response to bldg comments 1 (2).pdf14 1....P 4 A S 1 8, 0 S IJ W ip.g, 1, 9,$ 1_0 1, p, 0 2 2 0 2 0,
A P C H � I IF, C 1 5 IRWE
Ifl, A 08 2016
Response: a) Please refer to sheet A.2A. 1 for a revision to the existing door intoA14014 ON WN, 17
as required to provide clearances per ICC Al 17.2-2009 Section 404.2.3.
b) Please refer to sheet G.0.0 - Key Plan regarding the required toilet facility installations
meeting the requirements of IBC 3411.7/Table 2902.1/1109.2 and ICC Al 17.1-2009
section 603.1
c) Please refer to sheet G.0.0 - Key Plan regarding the required drinking fountain(s)
installation to meet both the accessible and standing spout outlet height requirements
of IBC 3411.7/2902.5.1/1109.5.1 and ICC Al 17.1-2009 section 602.4
On sheet A.M. I - Reflected Ceiling Plans:
3. Reflected Ceiling Plans - Second Floor - Provide as part of a complete submittal Washington
State Energy Code (WSEC) Compliance Forms for Commercial Buildings for the proposed
lighting installation. WSEC C 103.2 requires that the lighting fixture schedule with wattage and
control narrative also be shown on the plans. These items may be provided as a deferred
submittal, but must be received and approved prior to any 'cover' inspections, such as
'Ceiling Grid' or 'Framing', being performed.
Response: Please refer to sheet A.2B. I Reflected Ceiling Plan for annotations pertaining to the deferred
submittal for this project. The electrical contractor on the project will be making a deferred submittal to
include:
• WSEC Compliance Forms for Commercial Buildings.
• Light Fixture Schedule, including wattages.
• Light fixture control narrative.
On sheet A.M. I - Power & Data/Furniture Floor Plan:
4. Power & Data/Furniture & Finish Plan - Indicate on the plans the proposed locations of all fixed
equipment, counters, shelving, storage racks, etc. in space '202' - Work Area - and space
'208'- Work Room' to guide proper review. Shelving/racks that exceed 6 feet in height must
be seismically anchored.
Response: Please refer to sheet A.21D. 1 - Power & Data/Furniture Floor Plan showing general layout of
Tenant provided storage and work surfaces in space '202' and '208'. Shelving and/or racks exceeding
6' in height are not anticipated. Notation regarding the need for seismic bracing for shelving/racks
over 6' in height has been added to the plans.
Please feel free to contact me if you have any further questions or concerns.