Loading...
MEMO 311 MF Building.pdf MEMORANDUM Date: August 14,2015 To: Jen Machuga, Planner From: Leif Bjorback, Building Official Subject: GBH Holdings Address 303/311 Edmonds St. PLN2015-0036 I have performed a preliminary building code review of the plans that were submitted under the referenced application number, and have noticed no major building code related deficiencies in the proposed design. Code compliance of the following items should be carefully considered during the completion of the design drawings. 1.Fire rated construction of exterior walls and limitations on openings within exterior walls shall be regulated by IBC section 705. Due to the proximity of the two separate buildings on the site, show an assumed imaginary interior lot line between the two buildings in order to evaluate “fire separation distance” and associated requirements. 2.The interior exit stairway is required to be one hour fire rated per IBC 1022 and 1009.3. 3.Accessibility for the building and site shall be according to IBC chapter 11. In particular, it appears that the dwelling units on the first floor level will need to be Type B accessible units as per IBC 1107.7.1.1. 4.It is noted that exterior lighting has been shown on the preliminary plans. Code review of all lighting for compliance with the energy code will be done under the plan review for the building permit application. 5.Review of all other building code provisions will be done under the plan review for the building permit application. 6.Improvements to the existing building shall be done under separate building permits. Thank you. City of Edmonds Building Department