Loading...
Response Letter to Non-Structural Review #2.pdf�1 0O�� ]uk/1,2O14 J0�\ � " � ~-�. Leif0]orback Building Official, City ofEdmonds 1215th Avenue North Edmonds, WA 98026 Subject: Swedish Hospital Addition (N#n-Structuna|Review) -Rmoponses Permit: 2014-0238 Below are responses to the second non-structural review comments prepared by Beck &Associates, dated June 21,2O14. Corresponding drawings have been clouded with a delta that referenced "Permit Revisions". Slip sheet hardcopies have been provided to replace sheets previously submitted. 22uYALE AVENUE NORTH SEATTLE xmno10ynmv,2o 5555 nmvs,/xoon The Observation area is required to be provided Refer to A2.01B. A shower head and floor drain with a bathtub/shower in accordance with Table have been added to Toilet 0105.014. 2902.1. Provide complete design and detailing. The bathtub/shower is required to be accessible. (Chapter 29, WA State Amendments) Submit specifications for the 'metal panel' wall See enclosed Specification Section 074219 assembly for our review. The applicant will need Insulated Metal Panel Backup Wall to demonstrate that the 'metal panel' wall is not Assemblies. MCM are covered in section 1407 classified as MCM and that the requirements of of the IBC and covers products with core 2603 are met. densities greater than 20 pcf. The specified product, Centria MetalWrap, is covered in IBC Chapter 26, which covers foam plastics with core densities less that 20 pcf. (MetalWrap foam is I he p[ opused alternate method requires (2) 2- Please see additional notes on A2.0113 calling hour fire barriers to be provided across the out existing 2 -hour solid concrete walls, 8" building to separate the high-rise portion from minimum thickness. Additionally, see A9.12 for the new structure. Some of the walls located identification of door 0104.001A as 90 -minute where the new 2 -hour wall is required (closest rated. to the new construction), are not identified as 2 - hour walls. All walls required to be 2 -hour rated by the AMM (alternate method) and as required to provide a complete separation need to be specified on the plans to be 2 -hour rated (including identification of the required wall types). Additionally, Door 0104.001A is requi to be identified as a 90 -minute rated cloor. Update sheet A2.01 and A9.1.2 accordingly. 22uYALE AVENUE NORTH SEATTLE xmno10ynmv,2o 5555 nmvs,/xoon www.nbbli.com ® • a '0 e e 22 Reference newly added sheet A0.20 — See below. Architectural Site Plan. a1) Sheet A0.20 identifies a property line that a1) The eastern property line was incorrectly appears to run through the eastend of the new shown. See sheet A0.20 for corrected extents. addition (running Ill Buildings are not permitted to cross property lines. The property. a2) The fire separation distance from the east line will need to be adjusted or removed face of the new addition to the property line has through a boundary line adjustment prior to been identified on All See sheets A2.01A, permit approval. This is required regardless of if A2.02A, A2.03A and A4.12 for 1 -hour rated wall the properties are owned by the same entity. extents. Per Table 705.8, there is no limit to the allowable area of exterior wall openings. a2) A property line is identified on the west side of the Stevens Medical Office Building. Identify a3) The existing PSTI building to the south of the the fire separation distance from the east face proposed addition is Type II B Construction with of the new addition to this property line. If the less than 45% openings on its north elevation. distance is less than 30'-0", then the exterior Therefore, no rating is required along the south wall will need to be 1 -hour rated full -height. If face of the proposed addition, as the exterior this is the case, the floor plans will need to be wall separation distance exceeds the minimum updated to identify a 1 -hour rated wall type for 10'-1" and the canopy separation distance these walls. Provide an analysis for exceeds the minimum 40" separation. determination of allowable opening percentage in the exterior wall and protect openings as required. a3) The plans identify a fire separation distance of 28'-3" on the south side of the new addition. The exterior walls are required to be 1 -hour rated full -height. The floor plans need to be updated to identify a 1 -hour rated wall type for these exterior walls. Please be aware that a 1 - hour rated wall, rated from the interior side only) is permitted. However, the wall listing is required to be specifically for a 1 -hour rated wall, from the interior only. Using a 1 -hour assembly that is rated from both sides and eliminating the exterior side protection does not comply. 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 r) 206 621 2300 www. nbbj. com 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300 • •.I1i1IIIIII1jjIIIIIIIIII•• •. 23 In response to this comment, the Door See revisions to A9.11, A9.12 and A9.13. Notes Schedule (A9.11, A9.12, & A9.13) was related to individual doors have been deleted updated to identify smoke & draft control and replaced with general door and frame assemblies tested in accordance with UL1784 schedule note #1 stating required compliance for non -rated and 20 -minute rated doors. The with UL 1784. requirement for smoke & draft control assemblies tested in accordance with UL1784 applies to ALL fire-resistant rated doors, whether they are 20 -minute rated, 45 -minute rated, or 90 -minute rated. Update the schedule accordingly to identify this requirement at all rated doors. It may be simplest to make a 'blanket' statement within the Door Schedule for all fire-resistant rated doors to meet this requirement. Corridor 0202.002 (Level Two Plan — A; sheet Corridor 0202.002 will not be used for bed A2.02A) is required to have aminimum clear movement. 72" has been provided, which width of 8'-0". Update the plans accordingly. exceeds the minimum 3'-8" required. 27 A plan sheet is required to be added after the Refer to new sheets A9.13a and A9.13b for door Door Schedule that includes pertinent door hardware schedule. hardware requirements in order to demonstrate compliance with the code. 30 The plans do not appear to have addressed Previously, a wall phone was provided at the this issue. Identify the location of and all Level 2 elevator lobby to serve this function. The requirements for the two-way communication wall phone has now been replaced with a system. traditional two-way communication system. Refer to E0.00, E3.012, E4.015, E4.02A and E10.03 for details. Fyi, spec Section 283200 - Area of Rescue Intercom System, has also been added for Contractor information. 30a The system is required to provide Refer to E0.00, E3.012, E4.015, E4.02A and communication between the 2nd Floor E10.03 for two-way communication system at the elevator and the fire command center or Level 2 elevator lobby. central control point location approved by the fire department. Where the central control point is not constantly attended, a two-way communication system shall have a timed automatic telephone dial -out capability to a monitoring location or 9-1-1. 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300 1 www.nbbj.com 30b The two-way communication is required to include both audible and visible signals. Confirmed. The requirements for audible and visible signals are included in added spec section 283200 for the Contractor's information. 30c Directions for the use of the two-way Refer to added note on A2.02A, referencing communication system, instructions for electrical spec for two-way communication summoning assistance via the two-way system for signage including instructions for use, communication system and written summoning assistance and signage. identification of the location are required to be posted adjacent to the two-way communication system. This needs to be clearly stated within the drawings. 32 This item remains to be addressed.Accessible Observation Patient Rooms and Toilets are units and Type B units are required to be accessible. provided in general purpose hospitals in accordance with 1107.5.3.1 and 1107.5.3.2. It appears that this will apply to the Observation area. 33 Reference A5.01. The vertical grab bar at Refer to A5.01 for dimensions on vertical grab toilets is required to be located 39"-41" from bar, toilet seat height, max height at sinks in the back wall. It is currently specified as 42" toilet rooms and knee/toe clearances. from the back wall. Specify required toilet seat height. Specify the maximum height at sinks in toilet rooms (34") and provide detailing & dimensioning to demonstrate that knee & toe clearance are provided. 37 Reference A4.64 — Staff Shower. Provide Refer to Detail 18, 19, 20/A4.65. A note has complete detailing, dimensions, and been added to refer to A5.01 for mounting specifications to demonstrate that all dimensions. accessibility requirements will be met. 44 The pass-thru's need to be specified within See A1.01. Due to the high-cost of rated pass - the drawing set as 90 -minute rated. thru's ($5K each), we propose adjusting the rated partition on encompass the adjacent Toilet rooms as shown on the attached sketch. This approach is acceptable from DOH's perspective, per discussion with CRS reviewer, Clynn Wilkinson. (Note the pass-thru's are critical for staff efficiency and to prevent patients from having to walk into the hallway carrying a specimen cup.) 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300 www.nbbj.com 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 r) 206 621 2300 45 The Observation area either needs to meet The Observation area meets the requirements for the requirements for a 'Care Suite' (407.4.3) a Corridor system with an open Care Station. We OR 'Corridors.' Since the team has chosen not respectfully disagree with the interpretation that to treat this as a 'Care Suite' (due to the the Care Station needs to be enclosed with a number of rooms exceeding the permitted smoke partitions in addition to the surrounding number for a Care Suite), the space interior to smoke partitions that separate the Corridor from the Observation area (corridor area where the the Patient Rooms. See attached 2012 IBC Care Stations, etc. are located) needs to meet Commentary - Figure 407.2.2 for a diagram of all of the requirements for corridors (407.2). the relationship of open Care Station to The plans show that the Care Provider Station surrounding smoke partitions and patient rooms (including both Care Team Stations, Med, & in an 1-2 occupancy. Nourish) is located within the corridor space (defined as a corridor since the Observation What may have been unclear on is that existing area is not being designated as a Care Suite). concrete walls to remain will complete the smoke Section 407.2.2 specifically states: "Spaces for partition between the corridor and patient care providers', supervisory staff, doctors' and rooms. Refer to A2.0113, a note has been added nurses' charting, communications and related to clarify the existing wall construction. clerical areas shall be permitted to be open to the corridor, where such spaces areconstructed as required for corridors." Section 407.2 (along with 407.3) requires corridors to be separated from other areas via smoke partitions. Currently, plans show the Care Provider Station to be open to the corridor. The code requires these areas to be separated from the other corridor spaces via smoke partitions. Revise the plans to demonstrate compliance with either the Corridor provisions (407.2) or the Care Suiteprovisions (407.4.3) of the code. 46 The drawings need to be updated to See response to Comment #12. demonstrate that the proposed 2 -hour wall will provide a complete separation between the spaces. Reference our new comments to comment #12, above. 47 The drawings need to identify existing See response to Comment #12. construction as 2 -hour rated (verify in field). Additionally, Door 0104.001A is required to be 90 -minute and meet the requirements for smoke/draft control. 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 r) 206 621 2300 www.nbbj.com Should additional questions and comments arise, we request that a meeting be set up to allow conversation and collaboration on responses. Please don't hesitate to contact me. Rachel Jenner, Project Manager rlenner@nbbl.com (w) 206-621-2366, (c) 206-910-4445 Cc: Bryan Hall Tyler Howren Chuck Kolb John Mengedoht Amy Frerker Andris Lapins Dan Schnebele 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300 ® . • Ill! 110 NONE=. 50 This door (0101.009) is located in a corridor Refer to A9.11 for updated door schedule. Note and is therefore required to be a door that that doors 0101.007 and 0101.008 were also meets smoke & draft control requirements. corrected to be required to meet smoke and Update the Door Schedule accordingly. draft control requirements. 51 Update the Door Schedule to indicate that Refer to A9.11 for updated door schedule. this door (0101.003) is required to meet Reference response to comment 23. smoke & draft control requirements. 52 Update the Door Schedule to indicate that Refer to A9.11 for updated door schedule. Door 0101.00613 is required to meet smoke & Reference response to comment 23. draft control requirements. 54 Sheet A2.02D was not included in the revised Refer to sheet A2.02D. drawing set. Please make sure this sheet is included when resubmitting drawing sets in response to this comment letter. 60 The City does not review the Specifications. The new elevators do not serve all floors of the The plans (A7.11) need to be updated to building and therefore do not need to meet this demonstrate that all of the elevator requirement. However, we have added requirements, as indicated in the initial information to A7.11 showing the ambulance comment, will be met. stretcher footprint. The specified cab dimensions are 715/16" wide by 102" long with W-6" clear cab openings. The cab opening orientations shown in the DPD Code Solution diagram do not apply to this project; stretchers are loaded straight into the cab with no turning required. Should additional questions and comments arise, we request that a meeting be set up to allow conversation and collaboration on responses. Please don't hesitate to contact me. Rachel Jenner, Project Manager rlenner@nbbl.com (w) 206-621-2366, (c) 206-910-4445 Cc: Bryan Hall Tyler Howren Chuck Kolb John Mengedoht Amy Frerker Andris Lapins Dan Schnebele 223 YALE AVENUE NORTH SEATTLE WA 98109 T) 206 223 5555 F) 206 621 2300 Reference: Comment #11 Swedish Edmonds Ambulatory Care Center SECTION 074219 Construction Documents INSULATED METAL PANEL 10 June 2014 BACKUP WALL ASSEMBLIES 1.1 SUMMARY A. Section Includes: 1. Foamed -insulation -core metal backup wall assemblies for the following cladding systems: a. Formed metal wall panels. b. Composite material wall panels. C. Fiber -reinforced concrete panels. 1.2 SUBMITTALS A. Product Data: For each type of product. 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of panel and accessory. B. Shop Drawings: 1. Include fabrication and installation layouts of metal panels; details of edge conditions, joints, panel profiles, corners, anchorages, attachment system, trim, flashings, closures, and accessories; and special details. C. Samples for Verification: For each type of exposed finish, prepared on Samples of size indicated below. 1. Metal Panels: 10 inches long by actual panel width. Include fasteners, closures, and other metal panel accessories. D. Qualification Data: For Installer. E. Product Test Reports: For each product, tests performed by a qualified testing agency. F. Sample Warranties: For special warranties. G. Maintenance Data: For metal panels to include in maintenance manuals. 1.3 QUALITY ASSURANCE A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer. A. Deliver components, metal panels, and other manufactured items so as not to be damaged or deformed. Package metal panels for protection during transportation and handling. NBBJ Project No. 100822.06 074219-1 Reference: Comment #11 Swedish Edmonds Ambulatory Care Center SECTION 074219 Construction Documents INSULATED METAL PANEL 10 June 2014 BACKUP WALL ASSEMBLIES B. Unload, store, and erect metal panels in a manner to prevent bending, warping, twisting, and surface damage. C. Stack metal panels horizontally on platforms or pallets, covered with suitable weathertight and ventilated covering. Store metal panels to ensure dryness, with positive slope for drainage of water. Do not store metal panels in contact with other materials that might cause staining, denting, or other surface damage. D. Retain strippable protective covering on metal panels during installation. 1.5 FIELD CONDITIONS A. Weather Limitations: Proceed with installation only when existing and forecasted weather conditions permit assembly of metal panels to be performed according to manufacturers' written instructions and warranty requirements. A. Coordinate metal panel installation with rain drainage work, flashing, trim, and other adjoining work. 1.7 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of metal panel systems that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Failures including rupturing, cracking, or puncturing. b. Deterioration of metals and other materials beyond normal weathering. 2. Warranty Period: Two years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Basis -of -Design System: Subject to compliance with requirements, provide CENTRIA Architectural Systems MetalWrap or comparable system by one of the following: 1. Kingspan; Karrier Panel. 2. Metl-Span LLC; HPCI Barrier Panel. A. Insulated Metal Wall Panel Backup Wall Assembly: Consisting of foamed -insulation -core metal -skinned wall panels and accessories, attached to metal framing with clips, serving as combined thermal, air, and moisture barrier and support for cladding system specified elsewhere. NBBJ Project No. 100822.06 074219-2 Reference: Comment #11 Swedish Edmonds Ambulatory Care Center Construction Documents 10 June 2014 2.3 PERFORMANCE REQUIREMENTS SECTION 074219 INSULATED METAL PANEL BACKUP WALL ASSEMBLIES A. Structural Performance: Provide metal panel systems capable of withstanding the effects of the following loads, based on testing according to ASTM E 72: 1. Wind Loads: As indicated on Drawings. 2. Other Design Loads: As indicated on Drawings. 3. Deflection Limits: For wind loads, no greater than 1/180 of the span. B. Air Infiltration: Air leakage of not more than 0.01 cfm/sq. ft. when tested according to ASTM E 283 at the following test -pressure difference: 1. Test -Pressure Difference: 6.24 Ibf/sq, ft. C. Water Penetration under Static Pressure: No water penetration when tested according to ASTM E 331 at the following test -pressure difference: 1. Test -Pressure Difference: 15 Ibf/sq. ft. D. Thermal Performance Test: Thermal Resistance (R -value) indicated, in accordance with ASTM 01363, corrected to 15 mph (24.1 k/h) outside and still air inside, as -installed condition including fastening and joints. E. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes by preventing buckling, opening of joints, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime -sky heat loss. 1. Temperature Change (Range): 120 deg F, ambient; 180 deg F, material surfaces. F. Fire -Test -Response Characteristics: Provide metal wall panels and system components with the following fire -test -response characteristics, as determined by testing identical panels and system components per test method indicated below by UL or another testing and inspecting agency acceptable to authorities having jurisdiction. Identify products with appropriate markings of applicable testing agency. 1. Fire -Resistance Characteristics: Provide materials and construction tested for fire resistance per ASTM E 119. 2. Intermediate -Scale Multistory Fire Test: Tested mockup, representative of completed multistory wall assembly of which backup assembly is a part, complies with NFPA 285 for test method and required fire -test -response characteristics of exterior non -load-bearing wall panel assemblies. 3. Radiant Heat Exposure: No ignition when tested according to NFPA 268. 4. Potential Heat: Acceptable level when tested according to NFPA 259. 5. Surface -Burning Characteristics: Provide wall panels with a flame -spread index of 25 or less and a smoke -developed index of 450 or less, per ASTM E 84. 6. Fire Performance: Approved as a Class 1 wall panel per ANSI/FM 4880. A. General: Provide factory -formed and -assembled metal wall panels fabricated from two metal facing sheets and insulation core foamed in place during fabrication, and with NBBJ Project No. 100822.06 074219-3 Reference: Comment #11 Swedish Edmonds Ambulatory Care Center SECTION 074219 Construction Documents INSULATED METAL PANEL 10 June 2014 BACKUP WALL ASSEMBLIES joints between panels designed to form weathertight seals. Include accessories required for weathertight installation. 1. Insulation Core: Modified isocyanurate or polyurethane foam using a non -CFC blowing agent, with maximum flame -spread and smoke -developed indexes of 25 and 450, respectively. a. Closed -Cell Content: 90 percent when tested according to ASTM D 6226. b. Density: 2.0 to 2.6 Ib/cu. ft. when tested according to ASTM D 1622. C. Compressive Strength: Minimum 20 psi when tested according to ASTM D 1621. d. Shear Strength: 26 psi when tested according to ASTM C 273/C 273M. 2. Metallic -Coated Steel Sheet: Facings of zinc -coated (galvanized) steel sheet complying with ASTM A 653/A 653M, G90 coating designation, or aluminum -zinc alloy -coated steel sheet complying with ASTM A 792/A 792M, Class AZ50 coating designation; structural quality. Prepainted by the coil -coating process to comply with ASTM A 755/A 755M. a. Nominal Thickness: 0.019 inch. b. Finish: Siliconized polyester. 3. Panel Sealant: Factory -applied non -curing butyl. 4. Panel Coverage: 36 inches nominal. 5. Panel Thickness: 3.0 inches. 6. Thermal -Resistance Value (R -Value): R-21 according to ASTM C 1363. 7. Panel Configuration: Provide metal wall backup panels configured for the following application: a. Horizontal metal wall backup panels with integral pre -punched attachment system configured to serve as attachment points for manufacturer -furnished vertical subgirts to receive horizontal cladding. 2.5 MISCELLANEOUS MATERIALS A. Miscellaneous Metal Subframing and Furring: ASTM C 645, cold -formed, - metallic -coated steel sheet, ASTM A 653/A 653M, G90 coating designation or ASTM A 792/A 792M, Class AZ50 aluminum -zinc -alloy coating designation unless otherwise indicated. Provide manufacturer's standard sections as required for support and alignment of metal panel system. B. Panel Accessories: Provide components required for a complete, weathertight panel system including trim, copings, fasciae, mullions, sills, corner units, clips, flashings, sealants, gaskets, fillers, closure strips, and similar items. Match material and finish of metal panels unless otherwise indicated. C. Panel Fasteners: Self -tapping screws designed to withstand design loads. Provide exposed fasteners with heads matching color of metal panels by means of plastic caps or factory -applied coating. Provide EPDM or PVC sealing washers for exposed fasteners. D. Panel Sealants: Provide sealant type recommended by manufacturer that are compatible with panel materials, are nonstaining, and do not damage panel finish. NBBJ Project No. 100822.06 074219-4 Reference: Comment #11 Swedish Edmonds Ambulatory Care Center Construction Documents 10 June 2014 E M SECTION 074219 INSULATED METAL PANEL BACKUP WALL ASSEMBLIES 1. Sealant Tape: Pressure -sensitive, 100 percent solids, gray polyisobutylene compound sealant tape with release -paper backing. Provide permanently elastic, nonsag, nontoxic, nonstaining tape 1/2 inch wide and 1/8 inchthick. 2. Joint Sealant: ASTM C 920; elastomeric polyurethane or silicone sealant; of type, grade, class, and use classifications required to seal joints in metal panels and remain weathertight; and as recommended in writing by metal panel manufacturer. 3. Butyl -Rubber -Based, Solvent -Release Sealant: ASTM C 1311. Self -Adhering Flexible Flashing: Comply with Section 076000 "Flashing and Sheet Metal." A. General: Fabricate and finish metal panels and accessories at the factory, by manufacturer's standard procedures and processes, as necessary to fulfill indicated performance requirements demonstrated by laboratory testing. Comply with indicated profiles and with dimensional and structural requirements. B. Provide panel profile, including major ribs and intermediate stiffening ribs, if any, for full length of panel. C. Fabricate metal panel joints with factory -installed captive gaskets or separator strips that provide a weathertight seal and prevent metal -to -metal contact, and that minimize noise from movements. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances, metal panel supports, and other conditions affecting performance of the Work. 1. Examine wall framing to verify that girts, angles, channels, studs, and other structural panel support members and anchorage have been installed within alignment tolerances required by metal wall panel manufacturer. B. Examine roughing -in for components and systems penetrating metal panels to verify actual locations of penetrations relative to seam locations of metal panels before installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. A. Miscellaneous Supports: Install subframing, furring, and other miscellaneous panel support members and anchorages according to ASTM C 754 and metal panel manufacturer's written recommendations. NBBJ Project No. 100822.06 074219-5 Reference: Comment #11 Swedish Edmonds Ambulatory Care Center Construction Documents 10 June 2014 3.3 METAL PANEL INSTALLATION SECTION 074219 INSULATED METAL PANEL BACKUP WALL ASSEMBLIES A. General: Install metal panels according to manufacturer's written instructions in orientation, sizes, and locations indicated. Install panels perpendicular to supports unless otherwise indicated. Anchor metal panels and other components of the Work securely in place, with provisions for thermal and structural movement. B. Fasteners: Use fasteners recommended by manufacturer. C. Metal Protection: Where dissimilar metals contact each other or corrosive substrates, protect against galvanic action as recommended in writing by metal panel manufacturer. D. Joint Sealers: Install gaskets, joint fillers, and sealants where indicated and where required for weathertight performance of metal wall panel assemblies. Provide types of gaskets, fillers, and sealants indicated by metal panel manufacturer; or, if not indicated, provide types recommended by metal wall panel manufacturer. E. Foamed -Insulation -Core Metal Wall Panels: Fasten metal wall panels to supports with concealed clips at each joint at location and spacing and with fasteners recommended by manufacturer. Fully engage tongue and groove of adjacent panels. 1. Install clips to supports with self -tapping fasteners. F. Accessory Installation: Install accessories with positive anchorage to building and weathertight mounting, and provide for thermal expansion. Coordinate installation with flashings and other components. 1. Install components required for a complete metal panel system including trim, copings, corners, seam covers, flashings, sealants, gaskets, fillers, closure strips, and similar items. Provide types indicated by metal panel manufacturer; or, if not indicated, provide types recommended by metal panel manufacturer. 3.4 ERECTION TOLERANCES A. Installation Tolerances: Align metal wall backup panel system within installed tolerance of 1/4 inch in 20 feet (6 mm in 6.1 m), noncumulative, on level and plumb and location lines as indicated and within 1/8 inch (3 mm) offset of adjoining faces and of alignment of matching profiles. A. Remove temporary protective coverings and strippable films, if any, as metal panels are installed, unless otherwise indicated in manufacturer's written installation instructions. On completion of metal panel installation, clean finished surfaces as recommended by metal panel manufacturer. Maintain in a clean condition during construction. B. After metal panel installation, clear weep holes and drainage channels of obstructions, dirt, and sealant. NBBJ Project No. 100822.06 074219-6 Reference: Comment #11 Swedish Edmonds Ambulatory Care Center SECTION 074219 Construction Documents INSULATED METAL PANEL 10 June 2014 BACKUP WALL ASSEMBLIES C. Replace metal panels that have been damaged or have deteriorated beyond successful repair by finish touchup or similar minor repair procedures. END OF SECTION NBBJ Project No. 100822.06 074219-7 International Building Code and Commentary Volume I, 2012 Reference: Comment #45 Page 1 of 1 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY constructed with a fire barrier or fire wall would con- stitute an exit (see Section 1025); however, moving through a smoke barrier into another smoke compart- ment is not a horizontal exit and therefore corridor continuity must be maintained on both sides of the smoke barrier. To address the various operational requirements of occupancies classified as Group 1-2, the code includes provisions that both permit various areas to be open to corridors and address suite arrangements of the exit access portions of the facilities. Standards for areas open to corridors are covered primarily in this chapter. The design of suites is regulated by pro- visions found in Section 407.4.3. For the ease of operations of hospitals, it is often desirable to have certain areas open to exit access corridors. Recognizing these needs and that such areas are equipped throughout with an automatic sprinkler system, the code permits specific areas to be open to corridors, provided they are properly arranged and equipped with compensating protection features (e.g., automatic fire detection). Sections 407.2.1 through 407.2.4 identify those areas and the protection features required to maintain the safety of the corridor. In addition to practical reasons, such as in the case of care providers' stations, it is also desirable to des- ignate certain areas being open to the corridor for treatment purposes. In many instances, the care recipient is encouraged to leave the sleeping room for both physical as well as social benefit. So that care recipients can be encouraged to socialize and benefit from group activities and social interaction, the areas need to be open to the corridor. Such waiting areas also serve a useful purpose during a fire emergency. If evacuation becomes nec- essary, care recipients usually will be relocated to an adjacent smoke compartment in which the areas open to the corridor will serve as a refuge area. Sec- tion 407.5.1 contains provisions for the net area that must be available for the relocation of care recipients. Waiting areas provide a space in which care recipi- ents can be relocated such that treatment can con- tinue during a fire emergency. 407.2.1 Waiting and similar areas. Waiting areas and simi- lar spaces constructed as required for corridors shall be per- mitted to be open to a corridor, only where all of the following criteria are met: 1. The spaces are not occupied as care recipient's sleeping rooms, treatment rooms, incidental uses in accordance with Section 509, or hazardous uses. 2. The open space is protected by an automatic fire detec- tion system installed in accordance with Section 907, 3. The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic fire detection system installed in accordance with Section 907, or the smoke comparonent in which the spaces are located is equipped throughout with quick -response sprinklers in accordance with Section 903.3.2. 2012 INTERNATIONAL BUILDING CODE® COMMENTARY 4. The space is arranged so as not to obstruct access to the required exits. f• In the design of health care facilities, it is desirable to have small waiting areas and similar spaces open to the corridor. Such seating areas or gathering spaces provide care recipients and others a place to sit out- side of the sleeping rooms or to wait near special care areas for their turn in a treatment room. In con- sideration of the additional protection features speci- fied, small waiting areas and similar spaces are permitted to be open to corridors in Group 1-2 occu- pancies within each smoke compartment provided they are constructed to the corridor standards for Group 1-2 occupancies, as specified in Section 407.3. Care recipient sleeping rooms, treatment rooms, as well as hazardous and incidental use areas, cannot be open to the corridors under this section. This con- figuration is commonly found in a typical ward situa- tion. The exception would be treatment areas for psychiatric wards addressed in Section 407.2.3 and the care suite provisions in Section 407.4.3. Areas similar to waiting rooms could include common visit- ing areas, reception or information stations and patient check-in stations. General hospital office areas or support spaces beyond those associated with waiting or reception areas must separated from the corridor (see Figure 407.2.1). To reduce the likelihood that a fire within such an open space could develop beyond the incipient stage, thereby jeopardizing the integrity of the corri- dor, the area is to be equipped with an automatic fire detection system (see Section 907). The detectors are to be located so as to provide the appropriate coverage to the space. There is no size limit set by the code for these spaces. Due to the unlimited size of the space and consequently the potential for a significant number of people in the area, an automatic fire detection system is also required in all corridors open to the spaces within the smoke compartment, or the smoke com- partment in which such spaces are located must be protected throughout with quick -response sprinklers. Waiting areas and similar spaces open to corridors must be arranged so as to not obstruct access to exits. There must be a clear path of travel of the mini- mum required width for the corridor, which should be maintained at all times. As such, furniture layouts -must be arranged in a manner that obstruction of the 807.2.2 Care providers' stations. Spaces for care provid- ers', supervisory staff, doctors' and nurses' charting, cormnu- itications and related clerical areas shall be permitted to be open to the corridor, where such spaces are constructed as required for corridors. Stations for care providers need to be located to pro- vide quick access to care recipients and to permit visual or audible monitoring of the sleeping rooms. For these and other practical reasons, care providers' stations are permitted to be open to the corridor, pro- vided the walls surrounding the area are constructed as required for corridor walls (see Figure 407.2.2). 4-53 httn-Hwww_mndc2d.com//Iihr2ry/9naue=P2p,ei-nrintet-&,bid=l 74975kn=234 6/10/2014 International Building Code and Commentary Volume 1, 2012 Reference: Comment #45 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY Except as required in Section 407.8, the additional protection of automatic fire detection is not required because of the reduced risk to life safety and atten- dance by the staff (see Section 407.8). This section is not intended to apply to nurses' offices, administra- tive supply storage areas, drug distribution stations or similar areas with a higher fuel load and from which Page 1 of 1 continual observation of the nursing unit is not essen- atric care recipients who are not capable of self-preservation are housed, or group meeting or multipurpose therapeutic spaces other than incidental uses in accordance with Section 509, under continuous supervision by facility staff, shall be OFFICE OFFICE OFFI - - ---------- - SMOKE PARTITION rSD'. - -- ------------ ' i WAITING AREA j EXIT ' SEE SECTION 407.2.3 L5WS] SEE SECTIO 407.2.4 EXIT SDj AUTOMATIC FIRE DETECTION (SEE SECTION 907) For SI: 1 square foot = 0.0929 m2. 4.54 Figure 407.2.1 GROUP 1-2: WAITING ROOMS AND SIMILAR AREAS _- SMOKE PARTITIONS PATIENT ROOM (TYPICAL) STAFF LOUNGE SMOKE ' --�`------ BARRIER CARE PROVIDER/ NURSES'-- '----------------- � STATION -------------------- ' � I PATIENT ROOM (TYPICAL) ,SPt FIRE DETECTION (SEE SECTION 407.8) Figure 407.2.2 GROUP 1-2: CARE PROVIDERS' STATION 2012 INTERNATIONAL BUILDING CODE® COMMENTARY l,ffn•/Ai ni mort—>t f,/ )r,P)01 A