EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: September 25, 2008
To: Building Department/File
From: Mike Smith, Acting Fire Marshal 425-775-7720
Subject: Plan Check 2008-0693 Meadowdale Marina
The submitted plans have been reviewed under the 2006 IFC, the ECDC and NFPA
303 Fire Protection Standard for Marinas and Boatyards.
1) A Fire Connection Permit will be required and must be issued with the building
permits. Please refer to the City’s handout.
2) Per NFPA 303 a Class I Standpipe System will be required. This is a deferred
submittal and can be designed by your fire sprinkler contractor.
3) Permit for Fire Sprinkler Modification is required and can be a deferred
submittal. Since fire sprinkler systems already exist you will need to submit new
Sprinkler Hydraulic Calculations to justify the downsizing of the fire main to
these systems.
4) A Fire Alarm Permit will be required for Sprinkler Monitoring and other devices
per NFPA 72.
5) During Demolition and Construction a Fire Prevention Program Superintendent
appointed by the building owner will be required (2006 IFC Section 1408). Have
this person call me prior to construction for instructions.
6) Designated Fire Lanes and stripping will be required. Contact me for specifics.
7) A Fire Department Lock Box will be required for emergency access. Call my
office for authorization to purchase a box from our vendor.
8) In the permits and correspondence it appears you plan to return the project to its
original condition. Are there plans for repairing, fueling and maintenance on
boats, reopening bait and tackle shop, an eating establishment, etc? These
should be addressed as soon as possible.
As the review process continues other issues and requirements will be addressed.