BUILDING DEPARTMENT Comment Response
��'ry nr-1"1AA/"1A11'1Q
Date: June 6, 2018
To: Chuck Miller, Senior Plans Examiner, City of Edmonds
From: Thaddeus Egging, KPFF and Joseph Mangan, Pacific Mobile Project Engineer
Subject: Sherwood Elementary School Portable Classroom "A" (Permit # BLD2018-0470)
Comment Responses
The following comment responses are in response to Building Plan Review comments dated
May 11, 2018 prepared by Chuck Miller (attached for reference):
1. COMMENT: On Sheet A20.1-Pacific Mobile Foundation Designs: Clarify on the plans
the difference in the represented construction/connections and of that specified in the
provided structural calculations. Of particular concern are the lateral design elements
noted in Division 'II'— Foundation Design — Section `E' — Lateral Design — of the
calculations that to not appear on the plans.
RESPONSE: Differences between the submitted calculations page and foundation
drawing (A20.1) have been resolved. Revised sheet A20.1 and revised structural
calculations have been attached. Specific resolutions are highlighted and explanations
given in clouds. Note A highlights 7/16" sheathing prescribed by the calculations page
while thicker 1/2" sheathing is described in the drawing. The note also points to the
calculations having 16" o.c. fastener spacing while the plans show 12" o.c. The thicker
sheathing and closer fastener spacing should provide more strength and not be a
problem. Note B highlights 5/8" diameter anchor bolts on both the calculations and
drawings page. The drawing page gives options for 5/8" diameter anchor fasteners all
satisfying the requirements given by the calculations page.
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: May 11, 2018
TO: Will Thomsen
thomsenWCt)cdnxmds.N\ ediiet.edu
FROM: Chuck Miller, Senior Plans Examiner
chuck.]Ili llcrLaocdi»ondswa.gov
RE: Plan Check: BLD2018-0470 - 1st review
Project Address: 22901 106th Avenue W
Project: ESD Sherwood Elementary relocatable classroom `A'
Scope: Siting, connection, support, and lateral restraint of manufactured classroom
structure — nonseparated Education Group E occupancy — 42 occupants — VB
construction — no sprinkler system — fire alarm under separate permit
Please be advised that the building plans for the above referenced project have been disapproved
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
information, clarifications, or changes are needed. Reviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter.
A complete review cannot be performed until the revised plans/documents, including, a
written response in itemized letter format indicating„ where the `clouded' or otherwise
hi,_,hli<(hted chan(_Yes can be found on the revised plans, have been submitted to a Permit
Coordinator. Only those sheets specifically referenced as follows need to be resubmitted.
Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
On sheet A20.1 — Pacific Mobile Foundation Designs:
1. Clarify on the plans the difference in the represented construction/connections and of that
specified in the provided structural calculations. Of particular concern are the lateral design
elements noted in Division `II' - Foundation Design — Section `E' — Lateral Design — of the
calculations that to not appear on the plans.