Microsoft Word - 10-0333 Anderson remodel.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: 5/18/10 TO: David Coleman Architecture 5206 Ballard Ave Seattle, WA 98107 RE: Plan Check: BLD20100333 Project: Anderson Remodel Project Address: 18427 Olympic View Drive During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. 1.Section 4/A3.0 refers to sheet S2.0 for the beam requirement, but sheet S2.0 was not been submitted to the city with the plans. 2.East Elevation A3.0 refers to sheet A4.0, which was not submitted to the city with the plans. 3.Because window 5/M is proposed to enlarge the existing north/south wall line enough to remove an apparent brace/shear panel, the wall line will need to be justified with calculations. If retrofit holdowns will be required to be epoxied into the existing concrete, include the minimum embedment depth along with the holdown identification. 4.Section 4/A3.0 indicates that a 2x8 ledger is to be fastened to the masonry chimney. This is in conflict with the minimum 2” air space clearance from the chimney to combustibles per R1003.18. If a new beam is proposed, include beam calculations and show how the gravity loads are transferred to footings. 5.Include a note that the smoke detectors are required to be 110V, interconnected with battery backup. 6.Section 4/A3.0 shows the lowered ceiling joists abutting the exterior wall. Provide a ledger or alternate connection detail. Pat Lawler, CBO patrick.lawler@ci.edmonds.wa.us Plans Examiner 425 771 0220 x1703