Loading...
North Crest 4 Unit Condio 1.DOC EDMONDS FIRE DEPARTMENT MEMORANDUM Date: January 12, 2009 To: File From: Mike Smith fire Marshal 425-775-7720 Subject: North Crest 4 Unit Condo 620 Glen St The submitted plans have been reviewed under the 2006 IFC and the ECDC with the following comments: 1) Apply for a Fire Connection permit. This is not a deferred submittal and must be issued with the building permit. A handout is provided. 2) Portable fire extinguishers are required with a maximum travel distance of 75 feet. Minimum size is 2A10:B:C. 3) Address must be posted and visible from the street side of the building. Minimum 4 inch number with a one inch stroke on a contrasting backround is required. 4) Please show emergency lights and exit signs on your plans. 5) A fire Department Lock Box will be required for emergency access. Prior to building occupance please contact my office for an authorization to purchase a box. 6) Deferred submittals are: Fire Sprinkler, Fire Alarm, Life Safety Plan and Fire Portection Footprint.