PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: April 7, 2008
TO: Chris Harris
FAX: 425-825-3655
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check # 2008-0225
Project: Reichler Mechanical
th
Project Address: 21827 76 Ave W
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator.
1.Show how minimum ventilation will be provided to lower floor corridor, lobby and northeast
stair enclosure. (IMC 401.1, VIAQ 304 also see IMC/WAC 601, IBC 1016 & 1019)
2.Provide a site plan showing the proposed location of the heat pumps, and dimension clear width
from adjacent walkways to equipment as applicable.
3.Exhaust fan required in each of the existing restrooms to remain on the main floor. Note the
cfm and show the vent path to the exterior.
4.Complete the mechanical compliance forms for State WSEC/VIAQ. Forms can be found on the
following website: http://www.neec.net/files/forms06/MECH06.xls