Material Data.pdfES-A-2000B-FP
Series 2000B-FP
Double Check Valve Assemblies
Sizes: 3/4" — 2" (20 — 50mm)
Features
• Ease of maintenance with only one
cover
• Top entry
• Replaceable seats and seat discs
• Modular construction
• Compact design
• 3/4" — 2" (20 — 50mm) Cast bronze
body construction
• Low pressure drop
• No special tools required
• Gear operated, slow close shutoffs
• Pre -wired tamper switch (2)
Available Models
Suffix:
FP - UL approved gear operated slow
close ball valves
Pressure — Temperature
Temperature Range: 33°F — 140°F
(0.5°C — 60°C)
Maximum Working Pressure: 175psi
(12.1 bar)
Standards
AWWA Std. C510, IAPMO PS31
Job Name
Job Location
Engineer
Approval
A
A M E S
FIRE & WATERWORKS
2" 2000B-FP
r (50mm)
1" 2000B-FP
(25mm)
Series 2000B-FP Double Check Valve Assemblies shall be installed at referenced cross -
connections to prevent the backflow of polluted water into the potable water supply. Only
those cross -connections identified by local inspection authorities as non -health hazard
shall be allowed the use of an approved double check valve assembly.
Check with local authority having jurisdiction regarding vertical orientation, frequency of
testing or other installation requirements.
These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are
approved by the Foundation for Cross -Connection Control and Hydraulic Research at the
University of Southern California.
Specifications
A Double Check Valve Assembly shall be installed at each noted location. The assembly
shall consist of two positive seating check modules with captured springs and rubber seat
discs. The check module seats and seat discs shall be replaceable. Service of all internal
components shall be through a single access cover secured with stainless steel bolts. The
assembly shall also include two resilient seated gear operated slow close isolation valves
and four resilient seated test cocks. The assembly shall meet the requirements of ASSE
Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross -Connection
Control and Hydraulic Research at the University of Southern California. Assembly shall
be an Ames Company Series 2000B-FP.
Approvals
ASSIN
H55E ��® N
C V� US
c us
1015 B64.5 3/4" - 2"
Approved by the Foundation for Cross -Connection Control and Hydraulic Research at
the University of Southern California.
Horizontal approval on all sizes.
Contractor
Approval
Contractor's P.O. No.
Representative
Ames product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Ames Technical Service. Ames reserves the right
to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or
subsequently sold.
www.amesfirewater.com
Dimensions — Weights
• •
`
lies'°�
lilI
�i��
uJ
uJ
MODEL
SIZE
DIMENSIONS
WEIGHT
in.
mm
A
in.
mm
B
in.
mm
C
in.
mm
D
in.
mm
E
in.
mm
F
in.
mm
G
in.
mm
H
in.
mm
I
in.
mm
71b
kgs.
2000B-FP
3/4
20
107/8
276
41/4
108
33/8
86
7/8
22
63/16
157
51/2
140
27/8
73
21/8
67
121/4
311
8.7
3.9
2000E-FP
1
25
131/4
337
41/2
114
31/2
89
1
25
71/2
191
53/4
146
27/8
73
27/8
73
143/8
365
12.2
5.5
2000E-FP
11/4
32
15%
397
53/8
136
33/4
95
1%
41
91/2
241
61/16
154
27/8
73
33/16
81
161/2
419
17.3
7.8
2000B-FP
11/2
40
1 163A
416
1 55A
143
1 4
102
1 16/8
41
1 93/4
248
1 61/4
159
1 27A
73
1 33A
86
1 17
432
19
8.6
200OB-FPI
2
50
1 191A
486
1 61/2
165
1 41/4
108
1 21/4
54
1 131A
340
1 61/2
165
1 27/e
73
1 3%
92
1 191/2
495
26.4
12
Strainer sold separately
Capacities
As compiled from documented Foundation for Cross -Connection Control
and Hydraulic Research at the University of Southern California lab tests.
'Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.)
1
�IIIIIIIIIIIIIIIIIII■■ IIIIIIII■IIIIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIIIIIII��
IIIIIIIIIIIIIIIII■■ IIIIII■�IIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIII■��IIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIII■
�_IIIIIIIIIIIIIIIII■■IIIIII■IIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIIII■��IIIIIIIIIIIIIIIII■IIIIIIIIIIIIIIII■
kPa psi
96 14
N 83 12
J 69 10
y 55 8
41 6
N 28 4
i 14 2
a.
0 0
a
1 " (25mm)
is
y i
*
J 83 12
m 69 10
j 55 8
y 41 6
28 4
a 14 2
0 5 10 15 20 25 30 35 40 45 50 55 60 gpn
AP 0
19 38 57 76 95 114 133 152 171 190 209 228 Ipm
5 7.5 10 15
fps
1.5 2.3 3.0 4.6
mp:
Flow Rate
IMPORTANT. Inquire with governing authorities for
local installation requirements.
A
A M E S
FIRE&WATERWORKS
A Watts Water Technologies Company
N
N
O
J
a1
N
N
N
a
N
N
O
J
d
U)
N
N
a1
a
11/411132mm)
AP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm
0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm
5 7.5 10 15 fps
1.5 2.3 3.0 4.6 mps
Flow Rate
kPa psi 1112" (40mm)
83 12
69 10
55 8
41 6
28 4
14 2
0 0
Apo 10 20 30 40 50 60 70 80 90 100 110 120 gpm
0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm
5 7.5 10 15 fps
1.5 2.3 3.0 4.6 mps
Flow Rate
kPa psi
83 12
2° (50mm)
69 10
55 8
41 6
28 4
14 2
0 0
0 25 50 75 100 125 150 175 200 gpm
AP 0 95 190 285 380 475 570 665 760 Ipm
5 7.5 10 15 fps
1.5 2.3 3.0 4.6 mps
Flow Rate
www.amesfirewater.com 0
USA: Backflow- Tel. (916) 928-0123 • Fax (916) 928-9333
Control Valves- Tel. (713) 943-0688 • Fax (713) 944-9445
Canada: Tel. (905) 332-4090 • Fax (905) 332-7068
ES-A-2000B-FP 1225 0 2012 Ames Fire & Waterworks
Rellmabi�
Reliable Riser - Residential
1" (25mm), 1/" (40mm), and 2" (50mm) sizes.
For use in NFPA 13D and 13R
Residential Systems
Features:
1. Stainless Steel body construction.
2. All brass trim.
3. Factory assembled.
4. Factory pressure tested at 200 psi. (13.8 bar).
5. Choice of trim:
• Basic Trim (Fig. 1).
• Basic Trim with Pressure Relief Kit (Fig. 2).
• Basic Trim with Test and Drain Valve (Fig. 3).
• Basic Trim with Test and Drain Valve and
Pressure Relief Kit (Fig. 4).
6. Choice of mounting options:
• Supply / System lines support.
• Support Bracket (to stud) (Figs. 5 & 6).
• Recessed or Flush mount (to wood panel)
(Fig. 7).
7. NPT (female x female) or tapered metric
(female x female) connections.
8. Slim design allows for easy installation within
2" x 4" on 16" centers wood frame construction.
9. Dedicated UL Listed and ULC Listed Water
Flow Detector assures optimum sensitivity.
Water Flow Detector is factory installed
with a metallic, weatherproof cover.
Triggeringflow rate is 4(15) GPM(LPM) to
10(38)GPM(LPM).
Approvals & Listings
1. Listed by Underwriters Laboratories
Inc. and ULC Listed.
2. NYC MEA 258-93-E
Bulletin 425 Rev. B
Reliable
Riser —
Residential
Fig. 1 Base Trim
Fig. 2 Base Trim with Pressure Relief
Kit
Fig. 3 Base Trim with Test and Drain Valve
Fig. 4 Base Trim with Test and Drain
Valve & Pressure Relief Kit
W
c
N
CP
M
9-4
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Optional Trims - Technical Data:
Description
Basic Trim
Basic Trim with Pressure
Basic Trim with Test and
Basic Trim with Test and Drain
Relief Kit
Drain Valve
Valve & Pressure Relief Kit
Take Out
Dimensions
Weight*
Dimensions
Wei ht"
Dimensions
Weight*
Dimensions
Weight*
Dimension
Manifold
Size:
A
B
Lbs
A
B
Lbs
A
B
Lbs
A
B
Lbs
C
inch
inch
inch
inch
inch
inch
(kgs)
inch
inch
(kgs)
inch
mm(mm)(kgs)
mm(mm)(kgs)
mm
mm
mm
mm
mm
1"
11
8%
7.3
13J,
11
8.7
11
14J,
9.0
15
14J,
10.6
8 J;
25mm
279
222
3.32
343
279
3.95
279
362
4.09
381
362
4.82
210
1y"
11
9X
8.3
13y
11y
10.5
11
14%
9.7
15
14%
11.2
8 Y,
40mm
(279)
(235)
(3.77)
(343)
(292)
(4.77)
(279)
(375)
(4.41)
(381)
(375)
(5.09)
(210)
2"
11
9%
8.8
13'/
12
11.1
11
15y
10.5
15
15J;
12.2
8
50mm
279
248
4.00
343
305
5.05
279
387
4.77
381
387
5.55
210
* Support Bracket Kit (optional) - 1 lb (0.45 kg)
All Reliable Risers have a 1" NPT drain port.
Basic Trim With Pressure Relief Kit
Basic Trim with Test and Drain Pressure Relief Kit
Water
Water
B
Press. Relief
Pressure
Gauge Press. Relief
PressuGauge
Kit(Opt.)
Kit (Opt.)
Manifold System
Manifold S stem
Support
Bod Support
y LJ Bracket
Body
LJ
Bracket
C
Take -Out)
A
A
(Take -Out)
4
Supply
Supply Drain
Drain
Test and Drain
Drain Valve
Valve
Water Flow Detector
Water Flow Detector
Contact Ratings: 10A @ 125250 VAC 2.5A @ 24VDC)
(
(Contact Ratings: 10AQ 125250 VAC 2.5A@ 24VDC)
Product Description:
The Reliable -Risers come factory assembled with
all of the necessary accessories for a cost effective,
yet complete riser solution.
Reliable -Rises are [UL Listed][ULC Listed] [NYC
Approved MEA 258-93-E] for horizontal or vertical
installations as a one-piece, factory assembled
unit for use in NFPA 13D and 13R residential sys-
tems. The riser manifold assembly shall consist of
a (choose one):
• 1" (25 mm) cast, non -welded stainless steel
body with 1" female NPT or IS07-Rc1-11
threaded end connections.
Fig. 5
• 1-Y" (40 mm) cast, non -welded stainless
steel body with 1-/" female NPT or
IS07-Rc1.5-11 threaded end connections.
• 2" (50 mm) cast, non -welded, stainless
steel body with 2" female NPT or
IS07-Rc2-11 threaded end connections.
All of these manifold sizes have cast -on lettering
that clearly identifies the manifold's pipe size, flow
direction, UL Listing/ ULC Listing, and the test and
drain outlet. A built-in drain port is included to per-
mit hydrostatic testing without draining the system.
The assembly has a working pressure rating of 175
2.
psi (12.1 bar). Cast -in mounting holes are provided
for recessed or flush mounting to a wall. For stud
mounting, a support bracket is available that is spe-
cifically designed for the cast mounting holes.
All of the trim variations include brass compo-
nents, a cULus Listed 300 psi water pressure
gauge, and a 250 psi UL Listed/ ULC Listed
Waterflow Detector. This Waterflow Detector comes
factory installed with a weatherproof (outside)
cover.
Trim Descriptions
• Basic Trim
Residential riser manifold assembly trim shall
include a cULus Listed pressure gauge, a
drain valve, and dedicated waterflow
detector containing two sets of SPDT (Form
C) contacts, having an electrical rating of
10A @ 125/250 VAC/2.5 A @ 24 VDC.
Triggering flow rate is 4(15) GPM(LPM) to
10(38) GPM(LPM).
• Basic Trim with Pressure Relief Kit
Residential riser manifold assembly trim shall
include a cULus Listed pressure gauge, a
drain valve, and dedicated waterflow
detector containing two sets of SPDT (Form
C) contacts, having an electrical rating of
10A @ 125/250 VAC/2.5 A @ 24 VDC.
Triggering flow rate is 4(15) GPM(LPM) to
10(38) GPM(LPM). Pressure relief valve kit
shall be provided to maintain system
pressures below 175 psi (12.1 bar).
• Basic Trim with Test and Drain Valve
Residential riser manifold assembly trim shall
include a cULus Listed pressure gauge, a
Test and Drain valve, and a dedicated
waterflow detector containing two sets of
SPDT (Form C) contacts, having an electrical
rating of 10A @ 125/250 VAC/2.5 A @ 24 VDC.
Triggering flow rate is 4(15) GPM(LPM) to
10(38) GPM(LPM). The test orifice size for
the Test and Drain assembly shall be**
**(Choose one)
• 3/8" (10 mm)
• 7/16" (11 mm)
• 1/2" (15 mm)
Basic Trim with Test and Drain Valve &
Pressure Relief Kit
Residential riser manifold assembly trim shall
include a cULus Listed pressure gauge, a
Test and Drain valve, and a dedicated
waterflow detector containing two sets of
SPDT (Form C) contacts, having an electrical
rating of 10A @ 125/250 VAC/2.5 A @ 24 VDC.
Triggering flow rate is 4(15) GPM(LPM) to
10(38) GPM(LPM). Pressure Relief Kit shall
be provided to maintain system pressures
below 175 psi (12,1 bar).
Installation:
1. Install the manifold with the flow arrow pointing
towards SYSTEM side using threaded connec-
tions.
2. Connect a 1" NPT drain line. Ensure the drain
Ball Valve is in the CLOSED position.
3. Place the sprinkler system in service.
Caution:
Automatic sprinkler systems having non -fire
protection connection (permitting continual water
flow) require dielectric fittings, according to NFPA 13
sect. 4-6, when dissimilar metal piping materials are
joined.
Note:
2 112" MINIMUM CAP FOR WATER FLOW INDICATOR
COVER REMOVAL(TYPICAL ALL MANIFOLDS)
STUD SUPPORT BRACKET MOUNT
BRACKET FLUSH
WITH FACE OF
STUD
Fig.6
WOOD PANEL PLASTIC SPACERS
STUD T__-7 ---
—C
RECESSED OR FLUSH MOUNTED
3.
Fig.7
Ordering Information:
Residential Riser Part Number Code Key
IN
1M
1.5N
1.5M
2N
2M
1 N =1" (25mm) NPT Threaded Ends Assembly
1 M =1" (25mm) Metric Threaded Ends Assembly
1.5N = 1-1/2' (40mm) NPT Threaded Ends Assembly
1.5M = 1-1/2' (40mm) Metric Threaded Ends Assembly
2N = 2" (50mm) NPT Threaded Ends Assembly
2M = 2" (50mm) Metric Threaded Ends Assembly
B
T38
T716
T12
B = Basic Trim Assembly
T12 = Basic Trim Assembly with 1/2' (15mm)
Orif. Test and Drain Valve
0
1
2
3
0 = Assembly without Pressure Relief Kit
Water Detector - UL & FM Approved
1 = Assembly with Pressure Relief Kit
Water Detector - UL & FM Approved
2 = Assembly without Pressure Relief Kit
Water Flow Detector - ULC Approved
3 = Assembly with Pressure Relief Kit
Water Flow Detector - ULC Approved
Example #1: 1.5N — B —1
(1-112" (40mm) Residential Riser Assembly with NPT Female Inlet and Outlet Threads, Basic Trim with installed
Pressure Relief Kit).
Example #2: 2M — T12 — 0
(2" (50mm) Residential Riser Assembly with Metric Female Inlet and Outlet Threads, Basic Trim with Test and
Drain Valve having a 112" Diameter Test Orifice.)
Also, If Required:
Description
Part Number
Pressure Relief Kit For Basic Trim
98020076
Pressure Relief Kit For Basic Trim with Test and Drain Valve
6501203551
Support Bracket Kit
6899190001
Waterflow Detector RFDTH
96556910
Waterflow Detector ULC RFDTHA
96556914
Paddle Tree - Waterflow Detector
96556911
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified
and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
_ The Reliable Automatic Sprinkler Co., Inc. ® Recycled
® (800) 431-1588 Sales Offices Paper
Rellabili
() 8-051 Sales Fax
(914914) 82929-2042 Corporate Offices Revision lines indicate updated or new data
www.reliablesprinkler.com Internet Address E.G. Printed in USA 08/09 P/N9999970348
Bulletin 006 Rev. K February 2017
Reliable
Model RFC Series Residential Sprinklers
Flat Cover Plate, Concealed Pendent Sprinkler cULus Listed
Product Features
cULus Listed as Residential Sprinklers
Push -On cover plate installation
Low water flow requirements
Product Description
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R, or NFPA 13D. The
sprinklers are cULus Listed as Residential Sprinklers in ac-
cordance with UL 1626.
Model RFC30, RFC43, and RFC49 sprinklers have a 165°F
(74°C) temperature rated fusible -link operating element.
Model RFC58 sprinklers are offered with either a 165°F
(74°C) or 212°F (100°C) temperature rated fusible -link op-
erating element. Sprinklers with a 165°F (74°C) temperature
rating are ordinary temperature classification and should
be used with a 135°F (57°C) temperature rated cover plate.
Sprinklers with a 212°F (100°C) temperature rating are inter-
mediate temperature classification and should be used with
a 165°F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC
cover plate. Model RFC cover plates may be installed by
either pushing or threading the cover plate into the sprinkler
cup. Model RFC30, RFC43, and RFC49 sprinklers allow 1/2"
(13 mm) of cover plate adjustment. Model RFC58 sprinklers
allow 3/4" (19 mm) of cover plate adjustment.
Model RFC cover plates are available in a variety of finishes
as listed in Table H. In addition, Model RFC cover plates
may be ordered as either traditional solid cover plates or
perforated cover plates.
ModeIRFC30 ModeIRFC43
Model RFC49
ModeIRFC58
Solid Perforated
Model RFC Cover Plate
Sprinkler Model
Nominal K-Factor
Max. Coverage Area
Sprinkler
Identification
gpm/psi12(1/min/bar12)
ft x ft (m x m)
Number (SIN)
RFC30
3.0 (43.2)
14 x 14 (4.3 x 4.3)
RA0611
RFC43
4.3(62)
20 x 20 (6.1 x 6.1)
RA0612
RFC49
4.9 (70.6)
20 x 20 (6.1 x 6.1)
RA0616
RFC58
5.8(84)
20 x 20 (6.1 x 6.1)
RA0613
www.reliablesprinkler.com
Technical Specifications
Cover Plate Finishes
Style: Flat Concealed Pendent
(See Table H)
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 3.0 (43.2 metric)
Sensitivity
Max. Working Pressure: 175 psi (12 bar)
Fast -response
Min. Spacing: 8 ft. (2.4 m)
Temperature Rating
Material Specifications
165°F (74°C) sprinkler
Thermal Sensor: Nickel Alloy Solder Link
135°F (57°C) cover plate
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Cover Plate
Yoke: Brass Alloy
Model RFC cover plate
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Sprinkler Wrench
Towers: Copper Alloy
Model FC
Pins: Stainless Steel
Deflector: Bronze Alloy
Listings and Approvals
Cup: Steel
cULus Listed
Model RFC30 Sprinkler Components and Dimensions
Threads —
Body
Cup
Tower
Fusible Link —
Deflector (retracted)
Pin (extended) -
Deflector (extended)
1-3/4" (44 mm) +/- 1/4" (6 mm)
Nominal face of fitting to ceiling
Model RFC Cover Plate
Model RFC30 Sprinkler Hydraulic Design Criteria
2-5/16" (58 mm)
Dia.
3/16" (5 mm)
Ceiling
Minimum Flow and Residual Pressure
Max. Coverage Area
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
12 x 12
9
9.0
(3.6 x 3.6)
(34)
(0.62)
14 x 14
10
-7
11.0
(4.3 x 4.3)
(38)
(0.76)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Rev. K ��';��'� Page 2 of 7
February 2017 www.reliablesprinkler.com
Technical Specifications
Cover Plate Finishes
Style: Flat Concealed Pendent
(See Table H)
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 4.3 (62 metric)
Sensitivity
Max. Working Pressure: 175 psi (12 bar)
Fast -response
Min. Spacing: 8 ft. (2.4 m)
Temperature Rating
Material Specifications
165°F (74°C) sprinkler
Thermal Sensor: Nickel Alloy Solder Link
135°F (57°C) cover plate
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Cover Plate
Yoke: Brass Alloy
Model RFC cover plate
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Sprinkler Wrench
Towers: Copper Alloy
Model FC
Pins: Stainless Steel
Deflector: Bronze Alloy
Listings and Approvals
Cup: Steel
cULus Listed
Model RFC43 Sprinkler Components and Dimensions
Thre
Body
Cup
Towe
Fusible Li
Deflector (retry
Pin (extei
Deflector (extend
1-3/4" (44 mm) +/- 1/4" (6 mm)
Nominal face of fitting to ceiling
Model RFC Cover Plate
Model RFC43 Sprinkler Hvdraulic Desiqn Criteria
2-5/16" (58 mm)
Dia.
3-5/16" (84 mm) Dia.
3/16" (5 mm)
Ceiling
Minimum Flow and Residual Pressure
Max. Coverage Area
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
12 x 12
12
7.8
(3.6 x 3.6)
(45)
(0.54)
14 x 14
13
9.1
(4.3 x 4.3)
(49)
(0.63)
16 x 16
13
9.1
(4.9 x 4.9)
(49)
(0.63)
18 x 18
18
17.5
(5.5 x 5.5)
(68)
(1.21)
20 x 20
21
23.8
(6.1 x 6.1)
(79)
(1.64)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Rev. K ��';��'� Page 3 of 7
February 2017 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 4.9 (70.6 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed
Model RFC49 Sprinkler Components and Dimensions
2-5/16" (58 mm) y
Threads Dia.
Body
Cup
Tower 1-3/4" (44 mm) +/- 1/4" (6 mm)
Fusible Link Nominal face of fitting to ceiling
Deflector (retracted)
Pin (extended)
Deflector (extended)
Model RFC Cover Plate 3-5/16" (84 mm) Dia.
Model RFC49 Sprinkler Hvdraulic Desian Criteria
ao+Y�r«
3/16" (5 mm)
Ceiling
Minimum Flow and Residual Pressure
Max. Coverage Area
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
16 x 16
13
7.0
(4.9 x 4.9)
(49.0)
(0.48)
18 x 18
17
12.0
(5.5 x 5.5)
(64.3)
(0.83)
20 x 20
20
16.7
(6.1 x 6.1)
(75.7)
(1.15)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Rev. K ��';��'� Page 4 of 7
February 2017 www.reliablesprinkler.com
Technical Specifications
Sensitivity
Style: Flat Concealed Pendent
Fast -response
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 5.8 (84 metric)
Temperature Ratings
Max. Working Pressure: 175 psi (12 bar)
Ordinary:
Min. Spacing: 8 ft. (2.4 m)
165°F (74°C) sprinkler
135°F (57°C) cover plate
Material Specifications
Intermediate:
Thermal Sensor: Nickel Alloy Solder Link
212°F (100°C) sprinkler
Sprinkler Body: Brass Alloy
165°F (74°C) cover plate
Levers: Bronze Alloy
Yoke: Brass Alloy
Cover Plate
Sealing Assembly: Nickel Alloy with PTFE
Model RFC Cover Plate
Load Screw: Bronze Alloy
Towers: Copper Alloy
Sprinkler Wrench
Pins: Stainless Steel
Model FC
Deflector: Chrome Plated Bronze Alloy
Cup: Steel
Listings and Approvals
cULus Listed
Cover Plate Finishes
(See Table H)
Model RFC58 Sprinkler Components and Dimensions
Threads
Body
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended) —
1-7/8" (48 mm) +/- 3/8" (9 mm)
Nominal face of fitting to ceiling
Bottom View
2-5/16" (58 mm)
Dia.
Model RFC Cover Plate ---' f 3-5/16" (84 mm) Dia
Model RFC58 Sprinkler Hydraulic Design Criteria
3/16" (5 mm)
Ceiling
Minimum Flow and Residual Pressure
Max. Coverage Area()
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
16 x 16
16
7.6
(4.9 x 4.9)
(60.6)
(0.53)
18 x 18
18
9.6
(5.5 x 5.5)
(68.1)
(0.66)
20 x 20
20
11.9
(6.1 x 6.1)
(75.7)
(0.82)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Rev. K ��';��'� Page 5 of 7
February 2017 www.reliablesprinkler.com
Cover Plate FinishesM
Standard Finishes
Special Application Finishes
White Polyester
Off White Paint
Black Paint
Raw Brass
Chrome Plated
Bright Brass
Finished Bronze
Black Plated
Satin Chrome
Stainless Steel
Clad(3)
Custom Color
Paint(2)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. Custom color paint is semi -gloss, unless specified otherwise.
3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the backside. Cover plates
are not listed or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated.
Installation Dimensions
Recommended
Min. to
Min. to Max.
Cover
Cover Plate
Hole Diameter
Cover Plate
Max. Face
Dropped Deflector
Cover Plate
Sprinkler
Plate
Diameter
in Ceiling
Adjustment
of Fitting to
Distance below
Temperature
Model
inch
inch
Ceiling')
Ceiling
Model
(mm)
inch
(mm)
inch
inch
Rating
(mm)
(mm)
(mm)
RFC30
RFC43
RFC
3-5/16
2-5/8
1/2
1-1/2 to 2
1/2 to 1
135°F
RFC49
(84)
(67)
(13)
(38 to 51)
(13 to 25)
(57°C)
1350F(2)
RFC58
RFC
3-5/16
2-5/8
3/4
1-1/2 to 2-1/4
1/4 to 1
(57°C)
(84)
(67)
(19)
(38 to 57)
(6 to 25)
or 1650F(3)
(74°C)
Notes:
1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method prior
to installation. A 1/2" x 1/2" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing sprinklers.
2. For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (38°C).
3. For use with 212°F (100°C) temperature rated sprinklers with the Maximum Ceiling Temperature does not exceed 150°F (66°C).
Installation
Model RFC series sprinklers are intended to be installed in ac-
cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the
requirements of applicable authorities having jurisdiction. Mod-
el RFC series sprinklers must not be installed in ceilings with
positive pressure in the space above. Ensure that the 4 slots in
the cup are open and unobstructed following installation. Model
RFC series sprinklers are shipped with a protective cap that
should remain on the sprinkler until installed. The protective cap
should be replaced following installation of the sprinkler and
permanently removed only when the cover plate is installed and
the sprinkler system is placed in service following construction.
Model RFC series sprinklers are installed with the Model FC
wrench. The use of any other wrench to installed Model RFC se-
ries sprinklers is not permitted and may damage the sprinkler.
Temporarily remove the protective cap during installation of the
sprinkler. Insert the Model FC wrench over the sprinkler until the
wrench engages the body. Do not wrench any other part of the
sprinkler/cup assembly. The Model FC wrench is designed to
be turned with a standard 1/2" square drive. Tighten the sprin-
kler into the fitting after applying a PTFE based thread sealant
to the sprinkler's threads. Recommended installation torque is 8
to 18 ft/lb (11 to 24 N/m).
Do not exceed the maximum recommended torque. Exceeding
the maximum recommended torque may cause leakage or im-
pairment of the sprinkler. Use care when inserting or removing
the wrench from the sprinkler to avoid damage to the sprinkler.
Install the cover plate by hand by pushing the cover plate into
the cup and turning the cover in the clockwise direction until it
is tight against the ceiling.
Application
Model RFC series sprinklers are intended for installation where
residential sprinklers are permitted or required by NFPA 13,
NFPA 13R, and NFPA 13D. The sprinklers are concealed pen-
dent residential sprinklers.
Model RFC 30, RFC43, and RFC49 sprinklers are available in
ordinary temperature classification for installation where the
Maximum Ceiling Temperature does not exceed 100OF (380C).
Model RFC58 sprinklers are available in either ordinary or in-
termediate temperature classification for installation where the
Maximum Ceiling Temperature does not exceed 100OF (38°C)
or 150OF (660C), respectively.
Bulletin 006 Rev. K
February 2017
Page 6 of 7
www.reliablesprinkler.com
Model FC
Maintenance
Model RFC series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming. Replace
any sprinkler cover plate assembly which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or non -oper-
ation.
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada (cULus)
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Patents
Model RFC30, RFC43, RFC49, and RFC58 sprinklers are
covered by U.S. Patent No. 9,248,327 and U.S. Patent No.
7,275,603.
Model RFC30 and RFC43 sprinklers are additionally covered
by U.S. Patent No. 8,776,903.
Ordering Information
Specify the following when ordering.
Sprinkler
• Model (RFC30, RFC43, RFC49, RFC58)
• Temperature Rating
Cover Plate
• Model RFC
• Temperature Rating
• Finish (See Table H)
Sprinkler Wrench
• Model FC
v
Bulletin 006 Rev. K ��';��'� Page 7 of 7
February 2017 www.reliablesprinkler.com
Pendent / HB
(See Fig. 2)
Horizontal Sidewall / HB
(See Fig. 7)
Model F3QR Dry Pendent Sprinkler Model F30R Dry Pendent w/HB Escutcheon
"A" Dim. 2" to 48" (51 mm to 1219mm) in %" (6mm) increments "A" Dim. 31/2" to 48" 89mm to 1219mm in 1/4" 6mm increments
Finicha4m(1)
Sprinkler
Escutcheon
Bronze
Brass (3)
Chrome Plated
Chrome Plated
White Polyester (2)
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
(3) Not available for HB escutcheons.
F====- ___ ____-= �F===�
I
r- System Tee
1" NPT
772 /8" Dia.
4.0mm]
"A" Dimension Hole in Ceiling
Adjustment Range
-1/4" [-6.4mm] 1 43/64" Dia.
+1 1/4" [+31.8mm] [42.5mm] 1 1/2" [38.1mm]
Total Adjustment
Sprinkler Can Ceiling 1 1/4" [31.8mm]
1/4" [6.4mm]
Escutcheon Escutcheon
Ceiling Adjustment
Nominal Position 1 5/8
of Escutcheon [41.3mm]
1/4" [6.4mm]
Protrusion 3" Dia.
[76.2mm] NEW157FG01
Fig. 1
Note: The sprinkler can protrudes 1/4" when escutcheon is in nominal
position. Escutcheon adjustment provides -1/4" (-6mm) to +11/4"
(+32mm) "A" dimension adjustment range.
Sprinkler Guard: Model C-2
Sprinkler Installation Wrench: Model F3 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5714
Model F30R Dry Recessed FP Pendent Sprinkler
"A" Dim. 31/2" to 48" 89mm to 1219mm in 1/4" 6mm increments
Finicha¢]'j
Sprinkler
Escutcheon
Bronze
Brass
Chrome Plated
Chrome Plated
White Polyester (2)
White
(1) Other finishes and colors are available on special order.
Consult factory for details. Cup remainds unfinished.
Only the escutcheon will contain desired finish.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Sprinkler
Max.
Classification
Temperature
Ambient
Bulb Color
Rating
Temp.
Ordinary
135-F (57oC)
100-F (38oC)
Orange
Ordinary
155-F (68oC)
100OF (38oC)
Red
Intermediate (1)
175oF (79oC)
150oF (66oC)
Yellow
Intermediate
200OF (93oC)
150OF (66oC)
Green
High c1j
2860F 141-C
225oF 107oC
Blue
Sprinkler cup and FP Escutcheon fabricated of steel and recommended
for interior applications.
MListed and Certified only by cULus.
Standard Temperature Ratings
Sprinkler
Max.
Classification
Temperature
Ambient
Bulb Color
Ratin
Ordinary
135-F (57oC)
100oF (38oC)
Orange
Ordinary
155-F (68oC)
100oF (38oC)
Red
Intermediate (1)
175oF (79oC)
150oF (66oC)
Yellow
Intermediate
200-F (93oC)
150oF (66oC)
Green
High (1)
286oF 141-C
225oF 107oC
Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications.
(1) Listed and Certified only by cli
Lr-JL
System Tee
"A" Dimension 2 1/2" [63.5mm]
1" NPT
Adjustment Range Dia. Hole in Ceiling
-1/2" [-12.7mm]
3 1/2" [88.9mm]
+1/2" [+12.7mm]
Escutheon Dia.
1/2" [12.7
Escutheon Adl Adj.
Ceiling
1" [25 4,
Escutcheon
Total Adj.
TNV1�/2�[12.7mm]
Escutheon Adj.
.min Position
Sprinkler Can
f Escutcheon
1-1/4" [31.75mm]
1 5/8"
Nominal Protrusion
[41.3mm]
2 13/64" [55.88mm]
Dia.
—1—
Fig. 2
Note: The sprinkler can protrudes 11/4" when escutcheon is in nomi-
nal position. Escutcheon adjustment provides -1/2" (-12.7mm) to
+1/2" (+12.7mm) "A" dimension adjustment range.
h�l
- � System Tee
2 1/2" Dia.
[63.50mm]
"A" Dimension Hole in Ceiling
Adjustment Range
31/4" 2 19/64" Dia.
[36.35mm] [58.34mm]
Nominal Position
of Escutcheon
1Ceiling
Escutcheon Adjustment
1/4" [6.35mm] 3 7/32" Dia.
Escutcheon AdjustmentL [81.76mm]
1/2" [12.7mm]
Total Adjustment
1" APT
Sprinkler
Cup Assembly
Escutcheon
Ceiling
NEW157FG03
Fig. 3
Note: Do not install the Model F3QR Dry Recessed FP Pendent Sprin-
kler in ceilings which have positive pressure in space above.
Sprinkler Installation Wrench: Model XL02 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5714
2.
Model F3QR Dry Pendent Concealed Sprinkler
"A" Dim. 31/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments
['_[_P rnuor Plata (1) Pinishac 121
Standard Finishes
Special Application Finishes
Chrome Plated
Bright Brass Plated
White
Black Plated
Black Paint
Off White
Satin Chrome
Utilizes the 1/2" cover plate with 3/8" total adjustment.
2> Other finishes and colors are available on special order.
Consult factory for details.
Standard Temperature Ratings
Sprinkler
Cover Plate
Max.
Classification
Temperature
Temp. Rating
Ambient
Rating
Temp.
Ordinary
135°F (57°C)
135-F (57oC)
100-F (38oC)
Ordinary
155°F (68°C)
135-F (57oC)
100-F (38oC)
Intermediate (1)
175'F (79'C)
165oF (74oC)
150oF (66oC)
Intermediate
200°F (93°C)
165-F (74oC)
150-F (66oC)
High (1)
286°F (141°C)
165-F (74aC)
150-F (66aC)
Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of
brass and recommended for interior applications.
(1) Listed and Certified only by cULus.
Sprinkler Installation Wrench:
Model XL02 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5714
Model F3QR Dry Recessed F1 Pendent Sprinkler
"A" Dim. 31/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments
Finichpc (1)
Sprinkler
Escutcheon
Collar
Chrome Plated
White Polyester (2)
Chrome Plated
White
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Sprinkler
Max.
Classification
Temperature
Ambient Bulb Color
Rating
Temp.
Ordinary
135-F (57oC)
100-F (38oC)
Orange
Ordinary
155-F (68oC)
100-F (38oC)
Red
Intermediate (1)
175oF (79oC)
150'F (66oC)
Yellow
Intermediate
200-F (93oC)
150-F (66oC)
Green
High (1)
286aF (141aC)
225'F (107'C)
Blue
(1) Listed and Certified only by cULus.
Sprinkler Installation Wrench:
Model XL02 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5714
-IiIIH -I I-
L-
— System Tee
1" NPT
2 1/2" Dig.
[6.35mm]
"A" Dimension Hole in Ceiling
Adjustment Range
f 3/16" 2 19/64" Dig.
[t4.76mm] [58.34mm]
Nominal Position
Sprinkler
of Coverplate
Cup Assembly
Coverplate
Ceiling
Assembly
Ceiling
3/16" [4.76mm]
Coverplate Adjustment
3/16" [4.76mm]
3 5/16"
Di,
Coverplate Adjustment
[84.13mm]
3/8" [9.53mm]
Total Adjustment
NEW157FG04
Fig. 4
Note: Do not install the Model F3QR Dry Concealed Pendent Sprinkler
in ceilings which have positive pressure in the space above.
2 1/2" Dig.
[63.50mm]
Hole in Ceiling
"A" Dimension
Adjustment Range
t 1/4"
[t6.35mm]
Nominal Position
of Escutcheon
Ceiling
1/4" [6.35] C
Escutcheon Adjustment
1/4" [6.35]
Escutcheon Adjustment
1/2" [12.7mm]
Adjustment
System Tee
1" NPT
15/16"
[49.2mm]
15/16"
[23.8mm
Sprinkler
Cup Assembly
1 /8"
Ceiling [3.2mm]
Escutcheon
2 27/32" NEW757FG05
[72.2mm]
Fig. 5
3.
Model F3QR Dry Horizontal Sidewall Sprinkle
"A" Dim. 2" to 48" 51 mm to 1219mm in 1/4" 6mm increments
Finishes"'
Sprinkler
Escutcheon
Bronze
Brass (3)
Chrome Plated
Chrome Plated
White Polyester (2)
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cLILus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
(3) Not available for HB escutcheons.
1 1/2" [38.1omm]
Total Adjustment
Ceiling r
= T
4" [101.60mm] Mir
1 1/4" [31.75mm] 12" [304.80mm] M
Escutcheon Adjustment
System Tee Escutcheon Adjustment
" NET
L3. mm]
3"
[76.20mm]
2 1/8" Dia. —
[53.98man] 3
Hole in Wall 1/4" [6.35mm]
Sprinkler Can Protrusion
"A" Dimension
Adjustment Nominal Position
Range — 1/4" [-6.35mm] of Escutcheon
mewr5�rcoe + 1 1/4 [+31.75mm]
Fig. 6
Note: The sprinkler can protrudes 1/4" when escutcheon is in nominal
position. Escutcheon adjustment provides '/4" (-6mm) to +11/4"
(+32mm) "A" dimension adjustment range.
(1) Listed and Certified only by cULus.
Sprinkler Installation Wrench: Model F3 Sprinkler Wrench
prinkler Identification Number (SIN): R5734
Model F3QR Dry HSW w/HB Escutcheon
"A" Dim. 31/2" to 48" 89mm to 1219mm in 1/4" 6mm increments
Standard Temperature Ratings
Sprinkler
Max.
Classification
Temperature
Ambient
Bulb Color
Rating
Temp.
Ordinary
135-F (57oC)
100-F (38oC)
Orange
Ordinary
155-F (68oC)
100oF (38oC)
Red
Intermediate (1)
175oF (79oC)
150oF (66oC)
Yellow
Intermediate
200oF (93oC)
150oF (66oC)
Green
High
286oF 141oC
225oF 107oC
Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications.
1" [25.4mm]
Total Adjustment
Ceiling
1/2" [12.7mm]
Escutcheon Adjustment
4" [101.60mm] Min.
1/2" [12.7mm]
12" [304.80mm] Max.
Escutcheon Adjustment
2 3/32"
tT3
S4ri
[53.18mm]
PT
[SS.SBmm] [88.9mm]
Did. Escutcheon Did.
2 1/2" Did.
[63.5mm]
Hole in Wall
1-1/4" [31.75mm] Nominal
Protrusion
"A" Dimension
Sprinkler Can
Is
Adjustment
Newrn 7 Range + 1/2' [+12.7mm]
- 1/2" [-12.7mm]
Nominal Position
of Escutcheon
Fig. 7
Note: The sprinkler can protrudes 11/4" when escutcheon is in nomi-
nal position. Escutcheon adjustment provides -1/2" (-12.7mm) to
+1/2" (+12.7mm) "A" dimension adjustment range.
Model F3QR Dry Recessed FP Horizontal Sidewall Sprinkler
"A" Dim. 31/z" to 48" (89mm to 1219mm) in 1/4" (6mm) increments
Finishes "'
Sprinkler
Escutcheon
Bronze
Brass
Chrome Plated
Chrome Plated
White Polyester (2)
White
(1) Other finishes and colors are available on special order.
Consult factory for details. Cup remainds unfinished. "See page 2"
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Classification
Sprinkler Tem-
perature Rating
Max.
Ambient Temp.
Bulb Color
Ordinary
135-F (57oC)
100-F (38oC)
Orange
Ordinary
155-F (68oC)
100-F (38oC)
Red
Intermediate (1)
175oF (79oC)
150oF (66oC)
Yellow
Intermediate
200-F (93oC)
150OF (66oC)
Green
High (1)
286oF (141oC)
225oF (107oC)
Blue
(1) Listed and Certified only by cLlLus.
Sprinkler Installation Wrench:
Model XL02 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5734
F Ceiling
1 13/32"
Escutcheon [35.7mm]
4" [101. imm]Min.
Cup 3 12" [304."r,]Max.'*
�1" NPT
--- -- - 37/32" Did.
[[
��m]
2 5r Did.
[63.3.Smm] = Nominal Position
Hole Wall 3 of Escutcheon
2 19/64" Di..
[58.3mm] 1/4"
Escutcheon Adjustment
"A" Dimension
Adjustment Range 1 t0 [ Adjus]
i1/4' Escutcheon Adjustment
[36.35mm] 1/4" [6,351
Escutcheon Adjustment
=k • FOR FACTORY MUTUAL (FM)
• 4" - 6" FOR UNDERWRITERS LABORATORIES (UL)
Fig. 8
Notes: Do not install the Model F3QR Dry Recessed FP Horizontal
Sidewall Sprinkler in walls which have positive pressure in their
side space.
• Listed by cULus for Quick Response. Approved by FM for
Standard Response.
• Recessed Horizontal sidewall sprinklers are listed with cLlLus
for installation of min. 4" (100mm) - to - max. 6" (150mm) below
ceiling and approved by FM for installation of min. 4" (100mm)
- to - max. 12" (300mm) below ceiling.
91
Model F3QR Dry Recessed F1 Horizontal Sidewall Sprinkler
"A" Dim. 31/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments
Finishes (1)
Sprinkler
Escutcheon
Collar
Chrome Plated
White Polyester (2)
Chrome Plated
White
Chrome Plated
White
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cl-Lus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
Standard Temperature Ratings
Sprinkler
Max.
Classification
Temperature
Ambient
Bulb Color
Rating
Temp.
Ordinary
135-F (57oC)
100oF (38oC)
Orange
Ordinary
155-F (68oC)
100oF (38oC)
Red
Intermediate (1>
175oF (79oC)
150oF (66oC)
Yellow
Intermediate
200-F (93oC)
150oF (66oC)
Green
High (1)
286aF (141aC)
I 225oF (107oC)
I Blue
(1) Listed and Certified only by cULus.
Sprinkler Installation Wrench:
Model XL02 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5734
Technical Data:
Orifice Size: 112" (15mm)
Thread Size: 1" NPT per ANSI B2.1
Working Pressure: 175 psi (12 bar)
Nominal K Factor - US / (Metric): 5.6 / (80)
Product Description
Reliable Model F3QR Dry Sprinklers are quick response sprinklers
utilizing a durable 3mm frangible glass bulb. This quick response
enables these sprinklers to apply water to a fire much sooner than
standard response sprinklers of the similar temperature rating.
Model F3QR Dry Sprinklers are intended for use in dry and preac-
tion systems and in areas subjected to freezing temperatures, such
as freezers and unheated portions inside and outside buildings.
Environments wherein dry sprinklers are employed can be cor-
rosive. For this reason, Model F3 Sprinklers have a special wax fillet
placed in the gap between the cup that supports the bulb and the
wrenching boss. This wax will not interfere with the operation of the
sprinkler, and it prevents contaminents from entering the internal
portion of the drop nipple. The wax must not be removed.
Operation
The glass bulb consists of an accurately controlled amount of
special fluid hermetically sealed inside a precisely manufactured
glass capsule. This glass bulb is specially constructed to provide
fast thermal response. When the temperature increases sufficiently,
due to a fire, the bulb shatters allowing operating parts to clear the
waterway. This enables the inlet seal to release air or water and
subsequently, cause water flow over the deflector in a uniform
spray pattern, controlling or extinguishing the fire.
F Ceiling
Escutcheon
�^1 [3.2mm]
4" [101.6mm]1Ain.3
�=
System Tee
Sprinkler Cup
Assembly
1" NPT
12" [304.8mm]Max.
ref
1
2 27/32"
[72.2mm]
<< _
\�
2 1/2" Din.�—�
63.5mm]
Hole in Wall
-a
Nominal Position
1 15/16"
[^- of Escutcheon
[49.2mm]
1/4" [6.35]
Escutcheon Adjustment
"A" Dimension
1/2" [12.7mm]
NEW157FG09
Adjustment Range
Adjustment
31/4"
[t6.35mm]
1/4" [6.35]
Escutcheon Adjustment
# • FOR FACTORY
MUTUAL (FM)
• 4" — 6" FOR
UNDERWRITERS LABORATORIES
(UT)
Fig. 9
Listed by cULus for Quick Response. Approved by
FM for Standard Response.
Recessed Horizontal sidewall sprinklers are listed
with cULus for installation of min. 4" (100mm) - to
- max. 6" (150mm) below ceiling and approved by
FM for installation of min. 4" (100mm) - to - max. 12"
(300mm) below ceiling.
Ordering Information
Specify:
1. Sprinkler Type (select one):
(a) Model F3QR Dry Pendent
(b) Model F3QR Dry Pendent/HB
(c) Model F3QR Dry Recessed FP Pendent
(d) Model F3QR Dry Recessed F1 Pendent
(e) Model F3QR Dry Concealed Pendent
(f) Model F3QR Dry Horizontal Sidewall
(g) Model F3QR Dry Horizontal Sidewall/HB
(h) Model F30R Dry Recessed FP Horizontal Sidewall
(i) Model F30R Dry Recessed F1 Horizontal Sidewall
2. Sprinkler Temperature Rating.
3. Sprinkler Finish.
4. Escutcheon type (F1 or FP).
5. Cover Plate/Escutcheon Finish.
6. Length:
"A" Dimension (face of tee to face of ceiling or wall) in'/4"
(6mm) increments.
7. Model F3QR Dry Pendent (a) is available without
sprinkler can and escutcheon.
Note:
1. The "A" dimension is based on a nominally gauged
pipe thread "make-up" of 0.600" (15mm) per ANSI
132.1 [71/2 threads approximately].
2. All platings and paintings are decorative and intend-
ed for interior use.
5.
General Installation Instructions
Model F3QR dry sprinklers must be installed only in stan-
dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125)
pipe tees in the horizontal position, even at branch line ends.
They should not be installed into elbows or pipe couplings
located on drop nipples to the sprinklers. For these and
other fittings including CPVC", the dry sprinkler should be
installed into a fitting to allow protrusion into the fitting in ac-
cordance with the diagrams. The "A" dimension of the dry
sprinkler, which extends into the freezers or a freezing zone
from wet pipe systems, should be selected to provide, as a
minimum, the specified lengths in inches shown in Fig. 10.
Caution:
Do not install Model F3QR Dry sprinklers into CPVC
adapter fittings or tees that have an internal obstruction.
This will damage the sprinkler and /or the fitting. Refer to
Fig. 11.
During installation, the following steps must be followed
1. Cut the specified size hole (see illustrations) for the sprin-
kler in the ceiling or wall directly in line with the tee.
2. Apply pipe joint compound to the 1" (25mm) pipe
threads and install sprinkler using the Model F3 or
XLO2 Sprinkler Wrench as specified.
3. Install the Model FP push -on / thread -off escutcheon
or CCP cover plate if required.
Note: Installation of the Model F3QR Sprinklers is not rec-
ommended in copper pipe systems, as this may reduce
the life expectancy of the sprinklers.
Model F30R Concealed and Recessed In-
stallation Instructions
• The Model XLO2 wrench (Fig. 12) is designed to lo-
cate on the wrenching pads of the recessed sprin-
kler while centering in the cup. A standard'/2" drive
ratchet may be used to drive this wrench. Fig. 13 and
Fig. 14 show sequentially the insertion of the wrench.
First the wrench, with its jaws above the sprinkler de-
flector, is moved laterally until centered with the cup.
Then raise the wrench inside of the cup until its jaws
engage the sprinkler's square wrenching pads (Fig.
14). To remove the wrench, follow this procedure in
reverse order. Care should be taken to avoid striking
the deflector, with the wrench.
• Model F3 Wrench (Fig. 15) is used for installation of
Pendent and Horizontal Sidewall sprinklers.
• Glass bulb sprinklers have orange bulb protectors
to minimize bulb damage during shipping, handling
and installation. REMOVE THIS PROTECTION AT THE
TIME THE SPRINKLER SYSTEM IS PLACED IN SER-
VICE FOR FIRE PROTECTION. Removal of the pro-
tectors before this time may leave the bulb vulnerable
to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PRO-
TECTORS BY UNDOING THE CLASP BY HAND. DO
NOT USE TOOLS TO REMOVE THE PROTECTORS.
Maintenance
The Model F30R Quick Response Dry Sprinklers should
be inspected quarterly and the sprinkler system maintained
in accordance with NFPA 25. Do not remove the factory
applied thermally sensitive wax fillet between the bulb sup-
porting cup and the wrenching boss. Do not replace this
wax with a substitute substance. An Alternate substance
may interfere with proper operation of the sprinkler. Do not
clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gently
vacuuming. Remove any sprinkler which has been painted
(other than factory applied) or damaged in any way. A stock
of spare sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers should be maintained in the original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper opera-
tion or non -operation.
Caution:
Use specified by RASCO wrenches only, which are
designed to engage sprinkler's wrenching pad. (Fig. 15,
page 9)
RECOMMENDED EXPOSED MINIMUM BARREL LENGTH BASED ON AMBIENT TEMPERATURE IN THE PROTECTED AREA
(STANDARD DRY PENDENT SPRINKLER SHOWN)
AMBIENT
TEMPERATURE
OF PROTECTED
AREA- AT THE
DISCHARGE END
OF THE SPRINKLER
EXPOSED BARREL
AMBIENT TEMPERATURE
40'F/4'C I 50'F/10'C I 60'F/16'C
EXPOSED MINIMUM BARREL LENGTH**
(FACE OF TEE TO TOP OF CEILING)
IN. MM IN. MM IN. MM
40-F (4'C)
0
0
0
30'F (-1'C)
0
0
0
20'F (-TC)
4 (101)
0
0
10'F (-ITC)
8 (203)
1 (25.1)
0
0'F (-16'C)
12 (305)
3 (75)
0
-10'F (-23'C)
14 (356)
4 (101)
1 (25.1)
-20-F (-29'C)
14 (356)
6 (152)
3 (75)
-30-F (-34'C)
16 (406)
8 (203)
4 (101)
-40-F (-4('C)
18 (457)
8 (203)
4 (101)
-50-F (-46'C)
20 (508)
10 (254)
6 (152)
-60-F (-51'C)
20 (508)
10 (254)
6 (152)
INSTALL 1 INCH NPT THREADED
END OF DRY PENDENT SPRINKLER
WET PIPE
INTO THE 1 INCH NPT SIDE OUTLET
OF A MALLEABLE IRON TEE FITTING
____ -- PER ANSI B 16.3 (CLASS 150)
- ___ OR CAST IRON THREADED TEE FITTING
i n u
PER ANSI 16.4 (CLASS 125) ONLY.
LATc___�
Lr-`
1J
IF HUMIDITY AND TEMPERATURE DIFFERENTIAL
fi
CAUSES CONDENSATION ON THE EXPOSED DRY
I
SPRINKLER, CONSIDER WRAPPING THE EXPOSED
BARREL WITH INSULATION, FOAM INSULATING
i
TAPE OR EQUIVALENT.
MINIMUM (HEATED AREA)
EXPOSED
SEAL THE CLEARANCE SPACE
BARREL
AROUND THE SPRINKLER TO AVOID
LEAKAGE OF AIR INTO THE PROTECTED
LENGTH
AREA AND CONSEQUENT FORMATION OF
CONDENSATE AROUND THE FRAME, WHICH
COULD INHIBIT OPERATION OR CAUSE
PREMATURE OPERATION. SEE BELOW FOR
RECOMMENDED METHODS.
'A' CLEARANCE
DIMENSION HOLE
i
• THE PROTECTED AREA REFERS TO THE AREA BELOW THE CEILING,
THE AMBIENT TEMPERATURE IS THE TEMPERATURE AT THE DISCHARGE
END OF THE SPRINKLER.
FOR PROTECTED AREA TEMPERATURES THAT OCCUR BETWEEN THE VALUES
LISTED, USE THE NEXT COOLER TEMPERATURE.
)—
//�l
� THE MIN. REQUIRED BARREL LENGTH IS NOT THE SAME AS THE 'A' DIMENSION. CEILING)
ESCUTCHEON
NOTE: EXPOSED MINIMUM BARREL LENGTHS ARE INCLUSIVE UP TO 30MPH
WIND VELOCITIES IN THE PROTECTED AREA.
(PROTECTED AREA)
r3"
DIA.
*RECOMMENDED EXPOSED MINIMUM BARREL
LENGTHS ALSO APPLY TO
HORIZONTAL SIDEWALL DRY SPRINKLERS*
RECOMMENDED
DRY SPRINKLER SEAL ARRANGEMENTS
WET PIPE (STANDARD
DRY PENDENT SPRINKLER
SHOWN) WET PIPE
MINIMUM
(HEATED AREA) (HEATED AREA)
MINIMUM
EXPOSED
EXPOSED
BARREL
BARREL
LENGTH DECKTITE FLASHING —
INSIDE FACE
SEAL LENGTH
(SEE ABOVE) RASCO /4003910
(SEE ABOVE>
(RECOMMENDED)
1
CLEARANCE HOLE
i
I
INSULATED FREEZER
i OR COOLER STRUCTURE
OR EXTERIOR FRAMING
(PROTECTED AREA) w
DRY SPRINKLER (PROTECTED AREA) DRY SPRINKLER
IN COLD AREA W_ SIN COLD AREA
NEW157FG10
Fig. 10
7.
*CAUTION*
DO NOT INSTALL MODEL F3, MODEL F3QR OR MODEL DH56 HSW DRY SPRINKLERS INTO
CPVC ADAPTER FITTINGS OR TEES THAT HAVE AN INTERNAL OBSTRUCTION. THIS WILL
DAMAGE THE SPRINKLER AND/OR THE FITTING.
CPVC ADAPTER FITTINGS AND TEES WITH INTERNAL OBSTRUCTIONS ARE ALSO COMMONLY
FOUND DURING THE RETROFITTING PROCESS OF RELIABLE'S OLDER MODEL G3 DRY
SPRINKLERS.
INTERNAL NO
OBSTRUCTION INTERNAL
OBSTRUCTION
FEMALE FEMALE
PIPE PIPE .
THREAD THREAD
INCORRECT CORRECT
CPVC ADAPTER CPVC ADAPTER
FITTING OR TEE FITTING OR TEE
1
SHORTER LONGER
INLET INLET
MALE MALE
PIPE PIPE
THREAD THREAD
MODEL F3-PL,
MODEL F3QR-PL OR STANDARD
MODEL DH56 HSW-PL MODEL F3,
DRY SPRINKLER MODEL F3QR OR
MODEL DH56 HSW
DRY SPRINKLER
BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR
APPLICATION
016fgO8A
Fig. 11
m
Fig. 12 - XL02 Wrench
Fig. 13 - XL02 Wrench
15-
Fig. 14 - XL02 Wrench
0
Reliable ... For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision -made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured b
Reliable
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
®Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S A. 12112 P/N 9999970175