Loading...
PRE2011-0016 SFR 92xx OVD.doc MEMORANDUM June 30, 2011 Date: Mr Bruce Lambrecht To: Fire Marshal John J. Westfall 425.771.0213 From: Subject: PRE2011-0016 Single Family Residence 92xx OVD This Review is conducted in accordance with 2009 IFC and Edmonds Community Development Code. Fire Services provides the following comments: 1. Approved fire access is 400’ from approved access roadway on Olympic View Drive. Install turnaround for private road in accordance with COE Engineering Standards. (E2.5 attached). Turnaround may incorporate private road and is not required entirely on site. 2. Existing hydrant meet proper spacing requirements ECDC 19.25.055 C. 3. For information, flow-through design residential fire sprinkler systems are required when dwelling living space exceeds 3,000 s.f. ECDC 19.05.020 C. 4. For information, provide minimum combination water-service of one inch (1”) meter and one and one quarter inch (1 ½ ”) service line for each property; or show that domestic and fire protection needs, when required, can be met with smaller service. General Facility Charges are based upon domestic requirements only. For instance, up-sizing to one inch (1”) meter will be calculated to fees for a three quarter inch (3/4”) connection. Equipment will be charged by actual equipment costs. 5. Obtain building address from Development Services for house addressed from access frontage. Post approved address on building minimum 6” letters on contrasting background viewable from private drive. City of Edmonds Office of Fire Marshal