Loading...
MartinDeck.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 5, 2008 TO: James Martin e-mail: seattlejim@mindspring.com FROM: Ann Bullis, Assistant Building Official RE: Plan Check: 2008-0446 Project: New Deck Project Address: 724 Alder Street During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. 1.On the site plan, show the outline of the existing deck to be removed (with dashed line). 2.Revised deck ledger detail as follows: The deck 2x ledger must be attached directly to the 2x rim joist. Revise lag bolt size and spacing to 3/8” x 4 ½” lag screw at 3” o.c. staggered, or have a State licensed Professional Engineer justify the lag screw size and spacing you have proposed (with stamped/signed calcs). Show required flashing (for example: up under siding and downward over ledger with drip edge at bottom so water does not run back toward exterior wall). 3.The bolting of the ledger to the masonry chimney is considered non-conventional construction and requires design by a State licensed Professional Engineer (stamped and signed). Or, revise to meet conventional construction by providing posts and beam in this area with no connection to the masonry. 4.For the prefabricated guardrail, have the manufacturer’s installation instruction and load information on site for the building inspector for code verification, or submit now and it will be reviewed with this deck application.