with the requirements of at
® YES
❑ NO
least AWS D10.9, level AR -3?
wDo you certify that the welding was performed by welders qualified in compliance with the requirements
®YES
❑ NO
} of at least AWS D10.9, level AR -3?
LL Do you certify that welding was carried out in compliance with a documented quality control procedure
M YES
❑ NO
to ensure that all discs are retrieved, that openings in piping are smooth, that slag and other welding
residue are removed, and that the internal diameters of piping are not penetrated?
HYDROSTATIC TEST HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi for two hours or bu psi above static pressure in excess or i oupsi ror two nuws.
Differential dry -pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be stopped.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS? 91 YES ❑ NO
IF NO, STATE
REASON
TEST WITNESSED BY FOR a ttlll'w C.
SIGNATURE
TITLE r• P-15 DATE -5—h/013
FLUSHING Un er0,round Mains and ead-In connections to system risers flushed
VERIFICATION VERIFIED BY CO OF'UN'DERGROUN PIPING TEST CERTIFICATE?
FLUSHED BY INSTALLER OF LINDERGR UND SPRINKLER PIPING?
OTHER — EXPLAIN
ADDITIVE AND DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
CORROSIVE CHEM- SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT
ICAL VERIFICATION USED FOR TESTING SYSTEM OR STOPPING LEAKS?`
BLANK TEST GASKETS Number Used 0 Locations
SPRINKLERS
r piping.
® YES ❑ NO
® YES ❑ NO
® YES ❑ NO,
Munitugr Removed 0
MANUFACTURER TYPE MODEL MFG. K -FACTOR RATING °F QUANTIT
RELIABLE RECESSED SSP F1/RES18 1 2002 1 3.9 155°142
TOTAL 1 142
ALARM DEVICE
ALARM DEVICE
MAX. TO OPERATE THRU TEST PIPE
TYPE MAKE
MODEL MIN.
SEC.
WATREFLOW SWITCH POTTER ELECTRIC
VSR-F
EQUIPMENT
EQUIPMENT OPERATES PROPERLY
® YES ❑ NO
OPERATION
IF NO, EXPLAIN
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES
YES ❑ NO
AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO, EXPLAIN
INSTRUCTIONS
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES?
1„ SYSTEM COMPONENTS INSTRUCTIONS
YES ❑ NO
2. CARE AND MAINTENANCE INSTRUCTIONS
YES ❑ NO
3. NFPA 25
❑ YES ® NO
HYDRAULIC DATA
NAME PLATE PROVIDED
® YES ❑ NO
NAMEPLATE
IF NO, EXPLAIN
CUT OUT (DISC)
DO YOU CERTIFY THAT YOJ HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUT OUTS (DISCS) ARE
E YES ❑ NO
RETRIEVED?
CERTIFICATION
IF NO, EXPLAIN
LOCATION &
MAKE &
PRESSURE
FLOOR
MODEL
SETTING STATIC PRESSURE
RESIDUAL PRESSURE
FLOW RATE
REDUCING
INLET (PSI)
OUTLET (PSI)
INLET (PSI)
OUTLET (PSI) FLOW (GPM)
VALVEINSTALLED
❑ YES E NO
IF POWDER DRIVEN STUDSARE USED IN CONCRETE, HAS REPRESENTATIVE SAMPLE TESTING BEEN
[I YES El NO
POWDER DRIVEN
SATISFACTORILY COMPLETED?
STUD INSTALLED
IF NO, EXPLAIN
❑ YES ® NO
IN-SERVICE
DATE
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN
MAIN DRAIN
I READING GAUGE LOCATED NEAR WATER SUPPLY TEST PIPE
RESIDUAL PRESSURE WITH VALVES IN TEST PIPE
TEST
STATIC PRESSURE: n PSI
OPEN WIDE D
PSI
FINAL ACCEPTANCE
FOR S
SIGNATURE
a.
TITLE�1 ^A �--�.4tL- DATE�
TEST WITNESSED BY
FOR 0111TH I STEMS
t
SIGNATURE
TITLE^ DATE
CERTIFICATION
I CERTIFY THAT THE INFORMATION HEREIN IS TRUEAND THAT
THIS SPRINKLER SYSTEM WAS INSTALLED IN ACCORDANCE
WITH RCE 18-160 AND THE RULES ADOPTED BY THE
WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY
too. 1sr
THE STATE FIRE MARSHALL.
o1"►p
TOM HINTON
T+omm I Hinton
NAME OF CERTIFICATE OF COMPETENCY HOLDER
391-[1-2 ma
(PRINT OR TYPE)
µTy
SIGNATURE"CCE FICA OF COMPETENCY HOLDER
P914
CERTIFICATE REGISTRATION # 391-11-2369
ffll,54S
PERMIT # 2002-0235
DATE
Ammw SMITH FIRE SYSTEMS,
INC.
( ��) BUS (360) 651-7701
�9TAS 3813 Street NE 168th S 1 FAX (360) 651-2419
Arlington, WA 98223 Contr. Reg. No. SMITHFS1360T
FIRE SPRINKLER SUPPLY LINE
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR UNDERGROUND PIPING
PROJECTNAME S FIFTH & WALNUT BUILDING
JOB NO. N1 - 159
437 Fifth Avenue
Edmonds Washington
Upon completion of work, inspection and tests shall be made by the contractor's representatives and witnessed by an AHJ
and/or owner's representative. All defects shall be corrected and systems left in service before contractor's personnel finally
leaves the job.
A certificate shall be filled out and signed by both representativ,)s. Copies shall be prepared for approving authorities, owners
and contractor. It is understood that owner's representative's signature in no way prejudices any claim against contractor for
faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances.
AUTHORITY
FOR Edmonds Fire Department
HAVING JURISDICTION
PIPE AND FITTINGS
PIPE CONFORMS TO NFPA 13 & 24 STANDARD ❑ YES ❑ NO
(. t
FITTINGS CONFORM TO NFPA 13 & 24 STANDARD ❑ YES El NO
- • "".
TYPE & CLASS OF PIPE USED: Ductile Iron - Class 52
JOINT TYPES USED: Mega -lug / Mechanical Joint
J'hIN REST, AINTS
ALL PIPE JOINTS ARE RESTRAINED WITH Meaa-lua or Flanged Fiitinas
IN ACCORDANCE WITH NFPA 13 & 24 ❑ YES []NO
IF NO, EXPLAIN
FLUSHING
Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at outlets, such as
hydrants and blow -offs. Flush at flows not less than 390 GPM for 4 -inch pipe, 880 GPM for 6 -inch pipe, 2440 GPM for 10 -inch
pipe, and 3250 GPM for 12 -inch pipe. When supply cannot produce stipulated flow rates, obtain maximum available.
UNDERGROUND PIPING WAS FLUSHED IN ACCORDANCE WITH NFPA 13 & 24 STANDARD ® YES ❑ NO
IF NO, EXPLAIN
WATER FLOW FOR FLUSHING WAS OBTAINED BY ® PUBLIC WATER MAIN ❑ TANK OR RESERVOIR ❑ FIRE PUMP
FLUSHING
Fnn Edmonds Fire DPnartment
WITNESSED BY
'--7:715L
SIGNATURE —= C 2 TITLE/� / DATE /CI—i{—i-2
HYDROSTATIC TEST
Hydrostatic test shall be made at not less than 200 psi for two hours or at 50 psi above the static pressure in excess of 150
psi for two hours.
UNDERGROUND PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS EYES ❑ NO
IF NO, EXPLAIN
JOINTS COVERED AT TIME OF TEST YES ❑ NO
IF YES, EXPLAIN r =:C & ud 12 g
FOR Edmonds Fire Department
HYDROSTATIC TEST
WITNESSED BY
SIGNATURE TITLE//L �� I%yjl��[ ! ���Z DATE 'L(riJZ
LEAKAGE TEST
REQUIRED
YES ❑ NO
LEAKAGE: NEW PIPE LAID WITH RUBBER GASKETED JOINTS SHALL, IF THE WORKMANSHIP IS SATISFACTORY, HAVE LI I I LE UR
NO LEAKAGE AT THE JOINTS, THE AMOUNT OF LEAKAGE AT THE JOINTS SHALL NOT EXCEED2 QTS. PER HOUR PER 100 JOINTS
IRRESPECTIVE OF PIPE DIAMETER, THE LEAKAGE SHALL BE DISTRIBUTED OVER ALL JOINTS. IF SUCH LEAKAGE OCCURS AT A FEW
JOINTS, THE INSTALLATION SHALL BE CONSIDERED UNSATISFACTORY AND NECESSARY REPAIRS MADE. THE AMOUNT OF
ALLOWABLE LEAKAGE SPECIFIED ABOVE MAY BE INCREASE 1 FL. OZ. PER INCH OF VALVE DIAMETER, PER HOUR, FOR EACH
METAL SEATED VALVE ISOLATING THE TEST SECTION, IF DRY BARREL HYDRANTS ARE TESTED WITH THE MAIN VALVE OPEN, SO
THE HYDRANTS ARE UNDER PRESSURE, AN ADDITIONAL 5 FL'. OZ. PER MINUTE LEAKAGE IS PERMITTED FOR EACH HYDRANT,
TOTAL AMOUNT OF LEAKAGE MEASURED
ALLOWABLE LEAKAGE
QTS PER HOUR QTS PER HOUR
HYDRANTS NUMBER OF HYDRANTS INSTALLED ALL 0 .. PERATED PROPERLY LJ YES LI NO
INSTALLED MANUFACTURER MODEL
MODEL T E
[I
YES NO N j
HYDRANT HOSE THREADS ARE INTERCHANGEABLE WITH YES NO
THOSE OF FIRE DEPARTMENT ANSWERING ALARM
CONTROL VALVES WATER CONTROL VALVES LEFT WIDE OPEN fflYES ❑ NO
IF NO, EXPLAIN
IN SERVICE DATE DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN
FOREMAN SIGNATURE—.4 DATE k
REMARKS
FINAL ACCEPTANCE FOR SMIT FIRE
SIGNATURE
FOR Ecitycls
SIGNATURE I �
EMS CONTRACTOR'S REGI 136 TRATION NO. SMITHFST
. . .... _TITLE, DATE
nt
v
I CERTIFY THAT TI INFORMtnON IT
1 .REIN IS TRUE AND THA
THIS UNDERGROt :0 SPRINK ER TEM SUPPLY PIPING
WAS INSTALLED IN ACCORDANCE I H RCW 18-160 AND THE
I�
RULES ADOPTED BY THE WASHINGTON ADMINISTRATIVE
CODE AS ADMINISTERED BY THE STATE FIRE MARSHAL.
TOM HINTON
NAME OF CERTIFICATE OF COMPETENCY HOLDER
/I (PRINT OR TYPE)
SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER
CERTIFICATE REGISTRATION # 391-11-2369
DATE PERMIT # Ag 0.2 -010.Z
441,
-A�,�w
DATE 5-1 -1 /C
SMITH FIRE SYSTEMS, INC. BUS (360) 651-7701
3813 -168th Street E - Suite 1('Opy FAX (360) 651-2419
Ar
Arlington, WA Contr. Reg. No. SMITHFS1360T
FIRE DEPARTMENT CONNECTION LINE
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR UNDERGROUND PIPIN9
PROJECT NAME
FIFTH & WALNUT BUILDING Joe NO. N1 - 159
PROJECT ADDRESS
437 Fifth Avenue
Edmonds Washin tan
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representatives and witnessed by an AHJ
and/or owner's representative. All defects shall be corrected and systems left in service before contractor's personnel finally
leaves the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners
and contractor. It is understood that owner's representative's signature in no way prejudices any claim against contractor for
faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances.
AUTHORITY
FOR Edmonds Fire Department
HAVING JURISDICTION
PIPE AND FITTINGS
PIPE CONFORMS TO NFPA 13 & 24
FITTINGS CONFORM TO NFPA 13 & 24 ® YES ❑ NO
TYPE & CLASS OF PIPE USED: Ductile Iron - Class 52 & Galvanized Schedule 40 Steel Pipe
JOINT TYPES USED: Mega -lug & fainged
JOINT
FLUSHING
FLUSHING
WITNESSED BY
ATIC TEST
HYDROSTATIC TEST
WITNESSED BY
CONNECTION
FINAL ACCEPTANCE
AI 1 PIPF ,10INTR ARF RFRTRAINPn WITH Mena - Ii in R Pinnnad
IN ACCORDANCE WITH NFPA 13 & 24 YES [:]NO
IF NO, EXPLAIN
Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at outlets, such as
hydrants and blow -offs. Flush at flows not less than 390 GPM for 4 -inch pipe, 880 GPM for 6 -inch pipe, 2440 GPM for 10 -inch
pipe, and 3250 GPM for 12 -inch pipe. When supply cannot produce stipulated flow rates, obtain maximum available.
UNDERGROUND PIPING WAS FLUSHED IN ACCORDANCE WITH NFPA 13 & 24 YES NO
IF NO, EXPLAIN
WATER FLOW FOR FILU'SH'ING W&S OBT IkJ� BY , PUBLIC WATER MAIN ❑, TANK OR RESERVOIR ❑ FIRE PUMP
SIGNATURE
Hydrostatic test -hall be
psi for two hour
UNDERGROUND PIPING F
IF NO, EXPLAIN
atatno! less than 200
JOINTS COVERED AT TIME OF TEST
IF YES, EXPLAIN /' N
FOR Ed
SIGNATURE J
FIRF r'Ir=PARTMF'NFIRF r nN�N TI@R"9"F@R
WITH THOSE OF F RE DEPARVENT A
FOR SMIT FIRE 1
SIGNATURE
FOR Ed
SIGNATURE
Tq 0 LL �,'�.,��NZr vl ' 1 L DATE i+
two hours or at 50 psi above the static pressure in excess of 1 0
YTESTED AT 200 PSI FOR 2 HOURS
® YES ❑ NO
❑ YES /N0
nt
TITLEDATE
. d�r
4t)r, ARF INTFRRHANr;FARI F YFR I 1 Nn
SWERING ALARM
nt
NO. SMITHF S1360T
44- DATE
°rrrLE4 � DATE S % i
�
TION I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND
THAT THIS UNDERGROUND SPRINKLER SYSTEM SUPPLY
PIPING WAS INSTALLED IN ACCORDANCE WITH RCW 18-160
AND THE RULES ADOPTED BY THE WASHINGTON
ADMINISTRATIVE CODE AS ADMINISTERED BY THE STATE
FIRE MARSHAL.
NAME OF CERTIFICATE OF COMPETENCY HOLDER
(PRINT OR TYPE)
L"IC'AJTEOF
SIGNATURE OF CERTIPETENCY HOLDER
DATE WI V o 3 PERMIT # a b0 a P) 0 oZ
004 I'
lee, l3I
v CerrQdf'ri
'iva�wmy 6[u�3
391.,111"61'r