Loading...
PacificNutrition1.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May 7, 2008 TO: Ralph Allen E-mail: rwallen@gracearchitectspllc.com FROM: Ann Bullis, Assistant Building Official RE: Permit: 2008-0313 Project: Pacific Nutrition th Project Address: 21827 76 Ave W, Suite C During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator. 1.Note the following codes on the coversheet of the plans. a.2006 International Building Code (including Accessibility) with State Amendments b.2006 International Mechanical Code (including International Fuel Gas Code) with State Amendments c.2006 International Fire Code with State Amendments d.2006 Uniform Plumbing Code with State Amendments e.2006 Washington State Energy Code (WAC 51-11) f.2006 Washington State Ventilation Indoor Air Quality Code (WAC 51-13) g.Edmonds Community Development Code 2.A portion of the corridor wall that has been moved as part of this TI is a shearwall per the revised structural calculations (dated 2/7/08), submitted as part of the revision to permit 2007-0382. Provide revised structural calculations (stamped and signed) to justify or redesign to include the shearwall as currently approved. 3.Two openings are now proposed in the existing shear wall that runs north/south dividing the subject suite. Provide revised structural calculations (stamped and signed) to justify the new openings. 4.Note on room layout plan how the gym will be used (e.g. aerobics, exercise equipment, etc.). 5.Revise occupant load calculations using a factor of 60 for 201C, 50 for 209C, and 100 for the remaining suite. IBC Table 1004.1 6.Revise door schedule to match door numbers on plan. 7.Revise “corridor” label to hallway where you do not intend the corridor to be 1-hour rated. 8.Add the following to the Separate Permits list on the coversheet: Fire Sprinkler Alterations, Fire Alarm Alterations, remove note “(currently under review with shell/core permit)” as it does not apply to the TI permit. 9.Remove deferred submittals list from the coversheet as everything will be included under the separate permits list. 10.A special inspection for welding is noted on the coversheet. What welding will be done as part of this tenant improvement permit? 11.Lighting Summary forms submitted were not filled out. Please resubmit.