OLY VW 2010-0092 plan check.DOC
EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: March 24, 2010
To: Fire
From: Mike Smith, Fire Inspector 425-775-7720
Subject: Olympic View Water and Sewer Bldg Permit # BLD20100092
The fire department has the following comments based on the 2006 IFC and the
ECDC:
1) The PIV on the fire line is located down stream from the FDC. NFPA 24 does not
allow this Please contact my office and we can discuss different installations.
2) It appears you are moving the existing tank to a new location. Please refer to the
2006 IFC Chapters 22 and 34 for installation of Motor Fueling Dispensing Stations and
Storage of Class I & II Liquids in above ground tanks.
I will need more information than what was submitted ( a picture of a non descript tank
on a blank page).