EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: January 12, 2009
To: File
From: Mike Smith fire Marshal 425-775-7720
Subject: North Crest 4 Unit Condo 620 Glen St
The submitted plans have been reviewed under the 2006 IFC and the ECDC with the
following comments:
1) Apply for a Fire Connection permit. This is not a deferred submittal and must be
issued with the building permit. A handout is provided.
2) Portable fire extinguishers are required with a maximum travel distance of 75
feet. Minimum size is 2A10:B:C.
3) Address must be posted and visible from the street side of the building.
Minimum 4 inch number with a one inch stroke on a contrasting backround is
required.
4) Please show emergency lights and exit signs on your plans.
5) A fire Department Lock Box will be required for emergency access. Prior to
building occupance please contact my office for an authorization to purchase a
box.
6) Deferred submittals are: Fire Sprinkler, Fire Alarm, Life Safety Plan and Fire
Portection Footprint.