Loading...
ReichlerMech1.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: April 7, 2008 TO: Chris Harris FAX: 425-825-3655 FROM: Ann Bullis, Assistant Building Official RE: Plan Check # 2008-0225 Project: Reichler Mechanical th Project Address: 21827 76 Ave W During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator. 1.Show how minimum ventilation will be provided to lower floor corridor, lobby and northeast stair enclosure. (IMC 401.1, VIAQ 304 – also see IMC/WAC 601, IBC 1016 & 1019) 2.Provide a site plan showing the proposed location of the heat pumps, and dimension clear width from adjacent walkways to equipment as applicable. 3.Exhaust fan required in each of the existing restrooms to remain on the main floor. Note the cfm and show the vent path to the exterior. 4.Complete the mechanical compliance forms for State WSEC/VIAQ. Forms can be found on the following website: http://www.neec.net/files/forms06/MECH06.xls