Loading...
Northpoint_RFI-081 H12 Fire Partitions in Patinet Rooms.pdfSALUS HEALTHCARE ARCHITECTURE December 14, 2018 Leif Bjorback, Kristin Johns City of Edmonds, Development Services Department 121 5th Ave N Edmonds, WA 98020 Subject: Northpoint Recovery, Remodel of Edmonds Facility Request for revision Fire Partition and Exterior Glazing Connection Permit #BLD2018-0447 RE: RFI-081 To Leif Bjorback and Kristin Johns, Venture Construction will be meeting with either Milton Thompson or Eric Carter to review the attached details. We propose to revise how the fire partitions meet the existing exterior glazing on the second floor. This revision eliminates the 1 hour rated shaft wall that branch off from the fire partition in between patient rooms to die into the exterior mullions. The proposed detail allows the fire partition directly connects to the exterior glazing and buffered by gasket and fire sealants. We are requesting one of the site inspectors approve this detail. Thank you for your consideration. Douglas McNutt Principal — Salus Architecture Encl: Architectural Details C: R. David Frum, FAIA, ACHA Z:A16029 Northpoint Recovery\Docs\06.01-MunicipalReviewVAFTER PERMIT ISSUED Request for Clarification to City_10-24-18\RFI-081 H12 Fire Partitions in Patient Rooms\Northpoint RFI-081 H 12 Fire Partitions in Patinct Rooms.docx 1402 Third Ave, Suite 200 / Seattle, WA 98101 / T 206.652.0722 / F 206.340.2266 / www.salus.archi Mr. Leif Bjorback, January 23, 2018 Page 2 Original Detail 8/A9.00 that is part of the permit set: The original detail shows the 1 hour rated shaft wall branches off from the fire partition in between patient rooms to die into the exterior mullions. 16 Gauge metal studs were installed to box off the interior side of mullion and filled with rock wool. (E) EXTERIOR WALL AND STOREFRONT SEALANT GASKET AT RATED PARTITION FILL WITH MINERAL WOOL AND FIRE CAULK EACH SIDE INSULATION OR ROCK WOOL 16 GAUGE METAL STUD ON BOTH SIDE OF MULLIONS 1 HOUR RATED SHAFT WALL ASSEMBLY GWB n FIRE PARTITION AT (E) EXTERIOR WINDOW MULLIONS 0 3" = 1.-0- Mr. Leif Bjorback, January 23, 2018 Page 3 Revised Detail: This revision eliminates the shaft wall and allow the fire partition to directly die into the exterior glazing. C VTL���AS INTERIOR EXISTING GLAZING STI SPECSEAL FIRE SEALANTS OR EQUIVALENT PRODUCT -ONE HOUR RATING GASKET ROCK WOOL fM A aZ•`? RESILIENT CHANNEL BATT INSULATION 5/8" TYPE X GWB