MAG Plan Check Response 21 July 2017.pdfStrotkamp Architects
P.O. Box 501
Burlington WA 98233
Plan Check Comments dated 6-15-17 Response
To: City of Edmonds From: Strotkamp Architects
Community Development David Estes
Attention: Kristin Johns Pages: 5
Senior Permit coordinator
Address: 121 Fifth Ave North Date: 21 July 2017
Edmonds, WA 9020
425.771.0220 Re: BLD 1684 2016 Plan Check Comments
dated 24 April 2017 Response and other
dates
CC: Tom Strotkamp (transmittal)
David Broadus, Magic Toyota
Peter Chung, Magic Toyota
Design Team
❑ Urgent X For Review ❑ Please Comment ❑ Please Reply for Your Information
This memo is in response to the above referenced plan check comments for the building permit
submittal to clarify the issues raised in your plan check comments. These comments have been
incorporated into the "Plancheck/Const. Issue Rev "1" dated 21 July 2017 as part of this re -submittal
and are tagged on the drawings with a revision mark 1. To summarize our response to your comments
found in your review are as follows;
Building Officials Additional Comments
Item Comment Response
1 On sheet A-0.0 the structural sheets
for both the stormwater vault and the
structural engineering for the building
use the same page sequencing, please
revise.
2 Correct References to partial plans on
Sheets A-2.0 and A-2.1
See Plancheck/Const Issue Rev "1" dated 21
July 2017, Sheet A-0.0 which has been revised
to include only architectural, structural and
electrical in the building permit application.
See Plancheck/Const Issue Rev "1" dated 21 July
2017, Sheet A-2.0 an A-2.1 these references have
been corrected.
3 Provide a detail keyed to Sheet A-2.2 See Plancheck/Const Issue Rev "1" dated 21 July
and A-7.1 add accessible benches in 2017, Sheet A-2.2 for comment and added detail
locker rooms 10/A-7.2
Plan Check Comments
21 July 2017
4 Clarify and correct numbering of
partial plans sheet A-2.2
Building Department Comments
Item Comment
2.a — IBC WA amendments Section 427
2.d for electric Vehicle charging
See Plancheck/Const Issue Rev "1" dated 21 July
2017, sheet A-2.2 these references have been
updated and revised.
Response
See Plancheck/Const Issue Rev "1" dated 21
July 2017, Sheet A-2.0 for compliance with
Infrastructure ; items a, b, c & d of this section of the code, In
regard to comment a, the 5% is taken to be of
required parking spaces not total onsite
parking/display spaces. 120 required at 5% = 6
spaces. (see sheet A-1.0)
3. IBC Section 1009.8.1 Accessible
means of communication.
4.a-4.c IBC Table 1004.2.1
5. Include the open parking area in the
building area and occupancy
calculations
6.a-6.c
7
Base allowable building Heights and
Area Calculations (Table 506.2a)
IBC Section 507.4 should be 507.5
Plancheck/Const Issue Rev "1" dated 21 July
2017 See sheet A-2.1 General notes for this item
and key to location. Sections 1009.8.1 and
1009.8.2 have
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-0.1 for revised occupant
loads, exiting and common path of travel. (New
Sheet) also as part of the exiting requirements
from the parking deck a 104.10 Request for
modifications for the Occupant Load on the
parking deck is being submitted as part of this
transmittal.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-0.1 and IBC Section 104.10
Request for Modifications for Occupant load on
the Parking Deck.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-0.0 and A0.1 Revised for
tables 504.3, 504.4 and 506.2
Plancheck/Const Issue Rev "1" dated 21 July
2017 Sheet A-0.0 Improper IBC section
reference Revised to 507.5
0 Page 2
Plan Check Comments 21 July 2017
8.a-8.d Plumbing Fixture Calculations — a.) table revised on See Plancheck/Const Issue
Revise to IBC 2902.1.1 Rev "1" dated 21 July 2017 Sheet A-0.1 for
revised table complying with this comment.
Plumbing fixture requirements broke into three
areas, per prior discussion, office wing main
floor, service wing main floor and second floor
offices.
9.a-9.b IBC chapter 10 Egress plan for Plancheck/Const Issue Rev "1" dated 21 July
parking deck 2017 Sheet A-0.Iand IBC Section 104 request
for revision of occupant load from parking deck
based on actual usage have been revised to
indicate this revision.
10 ADA parking spaces per ICC This information was provided in the civil
Al 17.1.09 and 502 and engineering drawings but has been added on
sheet A-1.1 See Plancheck/Const Issue Rev "1"
dated 21 July 2017 for this information.
11. Van accessible location per IBC This information was provided in the civil
1106.5, ICC a117.1-09 , 502 engineering drawings but has been added on
sheet A-1.1 See Plancheck/Const Issue Rev "1"
dated 21 July 2017 for this information.
12. Improper references given on partial See Plancheck/Const Issue Rev "1" dated 21
plans July 2017 Sheet A-2.0 and A-2.1 for corrections
to partial plan keys.
13. Provide design and Detailing of Per discussion with the building official and as
Toyota Portal noted on See Plancheck/Const Issue Rev "1"
dated 21 July 2017 Sheet A-0.0, this item is a
deferred submittal.
14. Improper references given on partial See Plancheck/Const Issue Rev "1" dated 21
plans July 2017 Sheet A-2.0 and A-2.1 for corrections
to partial plan keys.
15.a- Section 1004.1.2 Area and occupancy See Plancheck/Const Issue Rev "1" dated 21
15.c of conference Training 208 requires July 2017 Sheet A-2.1 the area of room 208 has
change in existing and been revised to 734 sq. ft. No changes to exist
doors and hardware required. However, as
keyed per the hardware and door schedule sheet
A-6.0 doors 208.A and 208.0 are equipped with
panic devices which have been removed
0 Page 3
Plan Check Comments
21 July 2017
16. Elevation references incorrect
17.a- Reference ADA standards on partial
17.c plans and ADA compliant urinal
location
18.a- Private Restrooms per IBC 1109.2
18.d and ANSI A117.1-09, Section 603.2,
604.4, 604.5 and 606.2
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-3.0 for corrections to West
elevation.
Plancheck/Const Issue Rev "1" dated 21 July
2017 See sheet A-2.2 for clear floor space
requirements at each toilet room and ADA
compliant urinal call out. Also see A-7.1 an A
7.2 for ADA urinal call outs. Notes added to
partial plans A-2.2 for grab bar and mounting
height requirements.
Plancheck/Const Issue Rev "1" dated 21 July
2017 See sheet 1/A-2.2 for notes added for
compliance with these code sections.
19. Comply with IBC 1109.5, ANSI Plancheck/Const Issue Rev "1" dated 21 July
A117.1-09 602.4 2017 Drinking fountains have been revised and
added per plumbing requirements revised sheet
A-0.1 See Sheets A-2.0, A-2.1 and A-2.2. Detail
16/A-7.3 has been revised
20.a- Sheet A-5.4 IBC Section1011.7.3 for Plancheck/Const Issue Rev "1" dated 21 July
20.b
walls and soffits for storage under
2017 See Sheet A-0.2 for Wall type 12 per 9/A-
stairs shall be of one (1) hour
0.2. Notes added to stair sections 29/A-5.4,
construction.
3/A-5.5 and 5/A-5.5 referencing the one hour
assembly.
21.a-
Sheet A-5.4 IBC Section 1014.6
Plancheck/Const Issue Rev "1" dated 21 July
21.b
handrail extension requirements.
2017 Stair sections on both A-5.4 and A-5.5
have been revised to incorporate notes on
handrail extensions at the top and bottom of
stairs.
22.a-
IBC Section 1014.6 Handrail
See Plancheck/Const Issue Rev "1" dated 21
22.b
extensions top and bottom Stair
July 2017 Sheet A-5.5 for notes added on
sections on sheet A-5.5
handrail requirements at the top and bottom of
stairs.
23.
IBC Section 1015.5 Update details 9
Per exception IBC 1015.4 exception 4 (no
and 11 Sheet A-5.5
public access) details 9 and 1 l/A-5.5 are used
for stairs meeting the criteria in the exception
and no revision is required.
0 Page 4
Plan Check Comments
21 July 2017
24.a- IBC Section 1011.7.3 soffits and
24.b Walls with enclosed spaces are
required to be protected by 1 hour fire
rated construction.
25. IBC Section 2406 Safety Glazing at
doors types DC, DJ, DK, DM and DE
required
26. IBC Section 1011.73 Rated Door
assemblies required doors 105.A and
164.A
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-1.1 for one (1) hour fire
protection at the underside of stairs and notes
Section 25/A-5.4, 29/A-5.4, 3/A-5.5 and 5/A-
5.5. Stair sections 2/A5.5, 4/A-5.5 and 6/A-5.5
are not required to one hour (1) wall and soffit
assemblies.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-6.0 for added notes on safety
glazing, door type DM does not require safety
glazing as conditions per 2406.4.3 as items 2
and 3 are not met.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-6.0 Door schedule, the
thermal ratings have been added.
27. IBC Section 2406Safety Glazing Safety glazing not required as the plane of the
required at glazed panels adjacent to doors shown is 4'-0" from the glazing in
door on elevation F question and thus is not adjacent to the door.
28. IBC Section 2406Safety Glazing
required at glazed panels adjacent to
door on elevation Q
29. IBC Section 1011.12.2 Roof hatch
required to be 16 sq. ft. and have min
dim 2'-0"
30. WSEC Detail 20/A-6.5 Insulation
required at Detail 20/A-6.5
31. IBC Section 1109.11, ICC A117.1-
09, 904.3 ADA access at casework
rooms 126,103 and 133
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-6.2 glazing revised.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet a-2.4 for note on roof hatch
size. Also see structural drawings sheet S-5.0
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Detail 20/A-6.5 revised missing
insulation and note added.
Plancheck/Const Issue Rev "1" dated 21 July
2017
Dimensions added to elevations, current design
complies with 34" counter height at room 126.
ADA compliant work space is provided
adjacent to rooms 103 and 133 with work
spaces see elevation 2 at service writer 131 for
this item and retail 130 for ADA workspace this
area.
0 Page 5
Plan Check Comments
21 July 2017
32.a- IBC Section 1109.5.1, ICC A117,1-
32.b 09 Detail 16/A-7.3 update to meet
ADA requirements for drinking
fountains
See Plancheck/Const Issue Rev "1" dated 21
July 2017 See detail 16/A-7.3 updated for ADA
requirements on dual drinking fountains and
spout outlet heights.
33. ICC Al 17.1-09, 604.37 Add
See Plancheck/Const Issue Rev "1" dated 21
dimensions Detail 9/A-7.3
July 2017 detail 9/A-7.3 updated for toilet tissue
dispenser locations and requirements.
34. IBC WSA 3005.2 elevator machine
See Plancheck/Const Issue Rev "1" dated 21
room required to be provided with
July 2017 Sheet A-2.1 for notes concerning
independent air conditioning
independent temp control of the elevator
equipment room and further reference to
Mechanical Drawings ( under separate permit)
35. IBC WSA 3009 Provide a means of
See Plancheck/Const Issue Rev "1" dated 21
venting smoke and hot gases from the
elevator to the outside
36. 2015 WSEC Provide U and SHGC
for all glazing in man doors,
Overhead doors and skylights
37. U values for Overhead doors to be
specified in the drawings set
38. WSEC C402.5.1 Indicate on plans the
means of meeting the requirements
for continuous air barrier.
39. WSEC 402.5.1 Indicate on drawings
the completed building to be tested
for air leakage.
July 2017 Sheet A-2.4 for note on venting
requirements. Further reference is given to see
Mechanical Drawings (under separate permit)
for additional information. We have provided
this even though WSA 3009 states that this
requirement applies to buildings 4 or more
stories in height. We are assuming this is a local
decision in Edmonds.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-6.0 glazing notes on all
Solarban exterior glazing units U and SHGC
referenced as are man doors and overhead
doors. See Sheet A-2.4 for skylight U and
SHGC values.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-6.0 for U values at exterior
overhead doors.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-0.3 (added) for required
information and calculation of allowable air
infiltration. See also section C202 definitions
for the criteria for air barrier area calculation.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-0.3 for the requirements for
air barrier testing.
0 Page 6
Plan Check Comments
21 July 2017
Engineering Comments
1. Remove notes concerning power pole
removal
2. Add Note to sheet A-1.0 stating "
Refer to Civil Construction Plans for
Engineering Requirements"
3. Sheet A-2.4 call out slope of drive
from grade to parking deck.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-1.0 for this revision (deleted)
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-1.0 for this added note.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheets A-1.0, A-2.1 and A-2.4 for the
slope call out.
Planning Comments
1. Landscape cost Estimate provide Provided as part of this resubmittal
itemized cost estimate covering
landscape and irrigation to determine
the amount of the maintenance bond.
2. Height; correct the existing four
corners elevations and revise the
elevation calculations on Sheet A-1.0
3. Site Plans — civil and architectural
incorporate comments on lot lie
adjustment noting auditors file
number. Update showing new parcel
numbers and property lines.
Public Works Comments
Provide details on trash enclosure
meeting requirements of the City of
Edmonds
Fire Department Comments
1. Provide fire Marshal Notes Per plan
check
Plancheck/Const Issue Rev "1" dated 21 July
2017 See Sheet A-1.0 for correction to the
heights calculations
Plancheck/Const Issue Rev "1" dated 21 July
2017As of the date of this submittal, the
Snohomish county Accessor has not updated
and assigned new parcel numbers to the site.
Note added all sheets indicating accessors file
numbers and that new parcel numbers to be
issued. Our understanding is this process could
because of backlog take up to a year to occur.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-1.1 for trash enclosure and
related notes.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-0.0 for these comments
added to the cover sheet.
2. Call out that for separate permits for See Plancheck/Const Issue Rev "1" dated 21
the follows; automatic fire sprinkler July 2017 Sheet A-0.0 for list of deferred
system, fire alarm system and submittal both those requiring and those not
Emergency Radio System ( if requiring separate permits.
required after evaluation)
0 Page 7
Plan Check Comments
21 July 2017
3
C!
Provide Identification on the north
See Plancheck/Const Issue Rev "1" dated 21
and East Side of the structure 12" tall July 2017 Sheet A-3.0 for suggested location of
minimum 1" Stroke in contrasting building identification numbers with reference
colors to the building, Location to be to verify with the fire Marshal
determined by the fire Marshal's
Office.
Service Area Must Comply with An analysis of IFC Section 2311 has been done
requirements of IFC 2311 Repair and the project complies with all sections.
garages
5. Provide a code summary page
providing the following for each
room or floor occupancy class,
Occupant Load per room or area exit
travel distance and common path of
egress travel.
6. Provide a dry standpipe on the
parking deck.
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-0.1 for exiting, Occupant
loads common path of travel and maximum
travel distances
See Plancheck/Const Issue Rev "1" dated 21
July 2017 Sheet A-2.1 and civil engineering
drawings for FDC and dry standpipe location
per discussion on site 25 July 2017.
Call if you have questions, either (206-979-8320) or (425)-316-8979
Thanks
David Estes
Strotkamp Architects
0 Page 8