Microsoft Word - pln20110015-Lange_Wick-Memo to Planning-1.pdf
MEMORANDUM
Date:
May 27, 2011
To:
Mike Clugston, Planner
From:
JoAnne Zulauf, Engineering Technician
Subject:
PLN20110015, Lange/Wick - 3 lot Short Plat
8723 Main St.
The comments provided below are based upon review of the preliminary plans & documents
for the subject short plat. Additional information is requested from the applicant at this time
in order to continue review of the application and provide preliminary approval of the short
plat. Please ask the applicant to revise and resubmit plans addressing each of the comments
below.
Please also note, after receiving preliminary short plat approval from the Planning Division,
the applicant will be required to submit a complete set of civil engineering plans to the City
Engineering Division for review and approval.
thth
1.Please revise street name 208 St SW(Main) to Main St and 88 Ave W to
Unimproved Right of Way.
2.Label Tract A as an Access tract or Access/Utility tract if utilities will be located in the
tract.
3.Note width of access easement and width of paved portion of easement. For 3 lots, access
easement width shall be a minimum of 20ft with a minimum paved width of 16ft.
4.Please confirm that all existing trees located at the frontage of the property are shown on
the plan. Please make revisions to Tree Table if needed.
5.Show the location of existing and proposed underground utility lines, sanitary sewer
systems, water mains, water meters and water service lines from connection in right of
way to each lot within the proposed subdivision. Show that the required 2% fall can be
met for the sanitary sewer system.
6.Slope from Lot 3 outfall to proposed Main St catch basin does not meet the required fall of
.05%. Please provide invert elevations at outfall of each proposed detention system and
show minimum slope for discharge to the City system can be attained. If discharge to the
City system is not possible, then an alternate drainage proposal will need to be provided
for review and approval.
City of Edmonds
7.Show existing landscape strip along sidewalk on plans.
8.Please revise location of existing power pole at southeast corner of property to the
landscape strip. Please add second power pole located along frontage.
9.There is a power pole on the property to the west of the existing house. Please show on
plans.
10.Note location of nearest fire hydrant. Call out the distance from the property to hydrant.
Thank you.