Pre App Doug's Mazda.pdfDATE STAFF: City of Edmonds PRE -APPLICATION COMMENTS BUILDING DIVISION January 5, 2017 Leif Bjorback, Building Official RE: Project: Doug's Mazda Sales Building 22130 Highway 99 PRE2017-0001 A preliminary review was done with the pre -application materials provided and we have the following comments. 1) Codes in effect as of this meeting: a) 2015 International Building Code (including Accessibility) with State Amendments b) 2015 International Mechanical Code (including International Fuel Gas Code) with State Amendments c) 2015 International Fire Code with State Amendments d) 2015 Uniform Plumbing Code with State Amendments e) 2015 Washington State Energy Code (WAC 51-11) f) Edmonds Community Development Code 2) Basic Design Loads specific to Edmonds a) Snow load 25 psf — nonreducible b) Seismic design category D c) Ultimate wind speed 110 mph, 3 sec gust d) Wind exposure most likely B for this location 3) A soils report is required for this project. See Handout B18. 4) Plans must be stamped by a State licensed Architect or Professional Engineer, including structural plans and calculations. 5) List all separate permits on the cover sheet of the plans. Plumbing and mechanical are recommended to be listed as separate permits, along with fire sprinkler, fire alarm, signs, side sewer, water meter, State electrical, State elevator, etc. Shop drawings and similar documents may be listed as deferred submittals. 6) Provide allowable area calculations as per IBC 506. Please verify the Allowable Area figure of 36,000 sf as shown on sheet Al. It appears that this amount reflects the use of the `S 1' factor for single story buildings in IBC Table 506.2 instead of the more appropriate `SM' factor for multistory buildings. 7) On sheet Al, please revise the note regarding the "Table 504.4 Allowable stories above grade plane" to show 3 stories instead of 2. 8) On sheet Al, please revise the note regarding the "Fire resistance of exterior walls Table 602" to read "1 HR <10 FT TO PL." Building Division Pre -application Comments 1 9) It appears that portions of the building are closer than 10 feet to the property line and will need to be fire rated according to IBC Table 602. Exterior walls shall comply with IBC section 705 for fire ratings, projections and openings. 10) Provide details of fire rated walls, floor -ceilings, and projections on the plans, including the complete listed and tested fire rated assemblies and cross-reference where they apply on the plans. 11) Exit stair enclosures are required where more than 2 floor levels are open to each other. The enclosures must be 1-hour rated with self -closing fire -rated doors where connecting less than 4 stories. IBC 713.4, 1019 & 1023 12) Exit enclosures must exit directly to the outside or to an exit passageway with at least the same rating as the stair enclosure. IBC 1023 13) The building/site must be barrier free accessible including building entrances, interior and exterior accessible routes, parking, pedestrian access from the public street, customer service counters, etc. Provide details showing compliance. 14) It appears that a total of 3 accessible parking stalls will be required for the site per IBC 1106. At least one stall shall be van accessible, with a minimum 16 foot width, including access aisle. 15) An accessible route in accordance with IBC 1104 is required between the main and lower floor levels. 16) The 2nd floor restroom will need to meet accessibility standards, unless it meets an exception to IBC 1109.2. 17) Contact Steve Fisher, Recycling Coordinator, at 425-771-0235 regarding dumpster enclosure location and size. 18) Contact Jeff Groblyk, Public Works Water Division, at 425-275-4514 regarding premises isolation requirements for the facility. 19) Park impact fees will apply at the rate of $1.34 per square foot of new floor area. Building Division Pre -application Comments 2