ReichlerREV2.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: February 21, 2008
TO: Ralph Allen
E-mail: rwallen@gracearchitectspllc.com
FROM: Ann Bullis, Assistant Building Official
th
RE: Revision to Permit 21827 76 Ave W
Project: Reichler Addition/Remodel
th
Project Address: 21827 76 Ave W
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator.
1.Revised structural calculations were not received with the revised structural plans. Please
submit so review can be completed.
2.Several shearwall numbers are missing from the plans. Please provide.
3.Provide detail of support and connections for shearwall above locations on the framing plans.
4.Include elevator pit foundation on the revised foundation plan, including details.
5.On the main floor plan, provide a self-closing 1-hour door to separate the vertical northeast exit
enclosure from the horizontal access area (IBC 1019.1). (previous item 8)
6.Provide code justification why the existing non-accessible restrooms do not have to be brought
up to code, given this extensive addition/remodel (this was an issue of the original plan review).