Loading...
Plan Review Notes - Memory Care 7208 210th.doc City of Edmonds, Fire Prevention Services MEMORANDUM Date: February 8, 2016 To: Bryce Adrian, abryce@frontiereow.com From: Acting Fire Marshal Kevin Zweber 425-771-0213 Subject: BLD2016-0103 7208 210th ST SW Edmonds Memory Care Fire Alarm This Review is conducted in accordance with 2012 IFC, 2010 NFPA 72 and Edmonds Community Development Code. 1)Move FACP to room #116, Riser/Mechanical. 2)Call out outdoor rated Horn/Strobe to be located outside room #116 3)Add Strobe to rooms #241 and #341. 4)Show Type 1 Hood on Fire Alarm System Operational Matrix. 5)If present, note sloped ceilings, ceiling height differences per floor, beams, and beam pockets. IFC 907.1.2 6)Add manual pull stations near FSA in Control Stations #240 and #340. IFC 907.2 ex 2. 7)Call out duct detectors if required. 8)Call out Record of Completion. IFC 907.7.2 9)Call out required instructions and drawings. IFC 907.7.3 Please make corrections and resubmit your plans. City of Edmonds – Office of the Fire Marshal