Subject: Swedish Edmonds ACC (Fire Marshall Permit Review) -Responses
Permit: 2014-0238
Below are responses to the Fire Marshal review comments prepared by John Westfall, dated April 7,
2014. Corresponding drawings have been previously submitted under separate cover. If additional
copies are required, please let me know.
ecoYALE AVENUE NORTH SEATTLE mmeumynun*z2a 5555 r>2^aa21caoo
I
C2.00-AO.21 Snohomish Fire District 1
Confirmed. Meeting held 08/12/14.
requests preconstruction meeting to
7
clarify ingress & egress for emergency aid
apparatus, emergency room access,
continuity of operations, and emergency
fire response.
2
C2.00 -M1.01 Tank removal permit
Confirmed, tank removal permit will be
required for abatement & replacement of
coordinated by Contractor.
existing underground fuel tank(s).
3
Doublecheck assembly is located interior
[Ccli] Agreed the DCVA shall be listed. The
MECH ROOM 0186.000. DCDA is not
fire protection system including the DCVA is
specified on civils. Fire Connection Permit
part of the fire protection engineers design
will be required. Provide model and type
and drawing package. The fire protection
for WQ approval. Also, WQ must approve
sheets and specifications are provided such
the location interior, given the 50' length
that a qualified design build fire protection
of the Supply pipe from main to DCDA.
company can be hired. CDi does review their
Contact Linda McMurphy, 425.771.0235.
design. We don't know if a contractor has
(see 18a)
been chosen and/or when to expect a
submittal to review.
4
C5.10, C5.14-.15 Retention pipe in
Confirmed. Detention pipe shall meet
emergency apparatus lane at south shall
WSDOT and City of Edmonds standards,
meet the live loads of fire apparatus
ecoYALE AVENUE NORTH SEATTLE mmeumynun*z2a 5555 r>2^aa21caoo
www. nbbj. com
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
A1.01 -A1.02 Show calculations and paths
Refer to A1.01 and A1.02, Life Safety Plans,
5
for egress. Are elevators intended to be
for requested travel distance analysis.
used as component of egress?
Elevators are not intended to be used as
egress components.
6
A1.01 -A1.02 Show calculations for
Refer to A1.01 table titled "Smoke
establishing ("patient") refuge areas and
Compartment Required Refuge Area" for
call out on plans IBC 407.5.1.
Level One calculations. Level Two is shell
space and "patient" refuge areas do not
apply.
7
Rooms are called out for PATIENT RM and
The (10) Patient Rooms in the Observation
EXAMINATION only. Are any sleeping
Unit are for patient stays up to 24 hours; it is
rooms within scope of project? If so,
likely that patients will sleep in these rooms.
indicate locations, and "patient load"
IBC 407.4.3.5 applies to sleeping rooms in
calculations. IBC 407.4.3.5.
care suites. Refer to A1.01- the Observation
Unit is not a care suite, it uses a corridor
system.
8
Callout installation of carbon monoxide
[Sparling] The carbon monoxide monitors in
alarms, where required.
the Lobby and areas open to the lobby are
called
out on the E4 series drawings (combination
smoke detector and CO monitor).
9
A2.01A & A2.01C Location of AFTER
The after hourse security grille has been
HOURS SECURITY GRILLE match line G.5-
deleted. Refer to A2.01A and A2.01C.
5.0 is unclear, please clarify.
10
A1.02 & E2.02A Provide exit signs for
[Sparling] Refer to E2.02A, dated 07/24/14.
egress from SHELL SPACE 2A & 2B.
Exit signs have beeen added in the Level 2
shell spaces.
11
Post address at north end of east and
Address will be posted above the main entry
west elevations, scaled to existing
doors on the north elevation to comply with
buildings on campus.
Chapter 19, Section 501.2. Please clarify if
additional address markers are required on
the (existing) east elevation.
12
M5.01A Is generator diesel- or natural
[CDi] Refer to M5.01A, dated 06/10/14.
gas -fueled?
Diesel and Natural gas have been deleted
from the HVAC with our change over to
steam heat.
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
www. nbbj. cont
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
•
o
[CDi] Yes, Swedish facilities has confirmed
13
M1.01 Is 02 control valve provided for
(exterior) control of 2" supply line?
there is an existing exterior control valve.
14
M1.01-M3.01B-M7.04 Regarding oil and
[Cdi] Refer to M1.01-M3.01B-M7.04, dated
02 separation note, there is existing
07/24/14. Diesel and Natural gas have been
diesel generator in lower existing
deleted from the HVAC with our change over
mechanical room near Emergency Room.
to steam heat. Sheets revised in the
02 comes in building at lower mechanical
construction set. Swedish facilities has
room. Are these separate spaces?
confirmed the existing oxygen does not come
in through the mechanical room. It comes in
through a separate space.
15
It appears fire detection will consist of
[Sparling] The design intent is to provide
"corridor" smoke detectors in lieu of UL
smoke detection in the corridors of Level 1 in
268 smoke alarms. Please clarify design
order
for assist in fire alarm permit and building
to accommodate any spaces open to the
permit reviews. IBC 407.7-8
corridor per IBC 407.2.1.
16
Can INTERSTITIAL SPACE be accessed for
Interstitial Space is to be accessed for
maintenance or other purpose, and what
maintenance purposes only and is achieved
purpose? Call out access(es)?
via fixed ladder/floor hatch located at
approximately Grids A.3/2.8.
17
A9.11- .13 vs. Life Safety Plans
17a
Overhead Coiling Fire Doors (OCFD)
[Sparling] All overhead coiling fire doors will
0102.009A shall be connected to building
be connected to the building fire alarm
fire alarm, matchline 8.0-4.5
system.
17b
Magnetic hold -opens, where provided,
[Sparling] All magnetic hold open devices will
shall be connected to building fire alarm.
be connected to the building fire alarm
system.
17c
Assemblies 0103.031 and 0186.004
Refer to A9.12, dated 07/24/14, for revisions
callout NR SMOKE protection, matchline
to door ratings of 0103.031. Door 0186.004
D.5-5.0.
does not exist, however, if the comment
refers to Door 0186.000A, this door has been
deleted. Refer to A2.01C, datd 06/10/14.
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
www. nbbj. cons
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
•
Assembly 0101.004 callout NR SMOKE
's
Refer to A9.11 for revision to door rating.
17d
protection, matchline H.5-4.5.
Please note that this change was made post -
permit submission as part of our Construction
Documents release and therefore is not
clouded.
17e
Assembly 0104.005 callout, matchline
Refer to A9.12 for revision to door rating.
K.5-2.0.
Please note that this change was made post -
permit submission as part of our Construction
Documents release and therefore is not
clouded.
17f
Assembly 0104.014 callout, matchline J.5-
The door to PAT TLT 0104.014 was mislabeled
2.0.
in the permit submission as Door 0104.006.
This door was renumbered 0104.014 to
match the room number is not required to be
rated. The door is included in the door
schedule on sheet A9.12. Please note that
this change was made post -permit
submission as part of our Construction
Documents release and therefore is not
clouded.
17g
Assembly 0101.002F callout rating for 90
See A9.11 for revision to door rating. Please
min F.R. corridor doors, matchline YA-4.0.
note that this change was made post -permit
submission as part of our Construction
Documents release and therefore is not
clouded.
17h
Assembly 0101.003 callout rating for 90
See A9.11 for revision to door rating. Please
min F.R. corridor doors, matchline YA-8.5.
note that this change was made post -permit
submission as part of our Construction
Documents release and therefore is not
clouded.
17i
Callout NR SMOKE for all assemblies in
See A9.12 and A9.13 revised rating at Doors
CORRIDOR 0104.002, matchline K.0-1.5.
0104.007, 0188.000A, 0188.0006, 0104.011A,
0104.01113, 0104.012A, and 0104.013A.
Please note that this change was made post -
permit submission as part of our Construction
Documents release and therefore is not
clouded.
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
www.nbbj.com
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
e
Assembly 0104.001A callout rating for 90
•®
See A9.12 for revision to door rating. Please
17j
min F.R. corridor doors matchline M.5-
note that this change was made post -permit
2.0.
submission as part of our Construction
Documents release and therefore is not
clouded.
17k
Assembly 0105.011B callout rating for 90
Door 0105.0118 is in an unrated partition and
(or 45?) F.R. corridor doors, level one
therefore does not require a rating. They
west.
exist for operational purposes rather than life
safety.
171
Assembly 0204.031 callout 90 min. F.R.
Refer to A2.02D and A9.13, dated 06/10/14.
doors at west CONNECTOR.
Door has been renumbered 0204.031 and is
90 -min rated.
17m
Assembly 0201.002 callout NR SMOKE
See A9.13 for revision to door rating.
protection, matchline J.0 -X8.
18a
Required permits/submittals include:
Section 211000, 1.6.13 requires a Level 3
Fire Connection Permit (CIVIL UTILITY and
certified sprinkler designer or Registered
PLUMBING series) Callout Fire
Profesional Fire Protection Engineer. Fire
Connection Permit (FCP) on building
protection drawings will be a deferred
plans, OR callout and detail fire
submittal.
protection supply on civil engineering
plans. Fire connection permit is required
for the installation of the underground
supply for your fire protection system
and to de -conflict utility work.
Underground design must be stamped by
registered PE or a Level III (WA) fire
sprinkler contractor AND the installer
must also stamp the plans. The installer
must be either Level III or Level "U" fire
sprinkler contractor licensed by the State.
Provide three copies of plans showing all
valves, vault location, post indicating
valve, fire department connection and
piping to include size and material,
hydraulic calculations, thrust blocking
with calculations, pipe bury depth and
any and all other materials used and their
fire protection listings. RCW 18.160.070 /
RCW 18.27.110
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
www. nbbj. com
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
18b
Fire Sprinkler System Permit (M6 series)
Confirmed. Fire sprinklers will be provided
i. Callout Fire Sprinkler System permit IFC
throughout.
105.7.1. Automatic sprinkler is required
throughout all occupancies in building.
Standpipes may be included in sprinkler
scope & design.
18c
Distributed Antenna System (DAS) Permit
[Sparling] The Distributed Antenna System
(LOW VOLTAGE and TELECOM series)
(DAS) will be submitted for permit after the
i. (TELECOM) DAS for emergency
100% Construction Documents are
responder mobile radio coverage will
completed.
require building permit and approval.
Wired communications are not
acceptable means of emergency
communications. Reference IFC 510 for
permit and technical requirements,
system design, installation requirements
and acceptance testing, when DAS
requirement is determined. Review and
concurrence will also be provided
through Snohomish Emergency Radio
System (SERS).
18d
Fire Alarm Permit (LOW VOLTAGE series)
[Sparling] The Fire Alarm System will be
i. Automatic fire alarm system is required
submitted for permit after the 100%
for purposes of off-site sprinkler system
Construction
monitoring, smoke -detected egress, and
Documents are completed and the Fire Alarm
local alarm audible/visual notification and
shop drawings are completed.
exterior audibility.
18e
Tank Decommissioning/ Installation
Confirmed. Contractor will obtain permit.
Permit
19a
Regarding fire suppression/detection
[Sparling] The Fire Alarm Control Panel will be
systems design:
moved to Mech 0186.000.
a. Collocate fire alarm control panel
(FACP) in fire sprinkler riser room.
19b
Provide fire alarm enunciator at building
[Sparling] A Fire Alarm Annunciator will be
entry.
added in Vestibule 0103.029.
19c
M2.014 KEYNOTE 16 note Fire
[CDi] Refer to M2.01A, dated 07/24/14. Note
Department Connection provides 4" Storz
16 altered to include 4" Storz type with 30
connector with 30 degree angle.
degree angle.
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300
www.nbbj.com
Should additional questions and comments arise, we request that a meeting be set up to allow
conversation and collaboration on responses.
Please don't hesitate to contact me.
Rachel Jenner, Project Manager
rienner@nbbi•com
(w) 206-621-2366, (c) 206-910-4445
Cc: Bryan Hall
Tyler Howren
Chuck Kolb
John Mengedoht
Andris Lapins
Dan Schnebele
223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 r) 206 621 2300
Your fire protection systems underground
Confirmed. The Contractor will select a
19d
contractor, sprinkler designer and
qualified fire protection contractor.
installer are required to be licensed by
Office of the State Fire Marshal for that
work.
19e
Gypsum -sheathed elevator shaft meets
Need clarification from Fire Marshal. Per
definition of "non-combustible" for
2013 NFPA 13, 8.15.5.7.1, "Sprinklers shall be
purpose of eliminating required sprinkler
installed at the top and bottom of elevator
at top of shaft.
hoistways where elevators utilize
combustible suspension means such as
noncircular elastomeric-coated or
polyurethane -coated steel belts." The
specified Otis Gent utilizes a coated belt.
19f
1-2 occupancy requires Quick Response or
[CDi] Refer to M6.xx series, dated 06/10/14.
residential sprinklers.
Quick response heads are required and are
noted.
20
Provide minimum rated 2A:10B:C
Confirmed. 4A:80B:C portable fire
portable fire extinguishers in accordance
extinguishers are currently specified.
with NFPA 10.
21
Provide Snohomish County FD#1
Knox Company Knox -Vault 4100 Series Single
Knoxbox, located at exterior entry to
Lock Recessed Mount model has been
MECH ROOM 0186.000. Preapproval may
specified. See elevation 4/A4.02 for
be had online at www.knoxbox.com .
documentation of mounting location.
Should additional questions and comments arise, we request that a meeting be set up to allow
conversation and collaboration on responses.
Please don't hesitate to contact me.
Rachel Jenner, Project Manager