RESPONSE #4.docx    Hi Chuck, Thank you for the assistance this morning greatly appreciated. In the attachment should be the “clean drawing” with the changes. IN response to the questions Item (3) Installer to verify that intake openings serving the ERV’s will be at least 10’ from property line Item (4, & 6) added to the drawing one additional wall heater for a total of three (3) each units for downstairs office and other rooms, also added one (1) each laundry area exhaust fan connected to the downstairs ERV Item (5) installer to verify that exhaust opening to be at least three (3) feet from operable openings of windows or doors. Item (7) changed wording from return air to exhaust air Item (8) changed ERV # 2, 3 on drawing to be minimum 400 cfm each to handle required 706 cfm Item (9) made changes to EVR 2, and 3 to handle the 244 cfm od exhaust Item (10) will change wording from heater to fan coil   Will resend drawing with the wording changed on item (10)    Thank you,    Jon W. Kramer