Oil Dock Demo.DOC
EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: August 12, 2008
To: File
From: Mike Smith, Acting Fire Marshal
Subject: Oil Dock Demolition and Removal
The Fire Department has the following comments:
Site/Demolition Plan
Submit a demolition emergency plan for approval. Plan will identify a Fire Prevention
Program Superintendent and address after hours contact and provide first response
information in case of a fire or other emergency during construction. IFC 1408
Fire Prevention Program Superintendent has the authority to enforce fire prevention
and safety provisions. He is responsible for site safety including fire safety planning,
egress maintenance, training of personnel, monitoring and maintenance of fire
protection devices and hydrant accessibility. He is also responsible for supervising the
permit system for hot work in accordance with IFC Chapter 26.
Openings of vacant structures accessible to unauthorized persons shall be boarded,
locked, blocked or otherwise protected to prevent entry by unauthorized individuals.
IFC 311
Maintain fire hydrant for fire protection water supply during demolition phase of project.
IFC 508.5.4 & IFC 1412