MagicToyotaMech.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: December 12, 2007
TO: Heath Hutchens
Universal Mechanical
FAX: 425-881-6487
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check # 2007-1174
Project: Magic Toyota Garage Exhaust
Project Address: 21310 Highway 99
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator.
1.Garage exhaust fans must total at least 52, 440 cfm per VIAQ304.1 (34,960 x 1.5 cfm/sf =
52,440). Please revise plans and resubmit.